036-21584-001 Rev. C (0205)

2

Unitary Products Group

 Three elbows (two in vent pipe and one in the air intake pipe) are already accounted for and need not be included in the elbow count from the Table above.

NOTE: If installing furnace at altitudes between 2000 - 4500 ft. (609.6 - 1371.6m), intake and vent pipe length must be reduced by 10 ft. (3.05 m). If the instal-
lation requires the maximum allowable intake and vent pipe length, the furnace must be converted for high altitude operation. Refer to the proper high altitude 
application instruction for details.

 

30-7/8

21-1/2

13-7/8

7

11

7/8

23-3/4

7/8

30-1/8

26-1/2

24-5/8

A

40

26-1/2

25-3/8

28-3/8

21-1/2

11

8

26-3/4

1-3/8

1-1/4

C

24-3/8

20

5/8

5/8

B

24-7/16

2

D

1-1/2” GAS
PIPE ENTRY

7/8” JUNCTION
BOX HOLE

T-STAT WIRING
7/8” K.O.

CONDENSATE
DRAIN 7/8” K.O.

OPTIONAL RETURN AIR
CUT-OUT (either side)
FOR USE WITH
EXTERNAL FILTER
FRAME

LEFT SIDE

FRONT

RIGHT SIDE

BOTTOM IMAGE

RETURN END

TOP IMAGE

SUPPLY END

1-1/2” GAS
PIPE ENTRY

7/8” JUNCTION
BOX HOLE

T-STAT WIRING
7/8” K.O.

CONDENSATE
DRAIN 7/8” K.O.

DIMENSIONS

Models

Nominal

CFM

Cabinet

Size

Cabinet Dimension

A (in.)

B (in.)

C (in.)

D (in.)

PV9A12N040UP11

1200

A

14-1/2

13-1/2

12-1/8

6-1/4

PV9B12N060UP11

1200

B

17-1/2

16-1/4

15-1/8

8-1/2

PV9B12N080UP11

1200

B

17-1/2

16-1/4

15-1/8

8-1/2

PV9C16N080UP11

1600

C

21

19-3/4

18-1/2

8-7/8

PV9C20N100UP11

2000

C

21

19-3/4

18-1/2

8-7/8

PV9D20N120UP11

2000

D

24-1/2

23-1/4

21-7/8

10-5/8

COMBUSTION AIR SUPPLY AND VENT PIPING

MAXIMUM ELBOWS AND VENT LENGTHS

Models

Pipe Size 

Inches (cm) 

Maximum Number of Elbows* 

Minimum 

Length

1 2 3 4 5 6 7 8 

40,000

1-1/2

30

25

20

10

N/A

N/A

N/A

N/A

5

40,000

2

70

65

60

55

50

45

35

25

5

60,000

1-1/2 

(3.8)  30 25 20 10 N/A 

N/A 

N/A 

N/A 

60,000

(5.1) 

60 55 50 45 40 30 20 10 

60,000

(7.6) 

85 80 75 70 65 60 50 40 

20 

80,000

1-1/2 

(3.8) 

20  15  N/A N/A N/A N/A N/A N/A 

80,000

(5.1) 

60 55 50 45 40 30 20 10 

80,000

(7.6) 

85 80 75 70 65 60 50 40 

20 

100,000

(5.1) 

25  20  15  N/A N/A N/A N/A N/A 

100,000

(7.6) 

85 80 75 70 65 60 50 40 

20 

120,000

(7.6) 

75 70 65 60 55 45 35 25 

Содержание AFFINITY PV9A12N040UP11

Страница 1: ...ble speed ECM blower operation Provides increased comfort level very quiet unit oper ation Adjustable delay timer allows two stage operation with single stage thermostat Compact easy to install ideal height 40 cabinet Blower off delay for cooling SEER improvement Easy to connect power control wiring Built in high level self diagnostics with fault code display Low unit amp requirement for easy repl...

Страница 2: ...E RETURN END TOP IMAGE SUPPLY END 1 1 2 GAS PIPE ENTRY 7 8 JUNCTION BOX HOLE T STAT WIRING 7 8 K O CONDENSATE DRAIN 7 8 K O DIMENSIONS Models Nominal CFM Cabinet Size Cabinet Dimension A in B in C in D in PV9A12N040UP11 1200 A 14 1 2 13 1 2 12 1 8 6 1 4 PV9B12N060UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PV9B12N080UP11 1200 B 17 1 2 16 1 4 15 1 8 8 1 2 PV9C16N080UP11 1600 C 21 19 3 4 18 1 2 8 7 8 PV9...

Страница 3: ...80 52 75 49 11 x 8 1 2 7 7 20 45 75 PV9C16N080UP11 80 52 75 49 11 x 10 3 4 9 6 20 45 75 PV9C20N100UP11 100 65 93 60 11 x 11 1 12 8 20 45 75 PV9D20N120UP11 120 78 112 73 11 x 11 1 12 8 20 40 70 Models Max Outlet Air Temp Nominal Airflow Cabinet Width Total Unit AFUE Min Wire Size awg 75 ft One Way Approximate Operating Weight F CFM In Amps PV9A12N040UP11 165 1200 14 1 2 9 94 0 14 121 PV9B12N060UP11...

Страница 4: ... 1490 920 C A 1250 790 1290 790 D A 1310 810 1360 840 C C 1090 690 1140 690 D C HIGH LOW HEAT CFM 40 000 INPUT 3 Ton 60 000 INPUT 3 Ton JUMPER SETTINGS CFM CFM High Low High Low HEAT Tap ADJ Tap 1045 740 1110 710 A Any 905 645 960 640 B Any 825 595 870 600 C Any 765 590 830 570 D Any 80 000 INPUT 3 Ton 80 000 INPUT 4 Ton JUMPER SETTINGS CFM CFM High Low High Low HEAT Tap ADJ Tap 1330 880 1490 990 ...

Страница 5: ...e number of return air openings or calculate the return opening size in square inches to determine the proper filter pressure drop 3 Determine the External System Static Pressure ESP without the filter 4 Select a filter pressure drop from the table based upon the number of return air openings or return air opening size and add to the ESP from Step 3 to determine the total system static 5 If total ...

Страница 6: ...type filter and filter rack Attaches to the bottom of the furnace 1BR0314 For 14 1 2 cabinets 1BR0317 For 17 1 2 cabinets 1BR0321 For 21 cabinets 1BR0324 For 24 1 2 cabinets HIGH ALTITUDE PRESSURE SWITCHES These accessory kits may be used to convert units for high altitude operation Conversion must be made by qualified dis tributor or dealer personnel NOTE For high altitude conversion an orifice c...

Страница 7: ...036 21584 001 Rev C 0205 Unitary Products Group 7 NOTES ...

Страница 8: ...e without notice Printed in U S A 036 21584 001 Rev C 0205 Copyright by York International Corp 2005 All rights reserved Supersedes 036 21584 001 Rev B 1004 Unitary 5005 Norman Products York OK Group Drive 73069 NOTES ...

Отзывы: