4-16
IM 04P01B01-17E
Query
SJ[ p1]?
Example
Enable timer 1 on computation channel 0B. No
sum scale designation.
SJ 0B,1,OFF
Description • This command cannot be specified while
computation is in progress.
• About p3
The data for sum computation are sampled
every scan interval. For data with units such
as /s, /min, /h, and /day as in a flow rate, the
data can be summed over the unit time as
shown below. Parameter p3 is valid only for
sum values.
OFF
Σ
(measured value)
/s
Σ
(measured value)
×
scan interval
/min
Σ
(measured value)
×
scan interval/60
/h
Σ
(measured value)
×
scan interval/
3600
/day
Σ
(measured value)
×
scan interval/
(3600
×
24)
The unit of the scan interval is seconds.
VD
Sets the data display screen.
On screens without detailed parameters
Syntax
VD p1,p2
<terminator>
p1
Screen number (01 to 15)
p2
Display type
4CH bargraph
4-channel bar graph display (pen
model)
6CH bargraph
6-channel bar graph display
(
µ
R10000 dot model)
Channel alarm status
Channel alarm status display
Time/Chart speed
Date/Time/Chart speed display
DI/DO
DI/DO
status display
STATUS
Status display
System
System display
Batch name
Batch name (/BT1 option)
Lights out
Screen OFF
SKIP
Skip
Query
VD[ p1]?
Example
Assign the status display to screen 02.
VD 02,STATUS
On screens with the displayed channel switching
interval
Syntax
VD p1,p2,p3
<terminator>
p1
Screen number (01 to 15)
p2
Display type
1CH digital
1-channel digital display
2CH digital
2-channel digital display
4CH digital
4-channel digital display
6CH digital
6-channel digital display (dot model)
12CH digital
12-channel digital display (
µ
R20000
12, 18 and 24 dot model)
1CH 1CH bargraph
1-channel digital d 1 channel
bar graph display
1CH 4CH bargraph
1-channel digital d 4 channel
bar graph display (pen model)
2CH 2CH bargraph
2-channel digital d 2 channel
bar graph display
Tag_1CH digital
1-channel digital display (tag)
Tag_2CH digital
2-channel digital display (tag)
Tag_1CH 1CH bargraph
1-channel digital d 1 channel
bar graph display (tag)
Tag_1CH 4CH bargraph
1-channel digital d 4 channel
bar graph display (tag, pen model)
p3
Displayed channel switching interval
MANUAL
Fixed display channels, data
update rate (pen model): 2 s,
data update rate (dot model):
scan interval
AUTO1S
Switch the displayed
channels and data every
second.
AUTO2S
Switch the displayed
channels and data every 2
seconds.
AUTO3S
Switch the displayed
channels and data every 3
seconds.
AUTO4S
Switch the displayed
channels and data every 4
seconds.
AUTO5S
Switch the displayed
channels and data every 5
seconds.
Query
VD[ p1]?
4.4 Setting Commands