background image

 

 

 

Blank Page 

Содержание F3LR02-0N

Страница 1: ...le Notice KM67 for F3LR02 0N is discontinued by the cable manufacturer in June 2017 Therefore having 500m distance between unit with F3LR02 0N with newly engineering is impossible User s Manual IM 34M...

Страница 2: ...Blank Page...

Страница 3: ...M3 Model F3LR01 0N Model Name Fiber optic FA bus Module Model F3LR02 0N Model Name Fiber optic FA bus Type 2 Module Model F3LR02 1W Model Name FA bus Type 2 Module The document number for this manual...

Страница 4: ...rior notice Every effort has been made to ensure accuracy in the preparation of this manual However should any errors or omissions come to the attention of the user please contact the nearest Yokogawa...

Страница 5: ...o this product If component parts or consumable are to be replaced be sure to use parts specified by the company This product is not designed or manufactured to be used in critical applications which...

Страница 6: ...the software for use with each additional computer Copying the software for any purposes other than backup is strictly prohibited Store the original media that contain the software in a safe place Rev...

Страница 7: ...ve or flammable gases Where the product will not be exposed to mechanical vibration or shock that exceed specifications Where there is no chance the product may be exposed to radioactivity Use the cor...

Страница 8: ...water enter the module interior can cause malfunctions Do not use volatile solvents such as benzine or paint thinner or chemicals for cleaning as they may cause deformity discoloration or malfunctioni...

Страница 9: ...product for the external power supply use a SELV and limited energy circuit separated by reinforced insulation or double insulation from hazardous voltage Refer to the user s manual before connecting...

Страница 10: ...es Connect YHLS cable to SHIELD terminal Connect the DRAIN line of the YHLS cable to the SHIELD terminal of the YHLS master module securely Failing to do so may affect the performance of the YHLS syst...

Страница 11: ...d in the EU Batteries are included in some modules of this product The procedure is different when the user can remove or cannot remove Batteries the user can remove The battery of F3RP6 and F3RP7 can...

Страница 12: ...lows high speed communications For details on laying of fiber optic cables read the following technical documents available from Sumitomo Electric Industries Ltd Name of Document Document No Cabling I...

Страница 13: ...3SP67 6S IM34M06P14 01E Sequence CPU Network Communication Functions for F3SP66 4S F3SP67 6S IM34M06P14 02E F3SP22 F3SP28 F3SP38 F3SP53 F3SP58 or F3SP59 functions Sequence CPU Functions For F3SP22 0S...

Страница 14: ...tire document is strictly prohibited by the Copyright Law Except as stated above no part of the online manuals may be reproduced transferred sold or distributed to a third party in any manner either i...

Страница 15: ...ons on System Configuration A3 1 A3 1 2 Connection Topology A3 1 A4 Pre operation Setup and Cable Connection A4 1 A4 1 Startup Procedure A4 1 A4 2 Setting Switches A4 2 A4 2 1 Setting Unit Number Swit...

Страница 16: ...edure for Setting I O Conditions A7 3 A8 Errors and Troubleshooting A8 1 A8 1 Troubleshooting Flowcharts A8 1 A8 2 When RDY LED is Not Lit A8 2 A8 3 When ERR LED is Lit A8 3 Index Index A 1 Part B Fib...

Страница 17: ...on Checks B4 19 B4 5 1 Checking Transmission Loss B4 19 B4 5 2 LED Checks B4 20 B4 6 Precautions When Applying Power B4 21 B5 I O Refresh Time B5 1 B5 1 Estimating I O Refresh Time B5 1 B5 2 Example o...

Страница 18: ...Topology C3 5 C4 Pre operation Setup and Cable Connection C4 1 C4 1 Startup Procedure C4 1 C4 2 Setting Switches C4 2 C4 2 1 Setting Unit Number C4 3 C4 2 2 Enabling Disabling Shutdown Output on Tran...

Страница 19: ...C6 4 C6 2 Shutdown Output on Transmission Channel Error Function C6 5 C6 2 1 Overview of Shutdown Output Function C6 5 C6 2 2 Shutdown Output Function Setup C6 5 C6 3 Procedure for Setting Condition S...

Страница 20: ...Blank Page...

Страница 21: ...tion Aug 30 2019 00 Part A of the manual describes the Fiber optic FA bus Module F3LR01 0N Fiber optic FA bus Module Fiber optic FA bus Type 2 Module FA bus Type 2 Module Part A Fiber optic FA bus Mod...

Страница 22: ...Blank Page...

Страница 23: ...the following features Users need not be concerned with I O refresh time in ladder programming Subunits can include contact input output modules as well as RS 232 C communications modules and other sp...

Страница 24: ...es to configure a remote I O system however totally eliminates such headaches The following figure shows a system configuration example FA0121 VSD An example of a conveyer control system Assembly and...

Страница 25: ...specifications of the FA M3 Communications Specifications Table A2 3 Communications Specifications Item Specifications Transmission speed 10 Mbps Transmission media 2 core fiber optic cable hard plast...

Страница 26: ...ber Specifies the unit number 0 to 7 0 Unit number of main unit 1 to 7 Unit number of subunits 8 to 9 Cannot be used Optical connector port 1 to 6 if F3SP20 or F3SP30 is used Right Side View Switch Nu...

