<8. Detailed Description>
128
TI 34P02K35-02E Jun. 6, 2018-00
8. Detailed Description
8.1 Checking Operation Specifications of I/O
Modules
8.1.1 Checking Operation Specification of Analog/Digital Input
Compare the operation specification of each module against the requirement
specification to ensure that there is no problem.
SEE ALSO
For details on the operation specification of I/O modules, see Section A1.6, “I/O Modules” of IM
“STARDOM FCN/FCJ Guide.”
Some I/O modules have module-based settings and channel-based settings. Before
starting engineering, determine which settings are module-based and which are
channel-based. Specify these settings on the actual hardware.
● Module Based Settings
The following settings apply to the entire I/O module.
• Input range of NFAV144 (16-point voltage input module)
Two input span options are available: 1 to 5V or -10 to10V.
Selecting 1 to 5 V sets the input range of all channels to 1 to 5V.
If you select -10 to10V, the input span can be specified on channel basis.
• Burnout settings of temperature input module
Configures burnout operation on module basis by specifying whether to enable
or disable: burnout detection and selecting between up-scale burnout and down-
scale burnout.
• Filter settings for digital input module
To prevent false detection due to input chattering for a contact input module,
specify a filter time.
The filter time in milliseconds can be selected from the following options: 2, 4 8,
16, 32, 64, 128 and 256.
Содержание STARDOM FCN-500
Страница 2: ...Blank Page...
Страница 10: ...Blank Page...
Страница 32: ...Blank Page...
Страница 36: ...TI 34P02K35 02E Jun 6 2018 00 Blank Page...
Страница 76: ...TI 34P02K35 02E Jun 6 2018 00 Blank Page...
Страница 163: ...Blank Page...
Страница 221: ...Blank Page...
Страница 225: ...Blank Page...