<7. Operation>
7-3
IM 01C27F01-01EN
7.3 Starting Operation
After the zero point adjustment is completed, the
transmitter is already the operating status. Follow
the procedure below.
1) Confirm the operating status.
2) After confirming the operating status, perform
the following.
IMPORTANT
• Close the terminal box cover and the
amplifier cover. Screw each cover in tightly
until it will not turn further.
• Tighten the zero-adjustment cover mounting
screw to secure the cover.
7.4 Connecting to the Field
Wireless Network
■ Preparation work prior to connecting to a
Field Wireless Network
This transmitter does not need to be connected
with a physical wire. Instead of physical wiring, it
is necessary to set the field wireless devices to
communicate with before installing the transmitter.
This procedure is called a provisioning.
This transmitter supports provisioning via infrared
communication using a provisioning device and
can be securely connected to a network. If the
provisioning information is not set, the transmitter
cannot be connected to the field wireless network.
Provisioning:
Provisioning is work to set the security and
network information to enable the transmitter
to be connected to the field wireless network.
This transmitter supports a provisioning method
using infrared communication.
For details on provisioning using a provisioning
device, and procedure for connecting the
transmitter to the Field Wireless Network, refer
to the User’s Manual, FieldMate Versatile Device
Management Wizard (IM 01R01A01-01E) and
YFGW410 Field Wireless Management Station (IM
01W02D01-01EN).
F0703.ai
within 30cm
Figure 7.3
Provisioning Example
■ Provisioning work
This subsection describes provisioning work using
FieldMate as the provisioning device.
Provisioning work performs provisioning for
each field wireless device using FieldMate and
an infrared adapter. If Yokogawa-recommended
infrared device is used for provisioning, distance
between the transmitter glass window and the
infrared device should be within 30cm. For details of
Yokogawa-recommended infrared device, refer to
subsection 9.2 “Calibration Instruments Selection”.
Perform the following provisioning tasks.
• Setting provisioning information
• Creating a provisioning information file
1) Setting provisioning information
Set the device tag and network ID using a
FieldMate provisioning function. The device
tag, network ID, and join key are set in the Field
Wireless Device. It is not necessary to input
a join key because FieldMate automatically
generates it.
Setting device tag
The device tag is used for the user to
recognize the Field Wireless Device.
Setting network ID
This is the network ID for the field wireless
network to which the field wireless device is
connected. Set a value from 2 to 65535.
The field wireless device is connected to the
field wireless network corresponding to the
network ID set by provisioning work.