Страница 27: ...n Depth When installing the module always take into consideration space required for bending of cords and cables Table A2 4 Bending Radius Bending Radius r mm KF 07 a 18 3 CF 2071 CF 2071H a 35 0 Duri...

Страница 28: ...Blank Page...

Страница 29: ...umber of connectable subunits 7 max Number of Fiber optic FA bus modules installable in a main unit 7 max Number of Fiber optic FA bus modules installable in a subunit 1 max Modules installable in a s...

Страница 30: ...ain Star Configuration FA0322 VSD FA500 Main unit Subunits 7 max FA M3 FA M3 FA M3 FA500 FA M3 FA M3 L3LR01 0N FA500 LR20 0N 6 max when using F3SP20 or F3SP30 When using FA M3 with FA500 modules do no...

Страница 31: ...ts on How to Lay Fiber optic Cables under Introduction Build system configuration Determine instrument layout Determine routes for Fiber optic cables Operation Perform pre operation checks Turn on pow...

Страница 32: ...d in the main unit set the unit number to 0 Table A4 1 Unit Number Switch Settings Switch Setting Description 0 For modules installed in the main unit Factory setting 0 1 to 7 For modules installed in...

Страница 33: ...witch Settings Switch Number Function ON OFF Factory Setting 1 Shutdown output on transmission channel error Shutdown Hold output ON 2 to 4 Not Used OFF Note If the module has its Shutdown Output func...

Страница 34: ...CAUTION Always switch off the power before attaching or detaching a module F01 VSD Base module This module Anchor pin Figure A4 3 Attaching Detaching the Module CAUTION DO NOT bend the connector on th...

Страница 35: ...Figure A4 4 Securing Screws on Fiber optic FA bus Modules A4 3 4 Installation Depth The module s installation depth is 85 5 mm from the rear of the base module to the front of this module However if...

Страница 36: ...Fiber optic Cables for Indoor Use with Tension Members with bonding and polishing treatment on optical connector Model Suffix Code Style Code Option Code Description Max Transmission Loss dB Applicab...

Страница 37: ...00 Cable for outdoor system expansion 800 m a pulling eye on one end 5 92 900 Cable for outdoor system expansion 900 m a pulling eye on one end 6 47 L01 Cable for outdoor system expansion 1000 m a pul...

Страница 38: ...th sheath removed End with sheath removed 200 50mm e 0 L tolerance e 0 L tolerance 200 50mm 200 50mm 200 50mm FA020709 VSD Note Fiber optic cable KM61 KM62 and KM67 is available in two types of A and...

Страница 39: ...AP 8 4mm 1 0 10 0mm 1 0 External Dimensions Fiber optic single core cord Tension member plastic covered steel wire Lacing plastic lacing Inclusion plastic yarn or fiber Holding tape plastic fiber Heat...

Страница 40: ...R02 2 SF2 C LAP for outdoor use flame retardant cable equivalent of VW 1 2 CCV HC 20 07 F3LR01 1 F3LR02 1 Table A4 6 Cords and Cables with Connectors on Both Ends from Sumitomo Electric Type Model Spe...

Страница 41: ...tical connector connection tool Solderless cut type CAK 1020 CAK 0057 Optical power tester for testing work on optical connector CAT 2700 Master fiber set for testing work on optical connector CAT 200...

Страница 42: ...cable connector always hold the connector never the cable and then insert it until it clicks into place Then hold the connector and pull it lightly to make sure that it is correctly seated Detaching...

Страница 43: ...s or fiber optic cables keep the elongation within 0 7 of permissible elongation percentage When the cable is secured the elongation should be within 0 2 of permissible elongation percentage Beyond th...

Страница 44: ...70 1 10 2 60 80 1 10 2 60 90 1 10 2 60 100 1 10 2 60 110 1 19 2 69 120 1 28 2 78 130 1 37 2 87 140 1 45 2 95 150 1 54 3 04 160 1 62 3 12 170 1 71 3 21 180 1 79 3 29 190 1 87 3 37 200 1 95 3 45 Table A...

Страница 45: ...is not lit it may be because the Fiber optic FA bus module is not properly mounted to the base module Turn off the power and attach the module to the base module correctly The ERR LED indicator must b...

Страница 46: ...the powering sequence described above is not adhered to you should write your application so that it checks the status of subunits using the special registers as listed on the next page In this case...

Страница 47: ...7 1 When this module F3LR01 0N installed in a main unit or subunit is recognized as accessible the bit corresponding to its slot position in the Module Recognition special registers is set to 1 Howeve...

Страница 48: ...Blank Page...

Страница 49: ...is mounted and is a 3 digit integer with the following structure Slot number 1 within a unit 01 to 16 Unit number Main unit 0 Subunit 1 to 7 2 1 Slot number runs sequentially from 01 to 16 starting fr...

Страница 50: ...011 012 013 014 015 016 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 701 702 703 704 705 706 707 708 709 710 711 712...

Страница 51: ...I O refresh time There are 2 types of access namely read input and write output Calculate the I O refresh time for each access type using the following formula and sum the values I O refresh time for...

