3 - 9
IM 4H3B1-01E
3. INSTALLATION
3.2.4 Alarm Output Wiring
1 Make sure the power switch is turned OFF and remove the transparent cover at the rear
of the
µ
R1800.
2 Connect the alarm output wires to the alarm output terminal. Do NOT change the place
of the therminal block!
3 Replace the transparent cover.
Depending on your option, your alarm output terminal will be arranged like one of the
following:
!
CHARACTERISTICS:
Output type:
relay transfer contact (energize/de-energize type switchable)
Output capacity:
250VAC (50 or 60Hz), 3A
250VDC, 0.1A (resistive load)
Dielectric strength: 1500VAC (50 or 60Hz) for one minute between output terminal
and ground terminal
To adjust initial settings, see 9.1.
• To prevent an electric shock, ensure the main power supply is turned OFF
during wiring and ensure the ground terminal is connected using a class 3
resistance of 100
Ω
or less.
• Ensure the ground terminal is connected using a class 3 resistance of 100
Ω
or
less.
• Use "crimp-on" lugs with insulation sleeves for all connections if a voltage of
more than 30 VAC or 60 VDC is applied to the alarm output or fail/memory end
output. Furthermore, use doubleinsulated wires (withstand voltage
performance: more than 2300VAC) for those wires which apply 30 VAC or
60VDC. All other wires can be basic-insulated (withstand voltage performance:
more than 1350VAC). To prevent electric shock, do not touch the terminal after
wiring and make sure to re-attach the cover.
NOTE
To prevent an emission of electromagnetic disturbances, separate the alarm output wires
from the power supply and input wires at least 0.1m. Over 0.5m is recommended.
WARNING
ALARM
!
option /A1
2 contacts
option /A2
4 contacts
option /A3
6 contacts
1
2
3
4
5
6
ALARM
!
1
2
3
4
ALARM
!
1
2
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
3.2 Wiring
Figure 3.12 Alarm Output Terminals