036-21311-003-A-0104
6
Unitary Products Group
COOLING CAPACITIES -
2 TON (BHA024)
Temperature of Air on
Outdoor Coil
Air On Indoor Coil
600 CFM
700 CFM
800 CFM
900 CFM
1,000 CFM
WB
°
F
WB
°
F
WB
°
F
WB
°
F
WB
°
F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
85 °F
Net Cap
MBH
25.3 23.1 20.8 20.8 26.4 24.1 21.7 21.6 27.4 25.0 22.5 22.5 28.1 25.6 23.1 23.0 28.7 26.2 23.6 23.5
Total Power
Input kW
2.21 2.18 2.14 2.12 2.26 2.23 2.18 2.16 2.30 2.27 2.22 2.20 2.33 2.30 2.25 2.22 2.35 2.32 2.27 2.25
Sensible
Cap
acity
MBH
1
Entering
Dry
Bulb,
°
F
86 15.1 18.8 20.8 20.8 16.7 20.9 21.7 21.6 18.4 22.9 22.5 22.5 19.9 24.5 23.1 23.0 21.4 26.2 23.6 23.5
83 13.4 17.1 20.1 20.6 14.7 18.8 21.3 21.5 16.1 20.6 22.5 22.5 17.3 22.0 23.1 23.0 18.5 23.5 23.6 23.5
80
11.6 15.4 18.4 18.9 12.7 16.8 20.0 20.6 13.8 18.2 21.7 22.3 14.6 19.4 22.6 22.9 15.5 20.5 23.6 23.5
77
9.9 13.7 16.7 17.2 10.7 14.8 18.0 18.6 11.4 15.9 19.4 20.0 12.0 16.7 20.0 20.3 12.5 17.5 20.6 20.5
74
8.2 12.0 14.9 15.4 8.7 12.8 16.0 16.5 9.1 13.6 17.1 17.6 9.3 14.0 17.3 17.6 9.5 14.5 17.6 17.6
71
-
10.3 13.2 13.7
-
10.8 14.0 14.5
-
11.2 14.7 15.3
-
11.4 14.7 14.9
-
11.5 14.6 14.6
68
-
8.6 11.5 12.0
-
8.7 12.0 12.5
-
8.9 12.4 13.0
-
8.7 12.0 12.3
-
8.6 11.7 11.6
95 °F
Net Cap
MBH
24.3 21.6 19.3 19.3 25.2 22.4 20.0 20.0 26.0 23.2 20.6 20.7 26.5 23.6 21.0 21.1 26.9 24.0 21.4 21.4
Total Power
Input kW
2.37 2.32 2.26 2.24 2.42 2.37 2.31 2.29 2.47 2.42 2.36 2.34 2.50 2.44 2.38 2.36 2.53 2.47 2.40 2.39
Sensible
Cap
acity
MBH
1
Entering
Dry
Bulb,
°
F
86 14.7 18.2 19.3 19.3 16.3 20.2 20.0 20.0 18.0 22.2 20.6 20.7 19.4 23.1 21.0 21.1 20.9 24.0 21.4 21.4
83 13.0 16.5 19.1 19.2 14.3 18.2 19.9 20.0 15.6 19.8 20.6 20.7 16.8 21.2 21.0 21.1 17.9 22.6 21.4 21.4
80
11.3 14.8 17.4 17.5 12.3 16.2 19.0 19.1 13.3 17.5 20.5 20.7 14.1 18.5 20.9 21.1 14.9 19.6 21.4 21.4
77
9.6 13.1 15.7 15.8 10.3 14.1 16.9 17.1 11.0 15.2 18.2 18.3 11.4 15.9 18.3 18.4 11.9 16.6 18.4 18.5
74
7.9 11.4 14.0 14.1 8.2 12.1 14.9 15.1 8.6 12.8 15.9 16.0 8.8 13.2 15.6 15.7 8.9 13.6 15.4 15.5
71
-
9.7 12.3 12.4
-
10.1 12.9 13.0
-
10.5 13.5 13.7
-
10.6 13.0 13.1
-
10.7 12.4 12.5
68
-
8.0 10.6 10.7
-
8.1 10.9 11.0
-
8.2 11.2 11.3
-
7.9 10.3 10.4
-
7.7
9.4
9.5
105 °F
Net Cap
MBH
22.2 19.5 17.9 17.9 23.0 20.2 18.5 18.4 23.7 20.8 19.1 19.0 24.1 21.2 19.4 19.4 24.6 21.6 19.8 19.8
Total Power
Input kW
2.53 2.45 2.41 2.39 2.58 2.51 2.46 2.44 2.64 2.56 2.51 2.49 2.67 2.59 2.54 2.52 2.70 2.62 2.57 2.54
Sensible
Cap
acity
MBH
1
Entering
Dry
Bulb,
°
F