Страница 52: ...utput 32 point module x 1 Figure 6 1 An Example of I O Refresh Time Calculation F3SP22 28 38 53 58 59 66 or 67 Step 1 Calculate the time dependant on transmission distance 1 0 s x 150 m 100 m 1 5 s St...

Страница 53: ...of the Fiber optic FA bus modules mounted in each unit The following figure shows the relationship between fiber optic cable discontinuity and the status of the LED of the Fiber optic FA bus module FA...

Страница 54: ...2 2 Shutdown Output of Subunit Note To configure the system to reset the output of output modules in the event of a power interruption on the main unit or a transmission channel error turn on the Shut...

Страница 55: ...the right side of the module FA0721 VSD Condition switch To enable the Shutdown Output function you need to set the condition switch located on the right side of the Fiber optic FA bus module installe...

Страница 56: ...Setup from the Configuration pane of the displayed Project Settings Configuration window 3 Click the cell for the slot installed with the module to be configured Select the Output Setup tab under Det...

Страница 57: ...er CPU failure 0 Hold 1 Reset Unused always 0 Register 4 terminals 25 to 32 Register 3 terminals 17 to 24 Register 2 terminals 9 to 16 Register 1 terminals 1 to 8 Register 4 Register 3 Register 2 Regi...

Страница 58: ...tings from the WideField3 menu bar 2 Select Error Handling Setup from the Configuration pane of the displayed Project Settings Configuration window 3 Select Continue to run or Stop for I O module Erro...

Страница 59: ...ot accordingly See Section A8 2 When RDY LED is not Lit Set the unit number correctly Replace Fiber optic FA bus module Error in Fiber optic FA bus module RDY LED of Fiber optic FA bus module lit Is u...

Страница 60: ...nto place see Section A4 3 Replace the base module Replace the power supply module or the base module Is correct voltage supplied to the power supply module Is RDY LED lit on other modules Is RDY LED...

Страница 61: ...e Turn on power to all other units Set switches inside the side cover correctly Set SW2 to SW4 to off Is fiber optic cable connected Are all units switched on Is there a cable discontinuity Are the si...

Страница 62: ...Blank Page...

Страница 63: ...ble cores A4 6 L LED indicators ERR red A2 2 A4 14 A7 1 RDY green A2 2 A4 14 A7 1 M main unit A3 1 A4 2 module recognition special registers A4 17 P precautions when applying power A4 16 pulling eye A...

Страница 64: ...Blank Page...

Страница 65: ...g 30 2019 00 Part B of the manual describes the Fiber optic FA bus Type 2 Module F3LR02 0N Fiber optic FA bus Module Fiber optic FA bus Type 2 Module FA bus Type 2 Module Part B Fiber optic FA bus Typ...

Страница 66: ...Blank Page...

Страница 67: ...ic FA bus Type 2 modules in the FA M3 main unit and subunits and connecting them using fiber optic cables Modules in the subunits can then be handled like modules in the main unit 1 I O refers to cont...

Страница 68: ...alled in the master station Simple setup No specific remote I O configuration environment setup is required Optical transmission The use of fiber optic cables for transmission delivers high noise immu...

Страница 69: ...s are used Early error location reporting RAS 1 function The alarm monitor and error log functions facilitate identification of error locations such as a cable discontinuity When an error is detected...

Страница 70: ...Blank Page...

Страница 71: ...1 4 km 1 Maximum distance between units 500 m Transmission channel configuration Star daisy chain or loop configuration Maximum number of substations 56 substations 2 RAS features Shutdown output on...

Страница 72: ...base modules F3BU09 F3BU13 F3BU16 Optical connector port Attach a dust cap accessory is not using the port 2 Right Side View This figure is drawn with the panel cover removed Condition switches Rear F...

Страница 73: ...Dimensions of F3LR02 0N Installation Depth When installing the module always take into consideration space required for bending of fiber optic cords and cables Table B2 4 Bending Radius Bending Radius...

Страница 74: ...Blank Page...

Страница 75: ...st unit in a Fiber optic FA bus Type 2 system Whether it is equivalent to a subunit depends on whether we have a split unit configuration In a split unit configuration a substation is a division of a...

Страница 76: ...available for splitting subunits Select an appropriate pattern to suit your application 1 2 2 3 3 4 8 F3BU09 F3BU04 F3BU06 F3BU06 F3BU04 F3BU04 F3BU04 F3BU06 Number of substations F3BU04 F3BU04 F3BU04...

Страница 77: ...ere a module is mounted and is a 3 digit integer with the following structure Slot number within a unit 01 to 16 Unit number main unit 0 Subunit 1 to 7 Slot number runs sequentially from 01 to 16 star...

Страница 78: ...m 7 substations Subunit 6 substation 6 Subunit 5 substation 5 Subunit 4 substation 4 Subunit 3 substation 3 Subunit 2 substation 2 Subunit 1 substation 1 101 102 103 104 105 106 107 108 109 110 111 1...

Страница 79: ...404 405 406 407 408 409 410 411 412 413 414 415 416 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 701 702 703 704 705...

Страница 80: ...Link H modules FA Link H2 modules Fiber optic FA Link H modules Hard Disk modules and PC Card modules B3 5 Connection Topology Fiber optic FA bus Type 2 modules can be connected using a loop daisy ch...

