IM 12B07D02-01E
Specification 2-9
2-6. Control Drawing of PH202S mA HART® Specification (FM Intrinsically safe design)
Sensor(s)
terminals 11-17
Max. cablelength: 60 mtr.
Cable dia. : 3…12 mm.
Sensor(s)
terminals 11-17
Max. cablelength: 60 mtr.
Cable dia.: 3…12 mm.
Ùnclassified Location
FM Approved
Power Supply
(HART compatible)
Output
Supply
+
_
G
Classified Location
Unclassified Location
+
_
G
Functional
earth
Functional
earth
Intrinsically safe design
FM Class I, Div.1, Group ABCD,
T4 for ambient temp. < 55°C
T6 for ambient temp. < 40°C
PH202S transmitter
+
-
Load
Resistance
Classified Location
Functional
earth
+
_
24 volts DC Nominal
Supply Voltage.
FM Approved safety barrier or
power supply
with Rint = 300
:
(HART compatible)
For electrical data:
see text below.
For electrical data:
see text below.
Intrinsically safe design
FM Class I, Div.1, Group ABCD,
T4 for ambient temp. < 55°C
T6 for ambient temp. < 40°C
PH202S transmitter
Figure 1
Figure 2
・
Electrical data of the PH202S.
-Supply circuit (ter and -):
Maximum input voltage Vmax = 31.5 V.
Maximum input current Imax = 100 mA.
Maximum input power Pmax = 1.2 W.
Effective internal capacitance Ci = 22 nF.
Effective internal inductance Li = 35
P
H.
- Sensor input circuit (terminals 11 through 17):
Maximum output voltage Vt = 14.4 V. Maximum output current It = 32.3 mA.
Maximum allowed external capacitance Ca = 600 nF.
Maximum allowed external inductance La = 34 mH
・
If Hand Held Terminal (HHT) is not connected to the power supply lines of the PH202S
(see figure 1):
Any FM Approved barrier or power supply may be used that meets the following requirements.
Voc or Vt
d
31.5 V ; Isc or It
d
100 mA; Ca
t
22nF + Ccable ; La
t
35
P
H + Lcable
If HHT is connected to the power supply lines of the PH202S (see figure 2):
The Hand Held Terminal must be FM Approved. Refer to the manufacturers control drawing of
the HHT and the barrier/power supply to determine the cable parameters.
(Voc or Vt ) + VHHT
d
31.5 V; (Isc or It ) + IHHT
d
100 mA;
Ca
t
22nF + CHHT ; La
t
35
P
H + LHHT
When installing this equipment, follow the manufacturer’s installation drawing.
Installation should be in accordance with ANSI/ISA RP 12.06.01 “Installation of Intrinsically Safe
Systems for Hazardous (Classified) Locations” and the National Electrical Code (ANSI/NFPA 70).
Control equipment connected to the barrier/power supply must not use or generate more than
250 Vrms or Vdc.
・
Resistance between Intrinsically Safe Ground and earth ground must be less than 1.0 Ohm.
・
In case of using cable glands in Outdoor location, they shall be UV rated or made of metal.
WARNING
- Substitution of components may impair Intrinsic Safety
- To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing
or read, understand and adhere to the manufacturer’s’live maintenance procedures.
Application Doc. No.: IKE024-A10 P.4-1 to P.4-2
Содержание PH202G (S)
Страница 5: ...IM 12B07D02 01E ...
Страница 9: ...IM 12B07D02 01E LT LV PL EST SLO H BG RO M CZ SK ...
Страница 13: ...IM 12B07D02 01E 1 4 Introduction ...
Страница 86: ...IM 12B07D02 01E Spare parts 9 1 9 SPARE PARTS See Customer Maintenance Parts List ...
Страница 96: ...IM 12B07D02 01E 10 10 Appendix ...
Страница 116: ...IM 12B07D02 01E 12 4 Appendix ...
Страница 120: ...IM 12B07D02 01E 12 8 Appendix ...
Страница 124: ...IM 12B07D02 01E 12 12 Appendix ...
Страница 128: ...IM 12B07D02 01E 12 16 Appendix ...