background image

Johnson Controls Unitary Products

7

256819-YTG-J-1208

*

May be 0 (no breaker) or 1 (with breaker). 

ELECTRICAL DATA (FOR SINGLE SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60

Models

Heat Kit - 

Single Phase*

Heater

Amps

240V

Field Wiring

Min. Circuit Ampacity

Max. O.C.P.

 

Amps/Type

1

75

°

C Wire Size - AWG

208V

230V

208V

230V

208V

230V

AVY24B**H21

4HK*6500206

10.4

15.28

16.53

20

20

12

12

4HK*6500506

20.0

25.67

28.50

30

30

10

10

4HK*6500806

31.3

37.85

42.63

45

45

8

8

4HK*6501006

40.0

47.33

53.50

50

60

8

6

4HK165N1506

60.0

69.00

78.50

70

90

4

3

AVY36C**H21

4HK*6500506

20.0

27.54

30.38

30

35

10

10

4HK*6500806

31.3

39.73

44.50

45

45

8

8

4HK*6501006

40.0

49.21

55.38

50

60

8

6

4HK16501506

60.0

70.88

80.38

70

90

4

3

4HK16501806

73.3

85.32

97.00

90

100

4

3

AVY48D**H21

SVY48D**N21

4HK*6500506

20.0

29.29

31.88

35

35

8

8

4HK*6500806

31.3

41.48

46.00

45

50

8

8

4HK*6501006

40.0

50.96

56.88

60

60

6

6

4HK16501506

60.0

72.63

81.88

90

90

3

3

4HK16501806

73.3

87.07

98.50

90

100

3

2

4HK16502006

80.0

94.29

106.88

100

125

3

1

4HK16502506

100.0

115.96

131.88

125

150

1

1/0

AVY60D**H21

SVY60D**N21

4HK*6500506

20.0

31.42

33.75

35

35

8

8

4HK*6500806

31.3

43.60

47.88

45

50

8

8

4HK*6501006

40.0

53.08

58.75

60

60

6

6

4HK16501506

60.0

74.75

83.75

90

90

3

3

4HK16501806

73.3

89.19

100.38

90

110

3

2

4HK16502006

80.0

96.42

108.75

100

125

3

1

4HK16502506

100.0

118.08

133.75

125

150

1

1/0

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

ELECTRICAL DATA (FOR MULTI SOURCE POWER SUPPLY) - COPPER WIRE 208/230-1-60

Models

Heater

Model

Min. Circuit Ampacity

Max. O.C.P.

 

Amps/Type

1

75

°

C Wire Size - AWG

Circuit

Circuit

Circuit

1st

2nd

3rd

1st

2nd

3rd

1st

2nd

3rd

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

AVY24B**H21

4HK165N1506

47.5 / 53.5

21.7 / 25.0

50 / 60

25 / 25

8 / 6

10 / 10

AVY36C**H21

4HK16501506

48.5 / 55.4

21.7 / 25.0

50 / 60

25 / 25

8 / 6

10 / 10

4HK16501806

44.9 / 51.2

39.8 / 45.8

45 / 60

40 / 50

8 / 8

8 / 8

AVY48D**H21

SVY48D**N21

4HK16501506

51.0 / 56.9

21.7 / 25.0

60 / 60

25 / 25

6 / 6

10 / 10

4HK16501806

47.4 / 52.7

39.8 / 45.8

50 / 60

40 / 60

6 / 6

8 / 6

4HK16502006

51.0 / 56.9

43.4 / 50.0

60 / 60

45 / 50

6 / 6

8 / 8

4HK16502506

51.0 / 56.9

43.4 / 50.0

21.7 / 25.0

60 / 60

45 / 50

25 / 25

6 / 6

8 / 8

10 / 10

AVY60D**H21

SVY60D**N21

4HK16501506

53.1 / 58.8

21.7 / 25.0

60 / 60

25 / 25

6 / 6

10 / 10

4HK16501806

49.5 / 54.6

39.8 / 45.8

50 / 60

40 / 60

6 / 6

8 / 6

4HK16502006

53.1 / 58.8

43.4 / 50.0

60 / 60

45 / 50

6 / 6

8 / 8

4HK16502506

53.1 / 58.8

43.4 / 50.0

21.7 / 25.0

60 / 60

45 / 50

25 / 25

6 / 6

8 / 8

10 / 10

1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

Содержание AVY24 THRU 60

Страница 1: ...ovides easy installation to convert the air handler to the required refrigerant which is a true bolt on design that does not require brazing to replace or install MicroBlueTM Coated Fins All air handl...

Страница 2: ...6 17 5 21 5 w o cladding 22 5 with cladding 12 3 8 13 29 32 14 19 32 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 1 2 3 8 3 4 AVY36C H21 52 21 17 1 8 17 13 32 18 3 32 7 8 AVY48D H21 57 24 5 22 1 8 20 29 32 21 19...

Страница 3: ...1 Cooling Heat Pump Sweat 5 83 3 11 2 24 x 17 5 1 x 0 866 3 8 Enhanced None AVY60D2CH2 2C AVY60D4HH21 4H AVY60D4JH21 4J AVY60D4KH21 4K SVY60D3XN21 None SVY60D2CN21 2C Note H models are available with...

Страница 4: ...0 840 1387 823 D N A 1 Airflow at nominal voltage bottom return at 0 5 external static pressure tested without filter installed dry coil conditions 2 These units have variable speed motors that automa...

Страница 5: ...PERMANENT Size 16 x 20 x1 20 x 20 x1 22 x 20 x1 22 x 20 x1 Permanent Type Kit 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK Shipping Operating Weight lbs 140 134 170 164 AV 196 185 SV 194 181 AV 199 188 SV...

Страница 6: ...3 6 4 8 12 3 16 4 3 6 4 8 3 6 4 8 3 6 4 8 4HK 6500806 0 5 Heat C 5 6 7 5 19 2 25 6 2 8 3 75 5 6 7 5 5 6 7 5 4HK 6501006 0 5 Heat C 7 2 9 6 24 6 32 8 3 6 4 8 7 2 9 6 7 2 9 6 4HK16501506 0 5 Heat C 10 8...

Страница 7: ...0 0 53 08 58 75 60 60 6 6 4HK16501506 60 0 74 75 83 75 90 90 3 3 4HK16501806 73 3 89 19 100 38 90 110 3 2 4HK16502006 80 0 96 42 108 75 100 125 3 1 4HK16502506 100 0 118 08 133 75 125 150 1 1 0 1 O C...

Страница 8: ...rsion table on Page 5 ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY COPPER WIRE 208 230 3 60 Models Heat Kit Three Phase Heater Amps 240V Field Wiring Min Circuit Ampacity Max O C P 1 Amps Type 75 C...

Страница 9: ...national and local safety codes Voltage limits are as follows Airflow must be within the minimum and maximum limits approved for electric heat evaporator coils and outdoor units COOLING MODELS WITH EL...

Страница 10: ...SEER enhancement 2 Remove humidistat jumper on air handler control board 3 For heat pump applications set MODE jumper on air handler control board to the HP position 4 To change quantity of heat duri...