Страница 81: ...Fiber optic Cable Fiber optic Cable Fiber optic Cable Fiber optic Cable u4 s1 6 u2 s1 9 u1 s9 12 Fiber optic FA bus Type 2 module F3LR02 0N FB0352 VSD Power supply module Power supply module Substatio...

Страница 82: ...pe 2 module F3LR02 0N Power supply module Substation Unit 1 Slots 1 to 6 Substation Unit 1 Slots 9 to 12 Power supply module Power supply module Fiber optic Cable Fiber optic Cable Power supply module...

Страница 83: ...VSD F3LR02 0N Power supply module Unused port Power supply module Power supply module Power supply module Fiber optic Cable Unused port Fiber optic cable Substation Unit 1 Slots 1 to 6 Substation Uni...

Страница 84: ...the substations Design Flow System configuration Number of substations x required Select split pattern and unit numbers End Check total distance x 7 Selectable Is total within range NO 2 NO YES FB036...

Страница 85: ...um Total Distance m Daisy Chain Loop Daisy Chain or Loop 1 500 1000 17 880 2 1000 1500 18 840 3 1420 19 800 4 1380 20 760 5 1340 21 730 6 1300 22 690 7 1260 23 650 8 1230 24 610 9 1190 25 570 10 1150...

Страница 86: ...aisy chain configurations 1 Older versions of the F3BU04 or F3BU06 base module do not allow slot number change Check the nameplate of the base module for its version There are two types of nameplate n...

Страница 87: ...uments on How to Lay Fiber optic Cables under Introduction Build system configuration Determine instrument layout Determine routes for fiber optic cable Operation Pre operation checks Turn on power Co...

Страница 88: ...address number setting factory setting 0 Setting range 0 unit number when installed in main unit 1 unit number of subunit when installed in subunit 8 9 cannot be used 1 Connector port Condition switch...

Страница 89: ...9 Not used cannot be used Note Always set the unit number of the Fiber optic FA bus Type 2 module installed in the main unit to 0 With any other value the memory of the CPU module may be cleared The u...

Страница 90: ...y module F3BU05 Left Slot Number Slot Number 1 1 2 3 4 5 9 9 10 11 12 13 FB04231 VSD Power Supply Module F3BU06 Left Slot Number Slot Number 1 1 2 3 4 5 6 9 9 10 11 12 13 14 FB0423 VSD Power Supply Mo...

Страница 91: ...or a powered off intermediate substation as a major failure of the sequence CPU module Thus if a transmission channel error occurs with Condition Switch No 1 set to ON the output is either shut down...

Страница 92: ...ng Before performing this setup confirm the length of fiber optic cables Table B4 3 Light Intensity Switches SW Number Description Distance Between Stations Length of Fiber optic Cable m 5 Light inten...

Страница 93: ...ION Always switch off the power before attaching or detaching a module F01 VSD Base module This module Anchor pin Figure B4 2 Attaching Detaching the Module CAUTION DO NOT bend the connector on the re...

Страница 94: ...gure B4 3 Securing Screws on Fiber Optic FA bus Type 2 Module B4 3 4 Installation Depth The module s installation depth is 85 5 mm from the rear of the base module to the front of this module However...

Страница 95: ...nel enclosure 1 0 m 2 60 003 Cord for system expansion inside panel enclosure 3 0 m 2 60 Fiber optic Cables for Indoor Use with Tension Members with bonding and polishing treatment on optical connecto...

Страница 96: ...one end 7 00 KM67 300 Cable for outdoor system expansion 300 m a pulling eye on one end 3 35 400 Cable for outdoor system expansion 400 m a pulling eye on one end 4 16 500 Cable for outdoor system ex...

Страница 97: ...tective coating End with sheath removed End with sheath removed 200 50mm 200 50mm e 0 L tolerance e 0 L tolerance Note Fiber optic cable KM61 KM62 and KM67 is available in two types of A and B with op...

Страница 98: ...8 4mm 1 0 10 0mm 1 0 External Dimensions Fiber optic single core cord Tension member plastic covered steel wire Lacing plastic lacing Inclusion plastic yarn or fiber Holding tape plastic fiber Heat r...

Страница 99: ...R02 2 SF2 C LAP for outdoor use flame retardant cable equivalent of VW 1 2 CCV HC 20 07 F3LR01 1 F3LR02 1 Table4 7 Cords and Cables with Connectors on Both Ends from Sumitomo Electric Type Model Speci...

Страница 100: ...tical connector connection tool Solderless cut type CAK 1020 CAK 0057 Optical power tester for testing work on optical connector CAT 2700 Master fiber set for testing work on optical connector CAT 200...

Страница 101: ...a fiber optic cable connector always hold the connector never the cable and then insert it until it clicks into place Then hold the connector and pull it lightly to make sure that it is correctly sea...

Страница 102: ...cables may break For this purpose refer to Table 4 9 and take care not to subject fiber optic cables to excessive tensile impact bending or twisting Always pull a fiber optic cable by its tension mem...

Страница 103: ...configuration Note For details on unit representation for the system configuration examples given in this section see the text on Unit Representation in Section B3 5 Connection Topology Example of Dai...

