A7.2.3 Procedure for Setting I/O Conditions
This section describes the procedure for using the Shutdown Output on Transmission
Channel Error function.
A7.2.3.1 Setting Condition Switches
Setting the condition switch on the right side of the module
FA0721.VSD
Condition switch:
To enable the Shutdown Output function, you need to
set the condition switch located on the right side of the
Fiber-optic FA-bus module installed in the subunit.
Set DIP switch 1 according to the table in Section A2.4,
"Components and Their Functions".
1
2
3
6
7
5
4
8
O
F
F
1
2
3
4
5
6
7
8
Some modules may use the following DIP switch instead.
O
F
F
O
F
F
Figure A7.2 Condition Switches on Right Side of the Module