294604-YTG-G-0511
46
Johnson Controls Unitary Products
Additional Static Resistance
Size
(Tons)
Model
CFM
Wet Indoor Coil
Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter/Frame Kit
Electric Heat
024
(2.0)
DEZ
DEQ
DEX
500
0.01
0.00
0.01
0.02
600
0.01
0.00
0.02
0.03
700
0.01
0.00
0.02
0.03
800
0.01
0.01
0.02
0.03
900
0.01
0.01
0.02
0.04
1000
0.02
0.01
0.02
0.04
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
030
(2.5)
DEZ
DEQ
DEX
700
0.01
0.00
0.02
0.03
800
0.01
0.01
0.02
0.03
900
0.01
0.01
0.02
0.04
1000
0.02
0.01
0.02
0.04
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.07
0.03
0.17
-
036
(3.0)
DEZ
DEQ
DEX
700
0.01
0.00
0.02
0.03
800
0.01
0.01
0.02
0.03
900
0.01
0.01
0.02
0.04
1000
0.02
0.01
0.02
0.04
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
042
(3.5)
DEZ
DEQ
DEX
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
1500
0.05
0.05
0.04
0.09
1600
0.06
0.06
0.05
0.10
048
(4.0)
DEZ
DEQ
DEX
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
1500
0.04
0.05
0.04
0.09
1600
0.04
0.06
0.05
0.10
1700
0.05
0.07
0.05
0.11
1800
0.05
0.07
0.06
0.11
1900
0.06
0.08
0.06
0.11
2000
0.07
0.08
0.07
0.12
060
(5.0)
DEZ
DEQ
DEX
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
1500
0.04
0.05
0.04
0.09
1600
0.04
0.06
0.05
0.10
1700
0.05
0.07
0.05
0.11
1800
0.05
0.07
0.06
0.11
1900
0.06
0.08
0.06
0.11
2000
0.07
0.08
0.07
0.12