3-37
TI04L55B01-01EN
3.3.5
HTTP Function
You can access the GM from a Web browser and monitor measurement data in real time and
configure and operate the GM.
For details, see section 3.1.5, “Display (Web browser).”
3.3.6
Communication Channel Function (/MC option)
When data from Modbus devices or PC is recorded on the GM, the acquired data is assigned to
communication channels (GM10-1: C001 to C300, GM10-2: C001 to C500).
Data acquired from power meters using WT communication (/E2 option) is also assigned to
communication channels.
Alarms can be set on communication channels.
PC
Modbus device
WT
Communication channel
GM10-1: C001 to C300
GM10-2: C001 to C500
Data
l
Watchdog Timer Function
Data may fail to be updated due to Modbus or other communication problems.
The watchdog timer function replaces values with their preset values or last values and when
values are not updated within the specified duration (timer).
Data replacement occurs immediately when the timer expires, and the values are held until the
next read cycle.
The watchdog timer is also useful for detecting communication interruptions caused by
communication errors.
Timer
Data not updated
Communication
channel data
A
B
C
D
E
E
E
Preset value: Z
Z
F
G
Read cycle
Replace data
Communication data
H
3