Страница 104: ...station Substation Substation Figure B4 8 Loop Configuration Note 1 When configuring a daisy chain including star configuration When connecting a master station and a substation Connect port 1 or port...

Страница 105: ...100 1 10 2 60 200 1 95 3 45 Table B4 11 Transmission Loss Table for Fiber optic Cables 200 m to 500 m Length of Fiber optic Cable HG 20 08 Maximum Transmission Loss dB Length of Fiber optic Cable HG 2...

Страница 106: ...k whether the ERR indicator turns off If the ERR indicator is still on it may be due to a transmission channel error such as cable discontinuity See Section B7 3 When ERR1 LED or ERR2 LED is Lit and t...

Страница 107: ...here the powering sequence described above is not adhered to you should write your application so that it checks the status of subunits using the Module Recognition special registers In this case do n...

Страница 108: ...7 1 When this module F3LR02 0N installed in a main unit or subunit is recognized as accessible the bit corresponding to its slot position in the Module Recognition special registers is set to 1 Howeve...

Страница 109: ...e There are 2 types of access namely read input and write output Calculate the I O refresh time for each access type using the following formula and sum the values I O refresh time for each access typ...

Страница 110: ...t 32 point module x 2 Output 32 point module x 1 Input 32 point module x 3 Output 32 point module x 2 Figure B5 1 An Example of I O Refresh Time Calculation for F3SP22 28 38 53 58 59 66 67 Step 1 Calc...

Страница 111: ...tected in a transmission channel the system can automatically change the transmission channel configuration so as to allow normal system operation to continue This function is known as loop switching...

Страница 112: ...ff main unit or a powered off substation in the transmission channel as a major failure of the sequence CPU module Thus if a transmission channel error occurs with Condition Switch No 1 set to ON the...

Страница 113: ...ications via primary loop Error Discontinuity in primary loop Discontinuity in primary and secondary loops Error Discontinuity in both primary and secondary loops Port 1 Port 2 1 Discontinuity in prim...

Страница 114: ...function automatically cuts off the unreachable stations so that the station immediately preceding the point of discontinuity now becomes the terminal station and communications can continue For this...

Страница 115: ...les of substations connected to the channel The shutdown output on transmission channel error function is available only for configurations with one CPU module not a multi CPU system Note This functio...

Страница 116: ...pen Hold Shorted Open Hold Don t Care Stop Continue operation Continue operation Open Shorted Continue operation Open Shorted Continue operation Substation A Substation enable to access by master stat...

Страница 117: ...tup in Project is Reset OFF In case of using a FAIL contact of power supply module while the program stops choose one in the main unit and take external measures outside the system for safety operatio...

Страница 118: ...Side of the Module FB0631 VSD Condition switch To enable the Shutdown Output function you need to set the condition switch located on the right side of the fiber optic FA bus Type 2 module installed...

Страница 119: ...Setup from the Configuration pane of the displayed Project Settings Configuration window 3 Click the cell for the slot installed with the module to be configured Select the Output Setup tab under Deta...

Страница 120: ...ster CPU failure 0 Hold 1 Reset Unused always 0 Register 4 terminals 25 to 32 Register 3 terminals 17 to 24 Register 2 terminals 9 to 16 Register 1 terminals 1 to 8 Register 4 Register 3 Register 2 Re...

Страница 121: ...nu bar 2 Select Error Handling Setup from the Configuration pane of the displayed Project Settings Configuration window 3 Select Continue to run or Stop for I O module Error and Subunit Communication...

Страница 122: ...an error is generated in a module other than the Fiber optic FA bus type 2 module To decide whether the cause of a lit LED lies in a Fiber optic FA bus type 2 module check the status of the RDY ERR1...

Страница 123: ...tation 1 Substation 2 ERR1 lit Cable discontinuity ERR2 lit ERR lit FB0641 VSD CPU Power supply Power supply Power supply The statuses of the ERR and ALM LEDs depend on the configuration setup as show...

Страница 124: ...Substation 1 Substation 2 Cable discontinuity ERR2 lit ERR lit FB0642 VSD CPU Power supply Power supply Power supply The statuses of the ERR and ALM LEDs depend on the configuration setup as shown in...

Страница 125: ...tation 1 Substation 2 ERR1 lit ERR2 lit ERR lit FB0643 VSD CPU Cable discontinuity Power supply Power supply Power supply The statuses of the ERR and ALM LEDs depend on the configuration setup as show...

Страница 126: ...ation Substation 1 Substation 2 ERR1 lit Cable discontinuity FB0644 VSD Power supply Power supply Power supply A subunit line switchover alarm is output The ALM LED is lit but the ERR LED is not lit a...

Страница 127: ...ation Substation 1 Substation 2 ERR2 lit Cable discontinuity FB0645 VSD Power supply Power supply Power supply A subunit line switchover alarm is output The ALM LED is lit but the ERR LED is not lit a...

Страница 128: ...Substation 1 Substation 2 ERR1 lit Cable discontinuity FB0646 VSD Power supply Power supply Power supply ERR2 lit The statuses of the ERR and ALM LEDs depend on the configuration setup as shown in Tab...

Страница 129: ...occurred we mean either a subunit communication error or a subunit line switchover as described above has occurred Special relays The following special relays indicate the communication status of a s...

