Table 14: Additional Static Resistance
Size
(Tons)
CFM
Wet Indoor Coil
Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance
of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter/Frame Kit
Electric Heat
024
(2.0)
500
0.01
0.00
0.01
-
600
0.01
0.00
0.02
-
700
0.01
0.00
0.04
-
800
0.02
0.01
0.06
-
900
0.03
0.01
0.08
-
1000
0.04
0.01
0.10
-
1100
0.05
0.01
0.13
-
1200
0.06
0.02
0.16
-
030
(2.5)
700
0.01
0.00
0.04
-
800
0.02
0.01
0.06
-
900
0.03
0.01
0.08
-
1000
0.04
0.01
0.10
-
1100
0.05
0.01
0.13
-
1200
0.06
0.02
0.16
-
1300
0.07
0.03
0.17
-
036
(3.0)
700
0.01
0.00
0.04
-
800
0.02
0.01
0.06
-
900
0.03
0.01
0.08
-
1000
0.04
0.01
0.10
-
1100
0.05
0.01
0.13
-
1200
0.06
0.02
0.16
-
1300
0.07
0.03
0.17
-
1400
0.08
0.04
0.18
-
042
(3.5)
1100
0.02
0.02
0.04
-
1200
0.03
0.02
0.04
-
1300
0.04
0.02
0.05
-
1400
0.05
0.03
0.05
-
1500
0.06
0.04
0.06
-
1600
0.07
0.04
0.07
-
1700
0.07
0.04
0.08
-
1800
0.08
0.04
0.09
-
1900
0.09
0.05
0.10
-
2000
0.09
0.05
0.11
-
048
(4.0)
1100
0.02
0.02
0.04
-
1200
0.03
0.02
0.04
-
1300
0.04
0.02
0.05
-
1400
0.05
0.03
0.05
-
1500
0.06
0.04
0.06
-
1600
0.07
0.04
0.07
-
1700
0.07
0.04
0.08
-
1800
0.08
0.04
0.09
-
1900
0.09
0.05
0.10
-
2000
0.09
0.05
0.11
-
060
(5.0)
1100
0.02
0.02
0.04
-
1200
0.03
0.02
0.04
-
1300
0.04
0.02
0.05
-
1400
0.05
0.03
0.05
-
1500
0.06
0.04
0.06
-
1600
0.07
0.04
0.07
-
1700
0.07
0.04
0.08
-
1800
0.08
0.04
0.09
-
1900
0.09
0.05
0.10
-
2000
0.09
0.05
0.11
-