86 13.9 17.3 17.9 17.9 15.5 18.8 18.5 18.4 17.1 20.3 19.1 19.0 18.6 21.0 19.4 19.4 20.1 21.6 19.8 19.8
83 12.2 15.6 17.6 17.6 13.5 17.3 18.4 18.3 14.8 19.0 19.1 19.0 16.0 19.9 19.4 19.4 17.1 20.9 19.8 19.8
80 10.4 13.9 15.9 15.9 11.5 15.3 17.5 17.5 12.5 16.6 19.0 19.0 13.3 17.7 19.4 19.4 14.1 18.8 19.8 19.8
77
8.7 12.2 14.2 14.2 9.4 13.2 15.4 15.4 10.1 14.3 16.7 16.7 10.6 15.1 16.8 16.7 11.1 15.8 16.8 16.8
74
7.0 10.5 12.5 12.5 7.4 11.2 13.4 13.4 7.8 12.0 14.4 14.3 8.0 12.4 14.1 14.1 8.2 12.9 13.9 13.8
71
-
8.8 10.8 10.8
-
9.2 11.4 11.4
-
9.6 12.0 12.0
-
9.8 11.4 11.4
-
9.9 10.9 10.8
68
-
7.1
9.1
9.1
-
7.2
9.4
9.4
-
7.3
9.7
9.7
-
7.1
8.8
8.8
-
6.9
7.9
7.8
115 °F
Net Cap
MBH
20.2 17.4 16.6 16.4 20.8 17.9 17.0 16.9 21.3 18.4 17.5 17.3 21.8 18.8 17.9 17.7 22.3 19.2 18.3 18.1
Total Power
Input kW
2.69 2.59 2.56 2.53 2.75 2.64 2.61 2.58 2.80 2.70 2.67 2.64 2.84 2.73 2.70 2.67 2.87 2.77 2.73 2.70
Sensible
Cap
acity
MBH
1
Entering
Dry
Bulb,
°
F
86 13.0 16.4 16.6 16.4 14.7 17.4 17.0 16.9 16.3 18.4 17.5 17.3 17.8 18.8 17.9 17.7 19.3 19.2 18.3 18.1
83
11.3 14.7 16.2 16.0 12.7 16.4 16.8 16.7 14.0 18.1 17.5 17.3 15.2 18.7 17.9 17.7 16.3 19.2 18.3 18.1
80
9.6 13.0 14.4 14.3 10.6 14.4 16.0 15.8 11.7 15.8 17.5 17.3 12.5 16.9 17.9 17.7 13.4 18.0 18.3 18.1
77
7.9 11.3 12.7 12.6 8.6 12.4 14.0 13.8 9.3 13.4 15.2 15.0 9.9 14.2 15.2 15.1 10.4 15.1 15.3 15.1
74
6.2
9.6 11.0 10.9 6.6 10.3 11.9 11.8 7.0 11.1 12.8 12.7 7.2 11.6 12.6 12.4 7.4 12.1 12.3 12.1
71
-
7.9
9.3
9.2
-
8.3
9.9
9.8
-
8.8 10.5 10.3
-
8.9
9.9
9.7
-
9.1
9.3
9.2
68
-
6.2
7.6
7.5
-
6.3
7.9
7.7
-
6.4
8.2
8.0
-
6.3
7.3
7.1
-
6.1
6.4
6.2
125 °F
Net Cap
MBH
18.1 15.4 15.2 14.9 18.5 15.7 15.6 15.3 19.0 16.1 16.0 15.7 19.4 16.5 16.3 16.0 19.9 16.9 16.7 16.4
Total Power
Input kW
2.8
2.7
2.7
2.7
2.9
2.8
2.8
2.7
3.0
2.8
2.8
2.8
3.0
2.9
2.9
2.8
3.0
2.9
2.9
2.9
Sensible
Cap
acity
MBH
1
Entering
Dry
Bulb,
°
F
86 12.2 15.5 15.2 14.9 13.9 16.0 15.6 15.3 15.5 16.6 16.0 15.7 17.0 16.7 16.3 16.0 18.5 16.9 16.7 16.4
83 10.5 13.8 14.7 14.4 11.8 15.5 15.3 15.0 13.2 17.2 16.0 15.7 14.4 17.4 16.3 16.0 15.6 17.6 16.7 16.4
80
8.8 12.1 13.0 12.7 9.8 13.5 14.5 14.2 10.8 14.9 16.0 15.7 11.7 16.1 16.4 16.0 12.6 17.3 16.7 16.4
77
7.1 10.4 11.3 11.0 7.8 11.5 12.5 12.2 8.5 12.6 13.7 13.3 9.1 13.4 13.7 13.4 9.6 14.3 13.8 13.4
74
5.4
8.7
9.5
9.3
5.8
9.4 10.4 10.1 6.2 10.2 11.3 11.0 6.4 10.8 11.1 10.7 6.6 11.3 10.8 10.5
71
-
7.0
7.8
7.6
-
7.4
8.4
8.1
-
7.9
9.0
8.7
-
8.1
8.4
8.1
-
8.3
7.8
7.5
68
-
5.2
6.1
5.8
-
5.4
6.4
6.1
-
5.6
6.7
6.3
-
5.5
5.7
5.4
-
5.3
4.8
4.5
1
= These capacities are net capacities - indoor fan heat deducted.