26
<Read Me First>
IM 01W02E01-11EN
• Cable glands, adapters and/or blanking elements shall be installed so as to maintain the
specified degree of protection (IP Code) of the equipment.
• The antenna and the surge arrester shall be simple apparatus in accordance with EN
60079-14. Li and Ci of the simple apparatus shall be negligible. Temperature class of them
shall be determined from Po = 100 mW for ISA and Po = 130 mW for WLAN1/WLAN2.
• The following conditions must be met for the connections to ISA, WLAN1, and WLAN2.
(total Li of simple apparatuses) + (total Lc) ≤ 0.5 mH
(total Ci of simple apparatuses) + (total Cc) ≤ 0.09 μF
• The equipment shall be earthed in accordance with EN 60079-14, in order to maintain in
-
trinsic safety. A cable lug or a similar device shall be used to maintain the secureness of the
connection to the equipment. Care should be taken to avoid multi-point earthing since the
equipment is not galvanically isolated from the power supply.
Note 4. Control Drawing
Hazardous Location
*1: These apparatus are simple apparatus.
*2: Surge Arrester may not be installed.
Electrical Equipment
Antenna
(*1)
Surge
Arrester
(*1, *2)
Antenna
(*1)
Surge
Arrester
(*1, *2)
Antenna
(*1)
Surge
Arrester
(*1, *2)
Hazardous Location
YFGW510
Field Wireless Access Point
Nonhazardous Location
Radio wave
(IEEE802.15.4)
wiring
Control
Equipment 1
Power
Supply
+
-
+
-
Control
Equipment 2
Radio Wave
(IEEE802.11a/b/g)
or
metal wiring
or
optical fiber
ISA WLAN2
WLAN1
100BASE-TX/
100BASE-FX
Zone 1
F11.ai
WARNING
• AFTER DE-ENERGIZING, DELAY 1 MINUTE BEFORE OPENING
• POTENTIAL ELECTROSTATIC CHARGING HAZARD – SEE INSTRUCTIONS