SM-18001-rev.1
5-23
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
*1): The “02” setting may not be available according to the type of indoor unit.
*2): In case that the set temperature is changed and the temperature is kept for a specific time set by “F4”, it
automatically changes to the temperature set by “F5” or “F6.” (In case that the set temperature of “F5” and “F6”
is out of range, the upper or lower limit temperature is applied.)
*3): Applicable to fan, cooling and dry operation modes.
*4): Applicable to heating operation mode.
*5): Operation is stopped by pressing the “ ” (On/Off) button for 3 seconds.
*6): The sensor value at “C8” is indicated. When the thermistor for wired controller is used, the average value of
the thermistor for wired controller and the thermistor for indoor inlet is indicated.
*7): When the unit is restarted by the wired controller, the temperature automatically changes to the setting
temperature of “F5” or “F6”.
*8): Be sure to use only the "00" setting condition when combining optional function settings, "q4" and "q5," with
a water source unit. The water source unit detects entering water temperature instead of outdoor ambient
temperature. This setting does not function.
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
144
S5 Not Prepared
-
-
Not Used
145
S6 Not Prepared
-
-
Not Used
146
S7 Not Prepared
-
-
Not Used
147
S8 Not Prepared
-
-
Not Used
NOTES:
1. Wait at least 3 minutes from initial power ON to change the optional setting.
2. When changing “CF” setting (“Change of Louver Swing Angle”), restore the power supply or test the louver
swing a couple of times in the auto swing mode to validate the setting.
3. The optional settings are different according to the indoor and outdoor unit models.
Check to ensure if the unit has the optional setting or not.
4. The above optional functions with “X” mark at the individual setting can change the condition only when “All
Rooms” is selected in the Test Run Menu > Function Selection Menu.
5. Function selection items "L9" and "q1" to "S8" are available only for indoor units and wired controllers with
new software applied. Check to ensure if the unit has the optional setting or not.
Содержание CIDH018B21S
Страница 2: ......
Страница 10: ...viii SM 18001 rev 1...
Страница 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Страница 22: ......
Страница 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Страница 76: ...MAINTENANCE 4 2 SM 18001 rev 1 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 130: ......
Страница 131: ...SM 18001 rev 1 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 172: ......
Страница 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Страница 184: ...SERVICE PARTS LIST 7 2 SM 18001 rev 1 Refer to the Service Parts List for Ducted High Static Medium Static and Slim...
Страница 185: ......
Страница 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...