216
Active power polarity
A swing display of active power meter can be selected from P (one-way deflection) and
-
(both deflection).
Selection by
+
and
-
, set value is updated by SET .
Default setting: P (one-way deflection)
◆
217
Active power range
Set the full scale of active power meter. The setting range is
3
0 to
120
% of rated power.
And it can select from "
214
current display intrinsic sensitivity" tables.
Selection by
+
and
-
, set value is updated by SET .
(1000MW or more becomes 4 digits display fixation.)
<Caution
> In case of 220V direct input. C
alculates by VT ratio=
2.
Default setting:
3φ3W, 110V input
:
120
0kW,
3φ3W, 220V
input: 40.00kW,
1φ3W
: 100.0kW
1φ2W
, 110V input: 150.0kW,
1φ2W, 220V input
: 10.00kW
◆
218
Digit number of active power range
Sets the digit number of active power range.
Selection by
+
and
-
, set value is updated by SET .
Default setting: 4 digits
The unit may be changed if the number of digits is changed.
Example
) 1200kW 1.20MW
◆
219
Reactive power range
Sets the full scale of reactive power meter.
The setting range is
3
0 to 1
20
% of rated reactive power.
And it can select from "
214
current display intrinsic sensitivity"
tables. Selection by
+
and
-
, set value is updated by SET .
(1000Mvar or more becomes 4 digits display fixation.)
<Caution
> In case of 220V direct
input. Calculates by VT ratio=
2
.
Default setting:
3φ3W, 110V input
: 600.0kvar
3φ3W, 220V input
:
20.00kvar
1φ3W
: 50.00kvar
1φ2W, 110V input
: 75.00kvar
1φ2W, 220V inpu
t: 5000var
Power polarity
Setting No.
Now setting
One-way deflection display
New setting
Both swing display
P:
One-way
deflection
-
:
Both
deflection
+
-
-
+
4 digits
3
digits
+
-
-
+
Setting No.
Now setting
Digit number of active power range
Setting factor
New setting
Reactive power range
Setting factor
Setting No.
New setting
Now setting