7-2
<Toc>
<7. Function Block Diagram and Descriptions>
IM 05E01D02-41E
1st Edition : May 31,2000-00
■
Function Block Diagram for Standard Type
Hold program
Control computation
Preset output
RUN
STOP
OUTPUT1
OUTPUT1
17
16
Relay
terminals
, and
2
3
1
Current or pulse
terminals
and
RET
15 V loop
power supply
Retransmission
output
Current
terminals
and
15
14
Terminal
Parameter
Function
Analog signal
Contact signal
Front panel key
Legend
PRG1
PRG2
DI2
DI1
Contact input
RESET
RET
OT
Control
output
Output limiter
PV input
terminals , and
12
13
11
INPUT
Input selection
Unit selection
Input range conversion
Input bias
Input filter
Program 1
operation
Program 2
operation
PV event output
Time event output
PVE1
PV
event 1
PVE2
PV
event 2
TME
Time
event
Program
pattern selection
Start program 1
when DI1=ON
Start program 2
when DI2=ON
Correspondence between parameter DIS and external contact input functions
When DIS=3
Start program 1 when DI1 = ON
Reset program 1 when DI1 = OFF
Hold program when DI2 = ON
Cancel hold when DI2 = OFF
When DIS=2
Hide setup parameter lock when DI1 = ON
Show setup parameter lock when DI1 = OFF
When DIS=OFF (Factory-set default)
No function
No function
When DIS=1
Start program 1 when DI1 = ON
Reset program 1 when DI1 = OFF
Start program 2 when DI2 = ON
Reset program 2 when DI2 = OFF
* DIS is a setup parameter.
Changing DIS setpoint allows you to change the function of external contact input.
No function