Explanation Programming Points

6.1  Zero Adjustment 

(ZERO)

The transmitter is set to 0 mbar at atmospheric 

pressure. 
The 

ZERO

 can be adjusted at a lower or higher 

point. This will be explained step by step by an 

example.
Example: Increase ZERO t

o

 100 mBar.

1.

 The measuring unit of the transmitter is set to

mBar. If not this can be selected by choosing 

the right measuring unit in program point 

P104 

– UNITS (paragraph 6.4)

2.

Navigate to program point 

P101 - ZERO

Value

, and push the navigation button to enter

the menu.

3.

 Two choices appear on the screen: “

set

manual

” and “

use process

Set manual

 = Configuration without test

pressure.

Use process

 = Configuration with applied

pressure.

4.

Choose  “

set manual

”, +000.0 (mBar) will

appear on the display.

5.

Increase this value with the navigation button

to 100 mBar, push to confirm, and select

SAVE

SAVE

 to save the setting.

6.

 The transmitter will return to the home screen.

The measurement value at atmospheric

pressure is now -100 mBar. At an applied

pressure of 100 mbar the transmitter will

display 0 mbar.

The menu zero adjustment also has the choice of 

use process

”. The transmitter can be adjusted to 

zero in a real process situation. When chosen, the 

transmitter will measure the pressure in an actual 

process. This measurement will be used as the zero 

value. (4 mA)
1.

 Navigate to program point 

P101

, and push the

button to enter the menu.

2.

Choose  “

use process

” , and push to confirm.

The transmitter will display the actual 

measured value.

3.

 Push the navigation button to confirm, and

select 

SAVE

SAVE

 to save the setting.

4.

The transmitter will return to the main menu.

Zero value

P1O1

<6. Explanation Programming Points>

6.2  Span Adjustment 

(SPAN, 20 mA)

This setting can be used to adjust the range (SPAN) 

according to an entered value or adjusted with 

or without an applied pressure. The maximum 

pressure which can be measured (20 mA) is the 

measurement at 

ZERO (P101)

 + the entered value 

SPAN (P102)

. If 

the 

ZERO (P101)

 is increased then the maximum 

measured value will automatically be set higher 

by 

the same amount as

 the zero.

This will be explained step by step by an example.
Example:  

Measurement range 0 – 2000 mbar = 4 - 20 mA.
The 

span

 must be set at 2000 mbar

1.

 Navigate to program point 

P102 - SPAN

Value

, and push the navigation button to enter 

the menu.

2.

 Two choices appear on the screen:

Set manual

 and 

Use process

Choose 

Set manual

, a value will appear on 

the screen. (Depending on the range.)

3.

 Adjust the 

SPAN

 with the navigation button

to 2000 mbar. and select 

SAVE

SAVE

 to save the

setting

4.

 The transmitter will return to the home screen.

The menu span adjustment also has the choice of 

use process

”. The transmitter can be adjusted to 

the span in a real process situation. When chosen, 

the transmitter will measure the pressure in an actual 

process. This measurement will be used as the span 

value. (20 mA)
1.

 Navigate to program point 

P102

, and push the

button to enter the menu.

2.

 Choose  “

Use process

”, and push to confirm.

The transmitter will display the actual 

measured value.

3.

 Push the navigation button to confirm, and

select 

SAVE

SAVE

 to save the setting.

4.

 The transmitter will return to the main menu.

Span value

P1O2

Содержание EJA565E

Страница 1: ...yright 2020 1st Edition October 2020 Yokogawa Corporation of America 2 Dart Road Newnan Georgia 30265 U S A Tel 800 888 6400 Fax 770 254 0928 User s Manual Hygienic Sanitary Pressure Transmitters EJA5...

Страница 2: ...isplay and Navigation Button 9 5 1 Graphic Display Readout 10 5 2 Summary Programming Points 11 6 Explanation Programming Points 12 6 1 Zero Adjustment ZERO 12 6 2 Span Adjustment SPAN 20 mA 12 6 3 Ca...

Страница 3: ...ation Vertical Tank with a Truncated Bottom 21 6 11 7 Free Linearization 22 6 11 8 Free Linearization Manually 23 6 12 Burst Mode 24 6 13 Information 25 6 14 Factory 25 7 Programming 26 7 1 Programmin...

Страница 4: ...the output all within an accuracy of 0 1 1 1 Description The EJA565E transmitter is specially designed with a flush mounted diaphragm so it fully meet the needs of the food pharmaceutical chemical an...

Страница 5: ...01 2 Dimensional Drawings 2 Dimensional Drawings n EJA565E T20 PROCESS CONNECTION 1 2 NPT Electrical Connection M12 Electrical Connection Note Standard Drawings for all other connection types are avai...

Страница 6: ...lding operation 3 2 Installing Transmitter Code W33 1 After welding clean up edges and take care of the inside nipple wall 2 Make sure the O rings 10 and 11 are properly located 3 Improper installatio...