Страница 130: ...D On Off timing of special relays in the event of cable discontinuity in one of two cables in a cable pair M66 Channel normal M210 Channel error M211 Channel switched All subunits switched on one cabl...

Страница 131: ...u1 s1 9 u2 s1 6 u3 s1 3 FB064B VSD Port 1 Port 2 Figure B6 13 Example of Cable Discontinuity Note A slot number displayed on the system log screen indicates the slot where a Fiber optic FA bus Type 2...

Страница 132: ...of Cable Discontinuity Note A slot number displayed on the alarm display screen indicates the slot where a Fiber optic FA bus Type 2 module is installed It does not indicate the switch settings unit n...

Страница 133: ...ps the output Figure B6 17 Example of Cable Discontinuity Note A slot number displayed on the system log screen indicates the slot where a Fiber optic FA bus Type 2 module is installed It does not ind...

Страница 134: ...Blank Page...

Страница 135: ...ectly Replace Fiber optic FA bus Type 2 module I O error in I O module of the subunit accessed by ladder sequence program Is the RDY LED of the module lit Is the ERR1 or ERR2 LED of the module lit Are...

Страница 136: ...t clicks into place Replace the base module Replace the power supply module or the base module Is correct voltage applied to the power supply module Is RDY LED lit on other modules Is RDY LED lit Is m...

Страница 137: ...onnect fiber optic cable Replace fiber optic cable Turn on power to all units Set side switches correctly Is fiber optic cable connected Are all units switched on Is there a cable discontinuity Are th...

Страница 138: ...Blank Page...

Страница 139: ...number precautions when changing B3 12 startup procedure B4 1 station B3 1 master station B3 1 station address B3 1 substation B3 1 B3 2 terminal station B3 1 subunit B3 1 communication error B6 1 B6...

Страница 140: ...Blank Page...

Страница 141: ...h Edition Aug 30 2019 00 Part C of the manual describes the FA bus Type 2 Module F3LR02 1W Fiber optic FA bus Module Fiber optic FA bus Type 2 Module FA bus Type 2 Module Part C FA bus Type 2 Module I...

Страница 142: ...Blank Page...

Страница 143: ...by installing FA bus Type 2 modules in the FA M3 main unit and subunits and connecting them to each other Modules in the subunits can then be handled like modules in the main unit 1 I O refers to con...

Страница 144: ...ccessed the same way as modules installed in the main unit 2 Except for Ethernet Interface modules NX Interface modules FL net Interface modules FA Link modules FA Link H modules FA Link H2 modules Fi...

Страница 145: ...ons Table C2 3 Communications Specifications Item Specifications Transmission speed 10 Mbps Transmission media Two pair 4 wire shielded cable impedance 100 Transmission distance Maximum distance betwe...

Страница 146: ...t number of the main unit 1 to 7 unit number of a subunit 8 to 9 cannot be used factory setting is 0 Right Side View FC0232 VSD This figure is drawn with the panel cover removed Condition switches Rea...

Страница 147: ...Edition Aug 30 2019 00 C2 5 External Dimensions External Dimensions unit mm r FC0241 VSD RDY ERR1 ERR2 SUB UNIT NO REMOTE LR02 1W 0 1 2 3 4 5 6 7 8 9 1 R R T T R R T T SHIELD 0 2 Figure C2 2 External...

Страница 148: ...Blank Page...

Страница 149: ...system expansion through FA bus Type 2 modules The following table lists some system configuration terms used in this manual Table C3 2 Terminology Term Meaning Station The unit with FA bus Type 2 mod...

Страница 150: ...ere a module is mounted and is a 3 digit integer with the following structure Slot number within a unit 01 to 16 Unit number main unit 0 Subunit 1 to 7 Slot number runs sequentially from 01 to 16 star...

Страница 151: ...206 207 208 209 210 211 212 213 214 215 216 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 501 502 503 504 505 506 507...

Страница 152: ...e 2 System Item Specifications Number of FA bus Type 2 modules installable in a main unit 7 Number of FA bus Type 2 modules installable in a subunit 1 max Modules installable in a subunit All I O modu...

Страница 153: ...the other station Always form a loop using only one FA bus Type 2 module in the main unit In a loop configuration if a cable discontinuity or subunit down occurs the built in RAS function will operat...

Страница 154: ...1W Power supply Power supply Power supply Power supply FC0353 VSD Power supply Power supply Power supply Power supply Power supply Main unit Subunit 3 Subunit 1 Subunit 2 Subunit 5 terminal station Su...

Страница 155: ...ontinuity or subunit shutdown will not affect the communication between the main unit and the other subunits Main unit Subunit 1 Subunit 2 Subunit 3 Subunit 4 FC0354 VSD F3LR02 1W Unused port Unused p...

Страница 156: ...Blank Page...

Страница 157: ...startup procedure when using FA bus Type 2 modules Mount FA bus Type 2 module on base module Set switches of FA bus Type 2 module Connect cables Turn on power Pre operation checks Operation Determine...

Страница 158: ...lit off lit off Hold 3 Shutdown Use port 1 only Use both ports 1 and 2 Star or daisy chain Loop Always off OFF ON OFF ON OFF ON OFF Unit address number setting factory setting 0 Setting range 0 unit...

