830841-BIM-D-0512
Johnson Controls Unitary Products
11
Figure 7: Typical Field Control Wiring Diagram For Dual Fuel Heat Pump
Figure 8: Typical Field Power Wiring Diagram
Equipment Control Wiring
259/Y
258/B
262/R
263/W
264/G
265/O
YGVI
X/L
Terminal
Y2
C
O
W2
E
Y1
R
G
X/L
Thermostat
CFMCB
Common
Terminal
(Programmable
Thermostat Only)
Table 6:
Electrical Data
Size
(Tons)
DUQ
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
MCA
1
(Amps)
1. Minimum Circuit Ampacity.
Max Fuse
2
/
Breaker
3
Size
(Amps)
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
RLA
LRA
MCC
FLA
FLA
024
(2.0)
208/230-1-60 11.6
58
18
2.8
4.3
21.6
30
030
(2.5)
208/230-1-60 13.1
73
20
2.8
6.8
26
35
036
(3.0)
208/230-1-60 15.2
83
24
2.8
6.8
28.6
35
042
(3.5)
208/230-1-60 17.9
96
28
2.8
9.1
34.3
45
048
(4.0)
208/230-1-60 21.1
104
33
2.8
9.1
38.3
50
060
(5.0)
208/230-1-60 28.8
153
45
2.8
9.1
47.
60