Unitary Products Group

17

036-21311-003-A-0104

FIELD WIRING DIAGRAM

ELECTRICAL DATA

(BASIC UNIT)

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE DIS-

CONNECT

REFER TO ELECTRICAL DATA

TABLES TO SIZE THE DIS-

CONNECT

POWER WIRING

R

G

W

R

C

Y

Y

W 2

C

W 1

O

O

G

24 VOLT TRANSFORMER

UNIT TERMINAL STRIP

THERMOSTAT

NOTE:
HEAT ANTICIPATOR
SHOULD BE SET AT 0.25
AMPS FOR ALL MODELS.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can

cause improper and dangerous operation. Verify proper operation after servicing.

PROGRAMMABLE

THERMOSTAT ONLY

** = Minimum wire size of 18 AWG

wire should be used for all field

installed 24 volt wire.

**

* = Only required on units with

supplemental electric heat.

*

CONTROL WIRING

MODEL

BHA

POWER SUP-

PLY

VOLTAGE

LIMITATIONS

1

COMPRESSOR

OUTDOOR

FAN

MOTOR,

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

AMPS

2

MAX.

HACR

BREAKER

SIZE,

AMPS

UNIT

POWER

FACTOR

TRANSFORMER

SIZE (VA)

MIN.

MAX.

RLA

LRA

018

208/230-1-60

187

253

9.0

48.0

1.1

2.6

14.9

20

20

.96

40

024

208/230-1-60

187

253

11.2

60.0

1.1

2.6

17.7

25

25

.96

40

030

208/230-1-60

187

253

12.0

73.0

1.1

2.6

18.7

25

25

.96

40

036

208/230-1-60

187

253

17.3

94.0

1.1

3.5

26.2

35

35

.96

40

042

208/230-1-60

187

253

20.5

120.0

1.1

3.5

30.2

40

40

.96

40

048

208/230-1-60

187

253

24.4

140.0

1.5

4.0

36.0

50

50

.96

40

060

208/230-1-60

187

253

28.9

165.0

1.5

7.0

44.6

60

60

.96

40

036

208/230-3-60

187

253

10.9

78.0

1.1

3.5

18.2

25

25

.96

75

042

208/230-3-60

187

253

14.1

110.0

1.1

3.5

22.2

30

30

.96

75

048

208/230-3-60

187

253

14.1

105.0

1.5

4.0

23.1

30

30

.96

75

060

208/230-3-60

187

253

16.0

125.0

1.5

7.0

28.5

40

40

.96

75

036

460-3-60

414

504

5.8

40.0

0.6

1.8

9.6

15

15

.96

75

042

460-3-60

414

504

7.1

54.0

0.6

1.8

11.2

15

15

.96

75

048

460-3-60

414

504

7.1

55.0

0.8

2.0

11.7

15

15

.96

75

060

460-3-60

414

504

8.0

67.0

0.8

3.5

14.3

20

20

.96

75

036

575-3-60

518

630

4.5

32.0

0.4

1.5

7.6

15

15

.96

75

042

575-3-60

518

630

5.8

44.0

0.4

1.5

9.1

15

15

.96

75

048

575-3-60

518

630

5.6

44.0

0.6

1.6

9.3

15

15

.96

75

060

575-3-60

518

630

6.4

50.0

0.6

2.8

11.4

15

15

.96

75

1

= Rated in accordance with ARI Standard 110, utilization range “A”.

2

= Dual element, time delay type.

ELECTRIC HEAT

CORRECTION

FACTORS

NOMINAL VOLTAGE

VOLTAGE

KW CAP. MULTI-

PLIER

240

208
230

.75
.92

480

460

.92

600

575

.92

Содержание Champion Series

Страница 1: ...currents air velocity and temperature and unit vibration are monitored and recorded by the system to insure unit performance Equal size side supply and return duct connections allows easy hook up of d...

Страница 2: ...o aids in sound alterations with it s Super Structure design This design strategically places embossments in the pan for optimum strength and rigidity FAN SYSTEM All models operate over a wide range o...

Страница 3: ...sup ply and one return air rectangle to round duct adapter Adapters are preformed and designed to fit over current duct openings on the base unit Transition is from 15 square to 14 round ROOF CURBS NR...

Страница 4: ...annual usage period for cooling divided by the total electric power input in watt hours during the same period COP Coefficient of Performance the total heating capacity provided by the refrigeration...