Страница 159: ...gs Switch Setting Description 0 For modules installed in the main unit Factory setting 0 1 to 7 For modules installed in subunits 8 to 9 Not used cannot be used Note Always set the unit number of the...

Страница 160: ...cable or a powered off main unit or a powered off intermediate station as a major failure of the sequence CPU module Thus if a transmission channel error occurs with Condition Switch No 1 set to ON t...

Страница 161: ...s transmission channel configurations Table C4 5 Transmission Channel Configuration Value Used Ports OFF Star configuration or daisy chain configuration ON Loop configuration Note All FA bus Type 2 mo...

Страница 162: ...ION Always switch off the power before attaching or detaching a module F01 VSD Base module This module Anchor pin Figure C4 2 Attaching Detaching the Module CAUTION DO NOT bend the connector on the re...

Страница 163: ...environments fasten the module with a screw Use screws of type listed in the table below Insert these screws into the screw holes on top of the module and tighten them with a Phillips screwdriver Scre...

Страница 164: ...e tin plated soft copper braided shield Drain wire size 23AWG 22AWG Outer diameter Approx 8 0 mm Approx 11 0 mm Conductor resistance 20 C 65 7 km max 37 8 km max Dielectric strength through air Withst...

Страница 165: ...The above test results are obtained under the specified test conditions and should not be interpreted as guaranteed values for actual usage in real applications C4 4 3 Wiring of Recommended Cables Tab...

Страница 166: ...lowable tension No tensile force exceeding the maximum allowable tensile load should be applied during cable laying to prevent excessive conductor elongation loose connector loose wire open circuit or...

Страница 167: ...cable is not tensioned Maximum allowable tension N 7 kg mm2 x 4 No of cable wires x 0 5 cross sectional area of conductor in mm2 x 9 8 137 N Maximum allowable tension of copper conductor 7 kg mm2 Wir...

Страница 168: ...n may deteriorate or even crack thus leading to insulation breakdown if exposed to direct sunlight or fluorescent light over an extended period of time If the cable is to be used in such environments...

Страница 169: ...odel FMC1 5 5 ST3 5 RF from Phoenix Contact Port 1 Port 2 Pin 5 Pin 1 Pin 5 Pin 1 FC0450 vsd Figure C4 6 Connectors Installed on the Module front view Table C4 13 Connector Pin Assignment Connector Pi...

Страница 170: ...ators are on red communication is not allowed If the power of the adjacent station is off turn on its power and check whether the ERR indicator turns off If the ERR indicator is still on it may be due...

Страница 171: ...here the powering sequence described above is not adhered to you should write your application so that it checks the status of subunits using the Module Recognition special registers In this case do n...

Страница 172: ...7 1 When this module F3LR02 1W installed in a main unit or subunit is recognized as accessible the bit corresponding to its slot position in the Module Recognition special registers is set to 1 Howeve...

Страница 173: ...access type using the following formula and sum the values I O refresh time for each access type Time dependant on access type Time dependant on transmission distance Access type Formula Number of mod...

Страница 174: ...e x 2 Output 32 point module x 1 Input 32 point module x 3 Output 32 point module x 2 Figure C5 1 An Example of I O Refresh Time Calculation for F3SP28 38 53 58 59 66 67 Step 1 Calculate the time depe...

Страница 175: ...continue operation in the event of a communication error and turn off the Shutdown Output function A loop configuration secures two transmission loops a primary loop and a secondary standby loop The p...

Страница 176: ...chains in the event of cable discontinuity in both the primary and secondary loops accessing the subunit may cause an error In such situations you should include program codes for retry processing Wh...

Страница 177: ...loop Normal operation communications via primary loop Error Discontinuity in primary loop Discontinuity in primary and secondary loops Error Discontinuity in both primary and secondary loops Port 1 Po...

Страница 178: ...station and communications can continue For this function to work properly the cables must be correctly connected Terminal station Main unit Subunit 1 Subunit 2 ERR2 LED lit Loop back ERR1 LED lit Ca...

Страница 179: ...F3SP71 or F3SP76 this function is available for output modules with 32 outputs or less as well as F3YD64 1F F3WD64 3F F3WD64 4F and F3YD64 1P Do not enable the Shutdown Output function in a loop confi...

Страница 180: ...n Shorted Open Shutdown Don t Care Stop Continue operation Continue operation Shorted Open Shutdown 2 Shorted Open Continue operation 2 Hold Stop Don t Care Shorted Open Hold Shorted Open Hold Don t C...

Страница 181: ...FC0621_1 VSD Main unit Example 2 FC0621_2 VSD Cable discontinuity Main unit Subunit 1 A Subunit 2 C Subunit 3 C ERR2 lit ERR1 lit Example 3 FC0621_3 VSD ERR2 lit Cable discontinuity Main unit Subunit...

Страница 182: ...Setting the Condition Switches Located on the Right Side of the Module FC0631 VSD Condition switch To enable the Shutdown Output function you need to set the condition switch located on the right side...

Страница 183: ...elect the DIO Setup tab from the Configuration dialog box 3 Double click the field for the slot for which you wish to perform setup in the DIO Setup window The DIO Setup window for the slot opens Set...

