<2.CONNECTION>
2-3
IM 11G02Q02-01EN 2nd Edition : Sep. 04, 2020-00
n
SETTING OF COMMUNICATION CONDITION
The following list shows the required setting to establish communication between a master
device and IR202.
• Set up correctly so that the communication conditions of all IR202s must be same as
master’s
.
• Each IR202 in a line must be assigned different Station No. from each other. Station No. is
never shared with any other IR202 in the same line.
The table below shows the items to setup. Set them by operating the front panel keys.
Item
Value at delivery
Setting range
Remarks
Transmission speed 38400bps
Fixed (can not be changed)
Set up correctly so that the
communication conditions of
all IR202s must be same as
master’s
.
Data length
8 bits
Fixed (can not be changed)
Stop bit
1 bit
Fixed (can not be changed)
Parity setting
None
Fixed (can not be changed)
Station No.
1
0 to 31
(0 : communication function stop)
Each IR202 in a line must
be assigned different Station
No. from each other. Station
No. is never shared with any
other IR202 in the same line.
Set the station No. in the maintenance mode of IR202. (See the instruction manual.)