TABLE 13:
Electrical Data For Multi-source Power Supply: 208/230-3-60
Air Handlers
Models
Heater
Models
1
Heater Amps
@240V
Min. Circuit Ampacity
MOP
2
208V
230V
208V
230V
Circuit
Circuit
1st
2
2nd
1st
2
2nd
1st
2
2nd
1st
2
2nd
25B
6HK46502025
46.2
31.3
25.0
33.3
27.6
35
25
35
30
37B
6HK46502025
46.2
28.8
22.6
30.6
25.0
35
25
35
30
37C
6HK46502025
46.2
31.3
25.0
33.3
27.6
35
25
35
30
38B
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
TBD
38C
6HK46502025
46.2
31.3
25.0
33.3
27.6
35
25
35
30
49C
6HK46502025
46.2
34.1
25.0
36.4
27.6
35
25
40
30
49D
6HK46502025
46.2
34.1
25.0
36.4
27.6
35
25
40
30
6HK46502525
57.7
40.4
31.3
43.3
34.6
45
35
45
35
50C
6HK46502025
46.2
9.1
0.0
8.8
0.0
35
25
40
30
6HK46502525
57.7
9.1
0.0
8.8
0.0
45
35
45
35
50D
6HK46502025
46.2
27.9
18.8
29.5
20.7
35
25
40
30
6HK46502525
57.7
31.7
22.6
33.7
25.0
45
35
45
35
61C
6HK46502025
46.2
34.1
25.0
36.4
27.6
35
25
40
30
61D
6HK46502025
46.2
34.1
25.0
36.4
27.6
35
25
40
30
6HK46502525
57.7
40.4
31.3
43.3
34.6
45
35
45
35
NOTES:
1. The 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with service disconnects standard.
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. Refer to the
latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
TABLE 14:
Air Flow Data (CFM)
1, 2, 3, 4
(When operating with electric heat section.)
High/Low Speed Heat CFM
Heat Tap2
AVV25B
AVV37B
AVV37C
AVV38B
AVV38C
AVV49C
High
Low
High
Low
High
Low
High
Low
High
Low
High
Low
A
1225
1020
1225
1020
1425
1150
TBD
TBD
1430
1200
1650
1200
B
1150
950
1150
950
1150
1000
TBD
TBD
1375
1150
1550
1150
C 950
750
950
750
925
925
TBD
TBD
1150
1050
1375
1050
D
725
725
725
725
675
675
TBD
TBD
900
900
1150
1000
Heat Tap
AVV49D
AVV50C
AVV50D
AVV61C
AVV61D
High
Low
High
Low
High
Low
High
Low
High
Low
A
1650
1150
1650
1200
1650
1150
1850
1250
1825
1150
B
1600
1050
1550
1150
1600
1050
1775
1200
1775
1050
C 1325
1000
1375
1050
1325
1000
1570
1150-
1570
1000
D
1125
780
1150
1000
1125
780
1370
1050
1375
950
NOTES:
1. Air handler units have been tested to UL 1995 / CSA 22.2 No. 236 standards up to 0.50" wc. external static pressure.
Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended.
Heating applications tested at 0.50” w.c. esp. Above 0.5" CFM is reduced by
2% per 0.1" increase in static.
2. The ADJ tap does not affect the HEAT tap setting.
Airflow (CFM) indicator light (LED2) flashes once for every 100 CFM (i.e.: 12 flashes is 1200 CFM) - blinks are appro/- 10% of actual CFM.
3. All CFM are shown at 0.5" w.c. external static pressure. These units have variable-speed ECM motors that automatically adjust to provide constant CFM from 0.0"
to 0.4" WC. external static pressure. From 0.4" to 0.8" external static pressure, CFM is reduced by 2% per 0.1" static pressure. Operation of these units on duct sys-
tems with external static pressure greater than 0.8" is not recommended.
4. Airflow may be lower than what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air
cleaner for further details.