Страница 184: ...of a master CPU failure 0 Hold 1 Reset Unused always 0 Register 4 terminals 25 to 32 Register 3 terminals 17 to 24 Register 2 terminals 9 to 16 Register 1 terminals 1 to 8 Register 4 Register 3 Regist...

Страница 185: ...from the Configuration dialog box 3 On the Operation Control window select Run or Stop for I O Module Error and Subunit Communication Error in the Error Time Action group Figure C6 6 Operation Control...

Страница 186: ...e 2 module To decide whether the cause of a lit LED lies in the FA bus Type 2 module check the status of the RDY ERR1 port 1 and ERR2 port 2 LEDs of the FA bus Type 2 module mounted in each unit The f...

Страница 187: ...it 1 Subunit 2 ERR1 lit Cable discontinuity ERR2 lit ERR lit Power supply Power supply Power supply Bold line indicates active line The statuses of the ERR and ALM LEDs depend on the configuration set...

Страница 188: ...Subunit 1 Subunit 2 Cable discontinuity ERR2 lit ERR lit Power supply Power supply Power supply Bold line indicates active line The statuses of the ERR and ALM LEDs depend on the configuration setup a...

Страница 189: ...it 1 Subunit 2 ERR1 lit ERR2 lit ERR lit Cable discontinuity Power supply Power supply Power supply Bold line indicates active line The statuses of the ERR and ALM LEDs depend on the configuration set...

Страница 190: ...Subunit 1 Subunit 2 ERR1 lit Cable discontinuity Power supply Power supply Power supply Bold line indicates active line A subunit line switchover alarm is output The ALM LED is lit but the ERR LED is...

Страница 191: ...Subunit 1 Subunit 2 ERR2 lit Cable discontinuity Power supply Power supply Power supply Bold line indicates active line A subunit line switchover alarm is output The ALM LED is lit but the ERR LED is...

Страница 192: ...ubunit 1 Subunit 2 ERR1 lit Cable discontinuity Power supply Power supply Power supply ERR2 lit Bold line indicates active line The statuses of the ERR and ALM LEDs depend on the configuration setup a...

Страница 193: ...ication error or a subunit line switchover as described above has occurred Special relays The following special relays indicate the communication status of a subunit Table C6 8 Special Relays Category...

Страница 194: ...211 Channel switched All subunits switched on one cable of cable pair broken Broken cable removed Replaced with good cable Setup operation check alarm FB0649 VSD Figure C6 13 On Off Timing of Special...

Страница 195: ...ntinuity Main unit Subunit 1 Subunit 2 Subunit 3 FC064B VSD Port 1 Port 2 Figure C6 15 Example of Cable Discontinuity Note A slot number displayed on the system log screen indicates the slot where the...

Страница 196: ...RR1 lit Figure C6 17 Example of Cable Discontinuity Note A slot number displayed on the alarm display screen indicates the slot where the FA bus Type 2 module is installed However when SPU errors 11 1...

Страница 197: ...Type 2 module of subunit 2 stops its output Figure C6 19 Example of Cable Discontinuity Note A slot number displayed on the system log screen indicates the slot where the FA bus Type 2 module is inst...

Страница 198: ...Blank Page...

Страница 199: ...s not lit Set the unit number correctly Replace FA bus Type 2 module I O error in I O module of the subunit accessed by ladder sequence program Is the RDY LED of the module lit Is the ERR1 or ERR2 LED...

Страница 200: ...ace the base module Replace the power supply module or the base module Is correct voltage applied to the power supply module Is RDY LED lit on other modules Is RDY LED lit Is module mounted properly i...

Страница 201: ...ansmission cable Turn on power to all units Set side switches correctly Is transmission cable connected Are all units switched on Is there a transmission cable discontinuity Are the side switches set...

Страница 202: ...Blank Page...

Страница 203: ...rain insulation example Approx 8 mm diameter for fixed cable with 22 AWG drain or Approx 11 mm diameter for flexible cable with 22 AWG drain Insulation tube Pin terminal For fixed cable example Manufa...

Страница 204: ...The picture shows wire stripper model P 911 with black handle from Hozan Tool Industrial Model P 90 A has a green handle instead Wire stripper Note Always use a recommended wire stripper for the KM81...

Страница 205: ...ided shield 2 Remove the exposed tin plated soft copper braided shield aluminum mylar tape and plastic stuffing Take care not to damage the exposed drain wire Tin plated soft copper braided shield Dra...

Страница 206: ...le insulation and the exposed wires Then shrink the tube with a heat gun Insulation tube 7 Fully insert each pin terminal into the connector Ensure that each pin terminal is securely inserted in the c...

Страница 207: ...tion C3 5 C6 16 loop switching C6 1 M main unit C3 1 C3 4 module recognition special registers C4 16 P precautions when applying power C4 15 S shutdown output C4 4 C6 1 C6 5 star configuration C3 7 st...

Страница 208: ...Blank Page...

Страница 209: ...orrections Jun 2008 4th Edition Added FA bus Type 2 Module F3LR02 1W Jan 2008 3rd Edition F3SP66 and F3SP67 included in applicable CPU modules data and editorial corrections July 2003 2nd Edition Adde...

Страница 210: ...Blank Page...

Отзывы: