1055361-BTG-B-0913
Johnson Controls Unitary Products
11
Models
Blower
Motor Speed
External Static Pressure (in. wc.)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
230 Volt
AHR42C
High
1750
1670
1570
1477
1260
1125
935
Medium
1590
1520
1435
1277
1150
1010
870
Low
1330
1280
1200
1083
980
850
NA
AHR48D
High
2005
1940
1850
1755
1650
1530
1405
Medium
1705
1665
1605
1510
1425
1340
1185
Low
1355
1330
1300
1245
1170
990
980
AHR60D
High
2034
1955
1858
1753
1640
1522
1296
Medium
1733
1672
1609
1527
1431
1272
1220
Low
1388
1359
1313
1255
1133
1004
912
1. Air handler units have been tested to UL 1995 / CSA 22.2 standards up to 0.30" wc. external static pressure.
Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.6" are not recommended.
Airflow data shown is from testing performed at 230V. AHE units use a X13 motor, and there is minimal variation of airflow at other distribution voltage values. The
above data can be used for airflow at other distribution voltages.
AIR FLOW DATA (CFM)
1
(Continued)