56
IM 77C01E31-01EN
SFLC-212-181
56
6.3 Input/output functions
Item
Specification
Communication
output
Standard
EIA RS-485
Protocol
Modbus protocol RTU mode
RTU: Remote Terminal Unit
(Monitor operating unit)
PI-MBUS-
300 Rev.J
Modbus Application Protocol
specification V1.1b
Use function code
03H
, 04H, 06H, 08H
Transmission system Half duplex two-wire system
Synchronous system asynchronous communication method
Transmission rate
4800bps / 9600bps / 19200bps / 38400bps
Line code
NRZ
Start bit
1 bit
Data length
8 bit
Parity bit
NONE
(Nothing) / ODD (Odd number) /
EVEN (Even number)
Stop bit
1 bit
/ 2 bit
Transmission code
Binary
Cable length
1000m
Address
1 to
247
The number of connection
Max. 31 sets
Error detection
CRC-16
X
16
+X
15
+X
2
+1
Topology
Multidrop
Please reference to the
Model PR720 Power
and Energy Meter Modbus RTU Mode Protocol User’s Manual
(
IM 77C01E31
-10EN) for the details of communication output data.
Pulse output
Possible output : Watt-hour or var-hour.
Output form : Optical MOS-FET relay. 1a contact
Contact capacity: AC, DC1
25V
, 70mA (Resistance load, inductive load)
Pulse width :
250±10ms
(Output pulse width when the output pulse period of rated active power
constitut
es speed more than 2 pulse/s
econd by setting of an voltage measurement
range, a current-measurement range, and an output pulse unit is set to 100 to
130ms.)
Setting of output pulse unit is possible by the next range.
■ 3
-
phase 3
-wire : Full load power (kW, kvar)=
√
3
×Rated voltage(V)×Rated current(A)×10
-
3
■ Single
-
phase 3
-wire: Full load power (kW, kvar)=
2
×Rated voltage(V)×Rated current(A)×10
-
3
■ Single
-
phase 2
-wire: Full load power (kW, kvar)=Rated voltage(V)×Rated current(A)×10
-
3
Full load power (kW, kvar)
Output pulse unit.
kWh(kvarh)/puls
e
Multiplying factor
Below 1
0.1 0.01 0.001 0.0001 0.01 (
2
6
)
Over 1 Below 10
1
0.1
0.01
0.001
0.1
Over 10 Below 100
10
1
0.1
0.01
1
Over 100 Below 1,000
100
10
1
0.1
10
Over 1,000 Below 10,000
1,000
100
10
1
100
Over 10,000 Below 100,000
10,000
1,000
100
10
1,000
Over 100,000 Below 1,000,000 100,000
10,000
1,000
100
10,000
Alarm output
Alarm factor: Demand current, Demand power, Voltage, Alarm OFF. Possible to setting one of them.
Reset method: Automatic reset or Manual reset (Setting)
Output contact : No-voltage a contact (OR of each phase detection)
Contact capacity:
AC250V
5A, DC1
25V 0.3A
(Resistance load
) AC250V 2A, DC125V 0.1A (Inductive
load)
Alarm factor
Item
Specification
Demand
current,
Demand power
Function
Demand measurement value
≧
Upper limit setting value,
Alarm display, Alarm output.
Setting accuracy
±0.5
% (% for full scale )
Setting range
5 to 100% to the maximum scale. (1% step)
Voltage
Function
Measurement value
≧
Upper limit setting value,
Alarm display, Alarm output.
Measurement value
≦
Lower limit setting value,
Alarm display, Alarm output.
Setting accuracy
±0.5
% (% for full scale)
Setting range
Using a full scale as 150%.
30
to 150% (1% step)
Note(
26
) Although multiplying factor is 0.01, a multiplying factor display will be 0.1.
(The place by the integer is 4 digits display. An enlarged display is 4 digits below decimal point.)