EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(132) Not Prepared (r4)
(133) Not Prepared (r5)
(134) Not Prepared (r6)
(135) Not Prepared (r7)
(136) Not Prepared (r8)
(137) Not Prepared (r9)
(138) Not Prepared (rA)
(139) Not Prepared (rb)
(140) Not Prepared (S1)
(141) Not Prepared (S2)
(142) Not Prepared (S3)
(143) Not Prepared (S4)
(144) Not Prepared (S5)
(145) Not Prepared (S6)
(146) Not Prepared (S7)
(147) Not Prepared (S8)
(131) Setback Temperature Compensation (During card key removal, setpoint is setbacked) (r3)
This function is utilized to change the indoor temperature condition to Thermo-ON/OFF.
In case the setback operation is enabled and the card key is removed, setpoint is compensated and
fan operate at “LOW” speed.
By default,
Cooling: Se4
o
F (+2.5
o
C)
Heating: Setpoint -4
o
F (-2.5
o
C)
When the external signal is detected (card key is inserted), return to the original setting temperature.
Setting Condition
Actual Control Temperature
00 (Standard)
Wired Controller Setting Temperature (Indicated Value) +4
o
F (2.5
o
C)
01
Wired Controller Setting Temperature (Indicated Value) +5
o
F (3.0
o
C)
02
Wired Controller Setting Temperature (Indicated Value) +6
o
F (3.5
o
C)
03
Wired Controller Setting Temperature (Indicated Value) +7
o
F (4.0
o
C)
04
Wired Controller Setting Temperature (Indicated Value) +8
o
F (4.5
o
C)
05
Wired Controller Setting Temperature (Indicated Value) +9
o
F (5.0
o
C)
06
Wired Controller Setting Temperature (Indicated Value) +10
o
F (5.5
o
C)
07
Wired Controller Setting Temperature (Indicated Value) +1
o
F (0.5
o
C)
08
Wired Controller Setting Temperature (Indicated Value) +2
o
F (1.0
o
C)
09
Wired Controller Setting Temperature (Indicated Value) +3
o
F (1.5
o
C)
10
Wired Controller Setting Temperature (Indicated Value) +3
o
F (2.0
o
C)
Compensation for setback operation can be changed as shown in the table below.
Содержание CIDH018B21S
Страница 2: ......
Страница 10: ...viii SM 18001 rev 1...
Страница 15: ...SM 18001 rev 1 1 1 INSTALLATION 1 Installation...
Страница 19: ...SM 18001 rev 1 2 1 OPERATION 2 Operation...
Страница 22: ......
Страница 23: ...SM 18001 rev 1 3 1 TROUBLESHOOTING 3 Troubleshooting...
Страница 75: ...MAINTENANCE SM 18001 rev 1 4 1 4 Maintenance...
Страница 76: ...MAINTENANCE 4 2 SM 18001 rev 1 4 1 Maintenance of Outdoor Unit Refer to the Service Manual for Outdoor Unit...
Страница 130: ......
Страница 131: ...SM 18001 rev 1 5 1 EXTERNAL INPUT OUTPUT AND FUNCTION SETTING 5 External Input Output and Function Setting...
Страница 172: ......
Страница 173: ...SM 18001 rev 1 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions...
Страница 182: ...6 10 SM 18001 rev 1 FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A f t 3 l b...
Страница 183: ...SERVICE PARTS LIST SM 18001 rev 1 7 1 7 Service Parts List...
Страница 184: ...SERVICE PARTS LIST 7 2 SM 18001 rev 1 Refer to the Service Parts List for Ducted High Static Medium Static and Slim...
Страница 185: ......
Страница 186: ...2018 Johnson Controls Inc SM 18001 rev 1 Code No LIT 12013047 Revised February 2019...