A2-71
IM 34M06C11-01E
(25) F3YD32-1R/F3YD64-1R Transistor Output Modules (with short-
circuit protector)
Item
F3YD32-1R
F3YD64-1R
Output type
Transistor contact (source type)
Number of points
32
64
Common line type
8 points/common
Isolation method
Photocoupler isolation
Withstanding voltage
1500V AC for one minute between the group of terminals for external
connection and the internal circuit
Rated load voltage
(operating load voltage
range)
12-24V DC
(10.2-26.4V DC)
Maximum load current
0.1A/point, 0.5A/common line
0.1A/point, 0.4A/common line
Response
time
OFF→ON
1ms max.
ON→OFF
1ms max.
ON voltage
0.5V DC max.
Off-time leak current
0.1mA max.
Service
life
Mechanical
―
Electrical
―
Protection
circuitry
Short-
circuit
Controlled short-circuit current
Overheat
Output shutdown
Surge protector
*1
None
Fuse
None
Dissipating current
170mA (5V DC)
275mA (5V DC)
Output display
*2
LED (Lit when output is on)
LED (Lit when output is on for 32
outputs selectable by a switch)
Output status when the
program stops
HOLD/RESET
*3
When a sequence CPU module is used:
Default: RESET
Can be set globally on a module-by-module basis
*4
When a BASIC CPU module is used:
No setting function
The status is always HOLD
External power supply
12-24V DC, 60mA
12-24V DC, 110mA
External connection
One 40-pin connector
Weight
110g
130g
*1:
If an inductive load, such as a relay, is to be connected, a surge protector is also required on the load side. Connect
a surge protector or a diode across the load nearby so that the module output terminal voltage will not exceed the
specified operating load voltage range. For details, see Subsection A3.6.5, “Connecting Output Devices.”
*2:
The contact operation of the output block of the circuit and the LED display operate independently and thus may be
inconsistent in the event of an error.
*3:
For information on the module’s behavior during a CPU failure, see subsection A4.3.3, “Indicating Problem Severity
and Status of Output Module.”
*4:
When F3SP22, F3SP28, F3SP38, F3SP53, F3SP58, F3SP59, F3SP66, F3SP67, F3SP71 or F3SP76 module is
used, this setting can be specified in 16-point units.
CAUTION
Ensure that the polarity of the external power supply is correct. Otherwise, a short-circuit
condition may damage an output element and cause smoldering and scattering of chips.
Beware that wrongly connecting a connector wired for F3XD32 or F3XD64 to the
module may disable the protectors and damage internal elements.
Содержание FA-M3V e-RT3 Plus
Страница 2: ...Blank Page ...
Страница 14: ...Blank Page ...
Страница 20: ...Blank Page ...
Страница 21: ...TOC A 1 IM 34M06C11 01E Hardware Manual Part A Standard Version IM 34M06C11 01E 40th Edition ...
Страница 22: ...Blank Page ...
Страница 34: ...Blank Page ...
Страница 159: ...A2 125 IM 34M06C11 01E Unit mm F3YD32 F3YD64 1M F3YD64 1A F3YD64 1F F3YD64 1P F3YD64 1R F3WD64 FA021106 VSD ...
Страница 160: ...Blank Page ...
Страница 201: ...A3 41 IM 34M06C11 01E Figure A3 37 Example of Installation Measures ...
Страница 220: ...Blank Page ...
Страница 232: ...Blank Page ...
Страница 241: ...TOC B 1 IM 34M06C11 01E Hardware Manual Part B FA M3 Value F3SC21 1N IM 34M06C11 01E 40th Edition ...
Страница 242: ...Blank Page ...
Страница 252: ...Blank Page ...
Страница 253: ...TOC C 1 IM 34M06C11 01E Hardware Manual Part C FA M3 Value II F3SC22 F3SC23 IM 34M06C11 01E 40th Edition ...
Страница 254: ...Blank Page ...
Страница 268: ...Blank Page ...
Страница 274: ...Blank Page ...