1-9
IM 707231-01E
Functions
1
Alarm Output
When the Out check box is selected, you can output the alarm occurrence status as a
bus trigger to the measuring station’s BUSTRG1 or BUSTRG2.
An alarm is output if any of the groups for which alarm output was specified generate an
alarm.
When an alarm occurs and the bus trigger signals are set to output from the WE7231 in
the Trigger Source/Time Base Source/Arming settings dialog box, if the alarm output
conditions are Rise/Fall when the conditions are met, the bus trigger signal is set to True
for approximately 1
µ
s. When the alarm output conditions are High, Low, In, or Out, the
bus trigger signal is True for as long as the conditions are met. For information about the
settings in the Trigger Source/Time Base Source Setting dialog box, see section 4.6,
“Setting the Trigger Source/Time Base Source/Arming” in the WE7000 User’s Manual (IM
707001-01E).
Example of Alarm Output
TRIG_HIGH
CH1 input
signal
High level
Event output
BUSTRG output
BUSTRG output
Event output
(When the combination is AND)
(When the combination is OR)
CH2 input
signal
Alarm
(type: High)
TRIG_LOW
TRIG_LOW
TRIG_HIGH
TRIG_PULSE
TRIG_PULSE
High level
Alarm
(type: Rise)
Alarm Status Indicator
The alarm occurrence status for each group is displayed according to the combination
setting. Also, when you select the group you wish to display under the Moni tab, the
button displaying the alarm status appears. You can confirm the alarm status of each
channel, and when an alarm occurs, the button color turns from green to red.
Alarm Status Indicator Hold
When the Hold check box is selected, the alarm occurrence status indicator is held from
the point when an alarm occurs. If you click Reset, the hold is released.
1.4 Setting the Alarm