Страница 7: ...heavy electrical equipment e g Frequency controllers or heavy pumps Shielding must always be connected at the side of the power supply In case the process connection is already connected to ground e g...

Страница 8: ...egative side of the 2 wire loop The minimum power supply is based on the total circuit resistance The maximum external load RI max for 24 Vdc will be 600 Ohm CAUTION With a loop resistance of 250 a po...

Страница 9: ...needed Figure 1 Display EJA565E fully rotatable 360 Move the navigation button up or down to browse through various menus These movements can be distinct in choices of program points navigation throu...

Страница 10: ...when any form of linearization is applied A Straight line means no linearization is applied When a linearization is applied a curve will be displayed 2 HART protocol Displays a HART symbol 3 Write Pr...

Страница 11: ...00 seconds P107 Language Language choice between English Dutch German Russian Polish and French P108 Device Setup Configuration of Protection Alarm Backlight Temperature Secondary value Set time and...

Страница 12: ...value 3 Push the navigation button to confirm and select SAVE SAVE to save the setting 4 The transmitter will return to the main menu Zero value P1O1 6 Explanation Programming Points 6 2 Span Adjustm...

Страница 13: ...mitter will return to the main menu CAUTION Do not apply pressure while executing Cancel mounting position effect For low pressure ranges the mounting effect on the zero point will be more noticeable...

Страница 14: ...ter will return to the main menu Languages P1O7 6 8 Device Setup In this menu several operational settings can be made for the transmitter and the display 1 Navigate to program point P108 Device Setup...

Страница 15: ...near measurement and displayed by the symbol on the home screen Readout P1O9 Tons Number of tons only possible in combination with linearization P111 After selecting this readout the Specific Gravity...

Страница 16: ...te to program point P111 TANK LIN and push the navigation button to enter the menu Six choices appear on the screen No Lin No linearization Hor Tank Linearization setting for a horizontal tank cylindr...

Страница 17: ...value except Height 4 and confirm each selection with the control button The values must be entered in meters 6 Select SAVE SAVE to save the setting 7 The transmitter will return to the main menu n S...

Страница 18: ...age of filling of the tank 5 Fill in each value and confirm with the navigation button The entered value s must be in meters 6 Select SAVE SAVE to save the setting 7 The transmitter will return to the...

Страница 19: ...rm with the navigation button The entered value s must be in meters 6 Select SAVE SAVE to save the setting 7 The transmitter will return to the main menu n Simulation After linearization is entered an...

Страница 20: ...and confirm with the navigation button The entered value s must be in meters 6 Select SAVE SAVE to save the setting 7 The transmitter will return to the main menu n Simulation After linearization is e...

Страница 21: ...onfirm with the navigation button The entered value s must be in meters 6 Select SAVE SAVE to save the setting 7 The transmitter will return to the main menu n Simulation After linearization is entere...

Страница 22: ...ents The measuring must take place from low to high Filling an empty tank The actual measuring will be displayed on the screen in percentage for Xn filling and for Yn the measured volume To enter the...

Страница 23: ...llest possible deviation Factory setting Saved span in P102 Start Point The contents of a tank can be configured up to 70 points The entered value s must be from low to high Filling an empty tank The...

Страница 24: ...e screen push to enter this menu 3 Three choices appear on the screen 0 1 and 2 4 With these choices three distinct types of burst messages can be configured Make a choice and push the button to confi...

Страница 25: ...tput 4 20 or 20 4 mA Local Prot Protection On or Off Alarm Alarm output 3 2 or 22 8 mA Sec Value Selected secondary configuration Backlight Backlight On Sleep mode or Off Temp Temperature unit Celsius...

Страница 26: ...s necessary for proper communication see drawing below A power supply of at least 17 Vdc must be used The EJA565E can easily be programmed with the Hand Held Terminal YHC HART Communicator Option 1 HA...

Страница 27: ...cted units psi mBar SV Sensor Temperature Selected units Deg F or C TV Electronic Temperature Selected units Deg F or C FV Pressure Same as PV Dynamic variables PV SV TV FV and current can be read usi...

Страница 28: ...otatable To rotate the display place a small screw driver into the recess on top of the display Turn it by hand by moving the screw driver into the desired direction use the other hand to guide this m...

Страница 29: ...trical specifications The General Specificaitions listed below can be downloaded from the Yokogawa Corporation of America website https www yokogawa com us solutions products platforms field instrumen...

Страница 30: ...formation CAUTION When using the EJA565E process connectors suffix code W the welding information on page 6 must be followed exactly This is very important to prevent distortion of the weld on nipples...

Страница 31: ...ollowing address E mail support us yokogawa com n If you want have more information about Yokogawa products you can visit Yokogawa s homepage at the following web site Homepage http www yokogawa com n...

Отзывы: