<10. Parameter Summary>
10-6
IM 01C27F01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
5.
AI1
block
(continued)
29
Transducer Value
When Simulate Switch is set to Disable, this value
is used as the input value for the AI object. Refer to
Figure 10.1.
Disable
R
30
Simulate Value
When Simulate Switch is set to Enable, this value is
used as the input value for the AI object.
The input value can be changed.
---
W
51
Upper Limit
Indicates the upper limit (URL) for the pressure.
---
R
52
Lower Limit
Indicates the lower limit (LRL) for the pressure.
---
R
53
PV Range
Sets the measurement range.
1. EU at 100% : Indicates input value of the upper
limit.
2. EU at 0% : Indicates input value of the lower limit.
3. Units Index : Indicates the units of the
measurement range.
4. Decimal : Indicates the digit number below the
decimal point.
EU at 100%
= 100
EU at 0%
= 0
Units Index
= kPa (1133)
Decimal
= 2
W
54
Linearization Type
Select either No Linearization or Square root as a
setting of the output range.
0 = No Linearization :
Provides an output value scaled according to the
PV Range and Scale range settings.
(To use Direct with FF, set the same value for PV
Range and Scale.)
10 = Square root :
Provides a square root output computed for the
value scaled according to the PV Range and Scale
range settings.
0
W
55
Flow Constant
Indicates the flow coefficient, which shows the
correlation between the flow rate value and square root
value of the differential pressure.
1.0
W
56
Lower Cutoff
Specifies the low cut value. The unit is subject to
Scale.Units Index.
10
W
57
Cal Cmd
Specifies the calibration method.
0 = CAL_NONE : Initial state in which calibration is
not performed
1 = CAL_LOW : Applies an actual input and adjusts
the lower limit using the value specified in
Calibration Lowest Point.
2 = CAL_HIGH : Applies an actual input and adjusts
the higher limit using the value specified in
Calibration Highest Point.
5 = CAL_CLEAR : Clears the adjustment variable.
0 (reading
value is
always 0)
W
58
Cal Status
Indicates the calibration status.
0 = CAL_NONE : Start-up and default value
1 = CAL_SUCCESS : Indicates that calibration was
successful.
7 = CAL_BAD_TRIM_POINT : Indicates this status
when the adjustment variable is outside of range.
---
R
59
Calibration Highest
Point
Specifies the higher limit adjustment variable for
adjustment between two points.
---
W
60
Calibration Lowest
Point
Specifies the lower limit adjustment variable for the
adjustment between two points.
---
W
61
Calibration
Minimum Span
Indicates the minimum span of the adjustment
variable.
---
R
104
External Zero Trim Allows performing external zero adjustment.
(Trim on, Trim off)
Trim on
W
105
Low Cut Mode
Specifies the low cut mode.
(Linear, Zero)
Linear
W