COOLING CAPACITY
1
Models
Rated CFM
2
Entering Air
Dry/Wet Bulb
(°F)
MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
35/107.9
40/118.9
45/130.7
50/143.3
AHR18B 665
85/72 40.7 35.6 30.5 24.1
80/67 35.0 29.5 23.9 18.6
75/62 27.9 22.7 18.1 12.4
70/57 22.1 19.8 16.9 14.1
AHR22B
800
85/72 47.7
42.6
35.3
30.3
80/67 40.1
34.7
28.9
22.8
75/62 32.7
27.1
24.7
19.1
70/57 25.7
23.5
20.5
17.1
AHR24B
740
85/72 47.9 42.4 36.8 29.9
80/67 40.9 35.2 29.0 22.6
75/62 33.6 28.0 21.7 15.5
70/57 26.2 23.0 19.9 16.9
AHR29C
1000
85/72 38.9
35.4
31.6
27.6
80/67 33.9
30.3
26.8
23.0
75/62 27.3
23.7
22.5
18.0
70/57 22.6
20.1
17.5
14.8
AHR30B
1115
85/72 65.8 60.4 50.7 41.5
80/67 58.0 49.5 39.9 31.2
75/62 47.1 38.9 30.4 21.1
70/57 37.1 33.1 28.2 23.9
AHR34C
1000
85/72 35.0
31.8
28.4
24.7
80/67 32.2
29.1
25.7
22.3
75/62 26.4
23.4
21.0
17.1
70/57 21.4
18.6
20.2
12.1
AHR36B
1060
85/72 71.1 62.4 51.5 44.3
80/67 59.2 51.0 42.0 32.7
75/62 48.0 39.6 30.8 21.8
70/57 37.3 32.8 28.3 24.0
1245
85/72 83.2 66.7 60.1 48.9
80/67 66.0 59.5 47.8 37.1
75/62 55.0 45.2 35.5 24.8
70/57 42.9 38.1 32.6 27.6
AHR42C
1230
85/72 68.2 72.9 62.8 51.6
80/67 66.3 59.7 48.6 38.4
75/62 56.4 45.4 36.1 25.5
70/57 43.7 38.3 33.3 28.3
1485
85/72 69.8 86.0 74.0 59.1
80/67 68.5 69.5 56.6 44.2
75/62 65.3 54.1 42.0 29.8
70/57 51.0 45.4 39.1 32.8
AHR48D
1320
85/72 87.5 75.9 64.4 51.7
80/67 71.2 59.9 49.8 37.2
75/62 56.5 46.6 35.4 23.3
70/57 43.5 39.5 34.0 28.4
1610
85/72
102.3 90.1 76.1 60.5
80/67 83.7 71.5 57.3 43.6
75/62 67.0 54.0 41.2 27.0
70/57 50.9 46.6 39.8 33.4
(For notes see page 4.)