3. MODBUS Protocol
IM 249x-COMM
9
06 – Preset Single Register
Sets a single register. Cannot be used to change values that fill more
than one register. (e.g. PT ratio)
08 – Diagnostics
Only the loopback subroutine (Return Query Data) is supported. This
simply returns a response identical to the query.
16 – Preset Multiple Registers
Can set single or multiple registers. If this command is sent to a Maximum
or Minimum register, no data should be included with the query. The
Power Series Plus will simply reset the register(s) so that the next
measurement will become the maximum or minimum.
All registers are 2 bytes in size. Shaded registers are for Yokogawa internal use only.
REGISTER
NAME
R / W
UNITS
FORMAT
CONTENTS
1 (0000)
VER
R
-
Unsigned int
Firmware Version Number * 100
2 (0001)
MODEL
R
-
Unsigned int
Model Code
12=V/V/V; 13=A/A/A;
14=V/A/Hz; 15=W/VAR/PF
3 (0002)
CONN
R
-
Unsigned int
Terminal Connections
0=2Wire; 1=3Wire; 2=4Wire
4 (0003)
VOLT
R
-
Unsigned int
Input Voltage Rating
0=120/150Volts; 1=240/300Volts
5 (0004)
AMP
R
-
Unsigned int
Input Current Rating
0=1Amp;
1=5Amps
6 (0005)
FREQ
R
-
Unsigned int
Input Frequency Rating
0=55Hz; 1=400Hz
7 (0006)
ANOUT
R
-
Unsigned int
Analog Output Code
0=No Output; 1=0-1mA; 3=4-20mA
8 (0007)
AVG
R/W
-
Unsigned int
Rolling Average Setting
0~29
samples
9 (0008)
LL
R/W
-
Unsigned int
Line-Line Setting (Voltmeters Only)
0=Line-Neutral; 1=Line-Line
10 (0009)
LOCK
R/W
-
Unsigned int
Front Panel Lockout
0=unlocked; 1=locked
11 (000A)
VARPOL
R/W
-
Unsigned int
Not yet implemented
12 (000B)
(4 bytes)
PT
R/W
-
IEEE float
Potential Transformer Ratio
1.0:1 ~ 1250.0:1
14 (000D)
(4 bytes)
CT
R/W
-
IEEE float
Current Transformer Ratio
1.0:1 ~ 5000.0:1
16 (000F)
Spare
17 (0010)
Spare
18 (0011)
Spare
19 (0012)
Spare
20 (0013)
Spare
21 (0014)
Spare
22 (0015)
OUT1
R/W
Channel
dependent
Hi & Lo: float
Channel 1 Output Range Settings