Страница 5: ...2 23 2 16 2 11 2 12 Sensible Capacity MBH 1 Entering Dry Bulb F 86 10 9 13 4 13 9 13 8 12 3 14 8 14 4 14 3 13 6 16 3 14 9 14 8 14 9 17 1 15 3 15 2 16 2 17 9 15 7 15 6 83 9 6 12 1 13 6 13 5 10 7 13 5...

Страница 6: ...4 Sensible Capacity MBH 1 Entering Dry Bulb F 86 13 9 17 3 17 9 17 9 15 5 18 8 18 5 18 4 17 1 20 3 19 1 19 0 18 6 21 0 19 4 19 4 20 1 21 6 19 8 19 8 83 12 2 15 6 17 6 17 6 13 5 17 3 18 4 18 3 14 8 19...

Страница 7: ...Capacity MBH 1 Entering Dry Bulb F 86 17 6 21 9 22 5 22 6 19 5 23 6 23 0 23 0 21 5 25 3 23 5 23 5 23 5 26 1 23 9 24 0 25 5 26 9 24 4 24 4 83 15 5 19 8 22 2 22 3 17 0 21 7 22 8 22 9 18 5 23 5 23 5 23 5...

Страница 8: ...Entering Dry Bulb F 86 21 0 25 8 25 1 23 7 23 9 28 4 27 0 25 5 26 9 31 1 28 8 27 2 29 5 32 9 30 0 28 3 32 1 34 6 31 2 29 5 83 18 5 23 2 25 1 23 7 20 9 26 2 27 0 25 5 23 4 29 3 28 8 27 2 25 5 31 3 30...

Страница 9: ...H 1 Entering Dry Bulb F 86 23 4 29 0 27 9 25 3 26 5 31 9 30 1 27 3 29 6 34 8 32 3 29 3 32 0 35 8 32 7 29 7 34 4 36 9 33 1 30 1 83 20 4 26 0 27 9 25 3 23 0 29 2 30 1 27 3 25 5 32 3 32 3 29 3 27 3 33 9...

Страница 10: ...lb F 86 28 3 35 7 38 8 36 8 31 6 39 3 40 0 38 0 34 9 43 0 41 3 39 2 38 2 44 7 42 1 40 0 41 4 46 5 43 0 40 9 83 24 8 32 3 36 9 36 0 27 5 35 7 39 1 37 6 30 2 39 1 41 3 39 2 32 8 42 0 42 1 40 0 35 4 44 8...

Страница 11: ...5 44 3 46 6 45 4 38 4 48 2 47 8 46 5 42 3 52 2 48 9 47 6 43 7 53 1 49 6 48 3 45 1 54 1 50 3 48 9 83 30 3 40 0 45 7 44 6 33 4 44 1 47 3 46 1 36 5 48 1 48 9 47 6 37 5 49 3 49 6 48 3 38 5 50 6 50 3 48 9...

Страница 12: ...2 543 15 457 19 060 23 517 29 028 KW 1 428 1 581 1 733 1 886 2 038 2 190 2 343 2 495 1 These capacities are net capacities the indoor motor heat has been added These power inputs are total power input...

Страница 13: ...2 25 624 30 154 35 507 41 834 KW 2 566 2 694 2 822 2 950 3 078 3 206 3 335 3 463 1 These capacities are net capacities the indoor motor heat has been added These power inputs are total power inputs th...

Страница 14: ...ities the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added HEATING CAPACITIES 4 TON BHA048 CFM RETURN AIR CAP1 OUTDOOR AIR TEMPERATURE...

Страница 15: ...N DATA MODEL BHA 018 024 030 036 042 048 060 MINIMUM AIR FLOW CFM COOLING 450 600 750 900 1 050 1 200 1 500 HEATING 450 600 750 900 1 050 1 200 1 500 MAXIMUM AIR FLOW CFM COOLING 750 1 000 1 250 1 500...

Страница 16: ...788 691 1739 1652 1528 940 752 677 NOTE Above data includes allowances for a dry indoor coil and no filters For additional pressure drops refer to the Additional Static Pressure Resistance table MODEL...

Страница 17: ...253 11 2 60 0 1 1 2 6 17 7 25 25 96 40 030 208 230 1 60 187 253 12 0 73 0 1 1 2 6 18 7 25 25 96 40 036 208 230 1 60 187 253 17 3 94 0 1 1 3 5 26 2 35 35 96 40 042 208 230 1 60 187 253 20 5 120 0 1 1 3...

Страница 18: ...88 1 103 7 114 1 126 3 140 2 148 8 166 2 90 100 110 125 150 150 150 175 90 100 110 125 150 150 150 175 060 208 230 1 60 28 9 165 0 1 5 7 0 2NH04501006 2NH04501506 2NH04502006 2NH04502506 2 2 2 2 7 5...

Страница 19: ...25 0 9 6 14 4 19 2 24 1 21 3 27 3 33 3 39 3 25 30 35 40 25 30 35 40 060 575 3 60 6 4 50 0 0 6 2 8 2NH04501058 2NH04501558 2NP04502058 2NP04502558 1 1 2 2 10 0 15 0 20 0 25 0 9 6 14 4 19 2 24 1 23 4 2...

Страница 20: ...LTAGE CONN 7 8 DIA KNOCKOUT HIGH VOLTAGE CONN 131 32 DIA KNOCKOUT FRONT ELECTRICAL FILTER SERVICE ACCESS COMPARTMENT PANEL OVERALL OVERALL 4 1 2 11 2 2 1 2 All dimensions are in inches They are subjec...

Страница 21: ...S THEREAFTER FOR ALL OTHER HEATERS ZERO INCH CLEARANCE ALL SIDES FOR ENTIRE LENGTH OF DUCT FLEXIBLE DUCT COLLAR NOTE FOR UNITS APPLIED WITH A ROOF CURB THE MINIMUM CLEARANCE MAY BE REDUCED FROM 1 INCH...

Страница 22: ...FIELD SUPPLIED DISCONNECT SWITCH LOCATED TO REAR OF UNIT CONTROL WIRING TO INDOOR THERMOSTAT ROOF CURB INSTALLATION REAR DUCT SLAB ON GROUND INSTALLATION ROOF CURB INSTALLATION BOTTOM DUCT TYPICAL ROO...

Страница 23: ...F CURB DIMENSIONS 8 roof curb also available UNIT BASE RAIL UNIT BASE WOOD NAILER 8 MIN ABOVE FINISHED ROOF CURB FRAME COUNTERFLASHING INSULATION CANT STRIP ROOF DECK AND ROOFING MATERIAL INSULATION A...

Страница 24: ...PR 708 PR 716 PR 716 PR 713 PR 713 PR 710 PR 710 PR F6 F6 F4 F4 F2 F2 K6 K6 K4 K4 K5 K5 K3 K3 M1 M1 714 BK 714 BK 706 BK 706 BK 711 BK 711 BK 703 BK 703 BK 709 BK 709 BK F1 F1 F3 F3 F5 F5 DUAL POINT E...

Страница 25: ...ts Group 25 036 21311 003 A 0104 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY M R C COMPR RELAY DFST STAT M1 DETAIL A 222 Y BLU BLU DS DEFROST CONTROL 031 01268 000B FOR DEFROST CONTROL 031 09104 000A...

Страница 26: ...R 2 1 2 R C T 1 1 0 9 B K 2 4 V 1 0 8 P R 4 8 0 O R 6 0 0 2 1 4 B R 8 D 7 E A B K 3 8 1 3 B R 8 1 4 Y L 2 L 2 L 2 1 2 3 H 1 L 1 L 1 L 1 K 1 2 0 9 R K 2 F A N C O N T R O L B O A R D T L H F L H 4 1 2...

Страница 27: ...FAN MOTOR K2 RELAY ELECTRIC HEATER K3 RELAY ELECTRIC HEATER 24V DC COIL K7 RELAY LIMIT TRIP 24V DC COIL LP LOW PRESSURE SWITCH OPTIONAL ACCESSORY OPEN 7 PSIG LS LIMIT SWITCH ELECTRIC HEAT PART OF ELEC...

Страница 28: ...uilding structure duct work and base unit 10 Condensate pan shall be internally sloped and conform to ASHRAE 62 89 self draining standards with 3 4 NPTI copper ridged mount connection INDOOR SUPPLY FA...

Страница 29: ...tion with nickel chromium ele ments shall be provided in a range of 5 thru 25 KW offer ing two stages of capacity 7 KW and above on single phase heaters and one 20 KW and above on three phase heaters...

Страница 30: ...30 Unitary Products Group 036 21311 003 A 0104...

Страница 31: ...Unitary Products Group 31 036 21311 003 A 0104...

Страница 32: ...Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by York International Corporation 2004 All Rights Reserved 036 21311 003 A 0104 Supersedes 036...

Отзывы: