Transmitter
Quick Reference Instruction Manual
Wiring
IM01U10A00-00EN-R, 2nd edition, 2017-08-29
37 / 54
7.4.4 Assignment of inputs and outputs
The table below shows possible connection terminal assignments for I/O outputs depend-
ing on MS code Position 13.
The following figure shows the relevant position of the MS code:
-
-
-
-
/
-
RC
1
2
3
4
6
7
5
9
10
11
12
13
14
15
8
Configuration of input/output terminals for HART communication
HART I/O
MS code
Position 13
Connection terminal assignment
I/O1 +/-
I/O2 +/-
I/O3 +/-
I/O4 +/-
WP
JA
Iout1
Active
P/Sout1
Passive
–
–
Write-protect
JB
Iout1
Active
P/Sout1
Passive
P/Sout2
Passive
Iout2
Active
Write-protect
JC
Iout1
Active
P/Sout1
Passive
Sin
Iout2
Active
Write-protect
JD
Iout1
Active
P/Sout1
Passive
Sout
Passive
P/Sout2
Passive
Write-protect
JE
Iout1
Active
P/Sout1
Passive
Sin
P/Sout2
Passive
Write-protect
JF
Iout1
Active
P/Sout1
Passive
Sin
P/Sout2
Active
Internal pull-
up resistor
Write-protect
JG
Iout1
Active
P/Sout1
Passive
Sin
P/Sout2
Active
Write-protect
JH
Iout1
Active
P/Sout1
Passive
Iout2
Passive
Iin
Active
Write-protect
JJ
Iout1
Active
P/Sout1
Passive
P/Sout2
Passive
Iin
Active
Write-protect
JK
Iout1
Active
P/Sout1
Passive
Sin
Iin
Active
Write-protect
JL
Iout1
Active
P/Sout1
Passive
Iout2
Passive
Iin
Passive
Write-protect
JM
Iout1
Active
P/Sout1
Passive
P/Sout2
Passive
Iin
Passive
Write-protect
JN
Iout1
Active
P/Sout1
Passive
Sin
Iin
Passive
Write-protect
JP
Iout1
Passive
P/Sout1
Passive
Iout2
Passive
–
Write-protect
JQ
Iout1
Passive
P/Sout1
Passive
Iout2
Passive
P/Sout2
Passive
Write-protect
JR
Iout1
Passive
P/Sout1
Passive
NAMUR
Iout2
Passive
–
Write-protect