830841-BIM-D-0512
14
Johnson Controls Unitary Products
4.
All piping should be cleaned of dirt and scale by
hammering on the outside of the pipe and blowing out the
loose dirt and scale. Before initial start-up, be sure that all
of the gas lines external to the unit have been purged of air.
5.
The gas supply should be a separate line and installed in
accordance with all safety codes as prescribed under
Limitations, shown on Page 3. After the gas connections
have been completed, open the main shut-off valve
admitting normal gas pressure to the mains. Check all
joints for leaks with soap solution or other material suitable
for the purpose. NEVER USE A FLAME.
6.
The furnace must be isolated from the gas supply piping
system by closing its individual manual shut-off valve
before conducting any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2
psig (3.48 kPa).
Flue Vent Hood
The flue vent hood with screen is shipped loose. This hood must
be installed to assure proper unit operation. The hood must be
fastened to the outside of the side gas control/electrical
compartment with the screws provided in the bag attached to the
inside of the gas control/electrical compartment, see Figure 10.
Figure 10: Flue Vent Outlet Air Hood
Table 8:
Natural Gas Pipe Sizing Chart
1
1. Maximum capacity of pipe in cubic feet of gas per hour (based
upon a pressure drop of 0.3 inch water column and 0.6 specific
gravity gas).
Length
In Feet
Nominal Inches Iron Pipe Size
1/2”
3/4”
1”
1-1/4”
10
132
278
520
1,050
20
92
190
350
730
30
73
152
285
590
40
63
130
245
500
50
56
115
215
440
60
50
105
195
400
70
46
96
180
370
80
43
90
170
350
90
40
84
160
320
100
38
79
150
305
Table 9:
Propane (LP) Gas Pipe Sizing Chart
1
1. Maximum capacity of pipe in thousands of BTU per hour
(based upon a pressure drop of 0.5 inch water column).
Length
In Feet
Nominal Inches Iron Pipe Size
1/2”
3/4”
1”
1-1/4”
10
275
567
1,071
2,205
20
189
393
732
1,496
30
152
315
590
1,212
40
129
267
504
1,039
50
114
237
448
913
60
103
217
409
834
70
96
196
378
771
80
89
185
346
724
90
83
173
322
677
100
78
162
307
630
If flexible stainless steel tubing is allowed by the
authority having jurisdiction, wrought iron or steel pipe
must be installed at the gas valve and extend a
minimum of two (2) inches outside of the unit casing.
Natural gas may contain some propane. Propane being
an excellent solvent, will quickly dissolve white lead or
most standard commercial compounds. Therefore, a
special pipe dope must be applied when wrought iron or
steel pipe is used. Shellac base compounds such as
gaskoloc or stalastic, and compounds such as
rectorseal # 5, Clyde’s or John Crane may be used.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result
in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a
commercially available soap solution made specifically
for the detection of leaks to check all connections. A fire
or explosion may result causing property damage,
personal injury or loss of life.
Flue hood surfaces may be hot.
The flue exhaust hood must be properly installed and
within the recommended clearances. Further
communications and action must be given to the home
or building owner(s) to eliminate any unauthorized
human contact around this area during the heating
cycle. Flue hood surface and the immediate area reach
high temperatures during the heating cycle.
VENT OUTLET SCREEN
FLUE VENT OUTLET
AIR HOOD