3. MODBUS Protocol

IM 249x-COMM

9

06 –  Preset Single Register

Sets a single register.  Cannot be used to change values that fill more
than one register.  (e.g. PT ratio)

08 –  Diagnostics

Only the loopback subroutine (Return Query Data) is supported.  This
simply returns a response identical to the query.

16 –  Preset Multiple Registers

Can set single or multiple registers.  If this command is sent to a Maximum
or Minimum register, no data should be included with the query.  The
Power Series Plus will simply reset the register(s) so that the next
measurement will become the maximum or minimum.

Register Table

All registers are 2 bytes in size. Shaded registers are for Yokogawa internal use only.

REGISTER

NAME

R / W

UNITS

FORMAT

CONTENTS

1 (0000)

VER

R

-

Unsigned int

Firmware Version Number * 100

2 (0001)

MODEL

R

-

Unsigned int

Model Code  

12=V/V/V; 13=A/A/A;

14=V/A/Hz; 15=W/VAR/PF

3 (0002)

CONN

R

-

Unsigned int

Terminal Connections

0=2Wire; 1=3Wire; 2=4Wire

4 (0003)

VOLT

R

-

Unsigned int

Input Voltage Rating

0=120/150Volts; 1=240/300Volts

5 (0004)

AMP

R

-

Unsigned int

Input Current Rating 

0=1Amp;

1=5Amps

6 (0005)

FREQ

R

-

Unsigned int

Input Frequency Rating

0=55Hz; 1=400Hz

7 (0006)

ANOUT

R

-

Unsigned int

Analog Output Code

0=No Output; 1=0-1mA; 3=4-20mA

8 (0007)

AVG

R/W

-

Unsigned int

Rolling Average Setting  

0~29

samples

9 (0008)

LL

R/W

-

Unsigned int

Line-Line Setting (Voltmeters Only)

0=Line-Neutral; 1=Line-Line

10 (0009)

LOCK

R/W

-

Unsigned int

Front Panel Lockout

0=unlocked; 1=locked

11 (000A)

VARPOL

R/W

-

Unsigned int

Not yet implemented

12 (000B)
(4 bytes)

PT

R/W

-

IEEE float

Potential Transformer Ratio

1.0:1 ~ 1250.0:1

14 (000D)
(4 bytes)

CT

R/W

-

IEEE float

Current Transformer Ratio

1.0:1 ~ 5000.0:1

16 (000F)

Spare

17 (0010)

Spare

18 (0011)

Spare

19 (0012)

Spare

20 (0013)

Spare

21 (0014)

Spare

22 (0015)

OUT1

R/W

Channel
dependent

Hi & Lo: float

Channel 1 Output Range Settings

Содержание Power Series Plus IM 249x-COMM

Страница 1: ...Communications Power Series Plus Manual Power Series Plus Digital Switchboard Meter IM 249x COMM 1 IM 249x COMM Revision 1 October 1999...

Страница 2: ...okogawa Corporation of America 0 Introduction 1 YCA Protocol 2 Getting Current Settings and Display 3 Changing Settings 3 Unit Responses and Error Codes 7 Modbus Protocol 8 Function Codes 8 Register T...

Страница 3: ...You can read and change all the settings and read all measurements You can choose one of two available protocols for communications YCA or Modbus available only on 2493 YCA protocol is a simple master...

Страница 4: ...changed from the front panel Each unit in a network must have a unique number for communications to work The default on all units is 01 The FUNCTION is one of the following codes Note The functions a...

Страница 5: ...are the new settings parameters The format is described below Potential Transformer DP aa PT xxxxxy xxx The part before the slash is the value that you want to make the primary side of the transformer...

Страница 6: ...nd 01 DONE If you exceed the ratio limits for PT that is 1 1 or 1250 1 or make some other mistake you will get an error message such as 01 ERR 6C The error codes are explained under the Unit Responses...

Страница 7: ...ou would enter DP 01 OUT1 160 0 0 HI 160 LO 0 CENTER 0 to 1 If you want a wattmeter with 1to1 mA output to give max output 1mA when the input is 15050 Watts and minimum output 1mA when the input is 15...

Страница 8: ...atts B DUAL Watts Power Factor 3 VARs C TRIPLE Volt Volt Volt 5 Power Factor D TRIPLE Amp Amp Amp 6 Phase Angle E TRIPLE Volt Amp Hertz 7 Hertz F TRIPLE Watt VAR PF 8 DUAL Volts Amps b Input Frequency...

Страница 9: ...no analog output TMER When you send a DP message to change a setting you must confirm it within ten 10 seconds or the change is discarded and the unit replies with this DONE When a change has been mad...

Страница 10: ...re not returned to broadcast queries The Power Series Plus always acts as a slave in accordance with The Modicon Modbus Reference Guide PI MBUS 300 It has the following characteristics Interface RS 48...

Страница 11: ...Model Code 12 V V V 13 A A A 14 V A Hz 15 W VAR PF 3 0002 CONN R Unsigned int Terminal Connections 0 2Wire 1 3Wire 2 4Wire 4 0003 VOLT R Unsigned int Input Voltage Rating 0 120 150Volts 1 240 300Volt...

Страница 12: ...ytes I3 R Amps IEEE float Latest I3 Measurement 49 0030 4 bytes HZ R Hertz IEEE float Latest Frequency Measurement 51 0032 4 bytes W R Watts IEEE float Latest Watt Measurement 53 0034 4 bytes VAR R VA...

Страница 13: ...R W Volts IEEE float Maximum V1 Measurement 99 0062 4 bytes V2MAX R W Volts IEEE float Maximum V2 Measurement 101 0064 4 bytes V3MAX R W Volts IEEE float Maximum V3 Measurement 103 0066 4 bytes I1MAX...

Страница 14: ...e 121 0078 Spare 122 0079 Spare 123 007A Spare 124 007B Spare 125 007C Spare 126 007D Spare 127 007E Internal 128 007F Internal 129 0080 Internal 130 0081 Internal 131 0082 Internal 132 0083 Internal...

Страница 15: ...ssion mode and parity setting can only be changed using the front panel interface To get to the setting mode press the keys in the following order Mode Mode Set The display will now be showing the PT...

Страница 16: ...tes on Modbus Out of range floating point values are shown as 3 40282347 X 1038 The PSP uses a Motorola microcontroller This means that Intel based software such as Windows might interpret the floatin...

Страница 17: ...Connection Power Supply The far end can be connected to any communications device that is acting as the master such as a computer The unit can also be connected in parallel with other units If you wi...

Отзывы: