<2. Handling Cautions>
2-9
IM 01C27F01-01EN
2.10 Pressure Equipment
Directive (PED)
(1) General
• EJX Series pressure transmitters are
categorized as pressure accessories under the
vessel section of directive 2014/68/EU, which
corresponds to Article 4, Paragraph 3 of PED,
denoted as Sound Engineering Practice (SEP).
• EJX110B-
MS, EJX110B-
HS,
EJX110B-
VS, EJX510B-
D, and
EJX530B-
D can be used above 200 bar and
therefore considered as a part of a pressure
retaining vessel where category III, Module H
applies. These models with option code /PE3
conform to that category.
(2) Technical Data
• Models without /PE3
Article 4, Paragraph 3 of PED, denoted as
Sound Engineering Practice (SEP).
• Models with /PE3
Module: H
Type of Equipment: Pressure Accessory-Vessel
Type of fluid: Liquid and Gas
Group of fluid: 1 and 2
Model
Capsule
code
PS
(bar)*
1
V(L)
PS·V
(bar·L)
Category*
2
EJX110B
F, L
160
0.01
1.6
Article 4,
Paragraph 3
(SEP)
M, H, V
250
0.01
2.5
EJX110B
with code /
PE3
M, H, V
250
0.01
2.5
III
EJX310B L, M, A, B
160
0.01
1.6
Article 4,
Paragraph 3
(SEP)
EJX430B
H, A, B
160
0.01
1.6
Article 4,
Paragraph 3
(SEP)
EJX510B
A, B, C
100
0.1
10
Article 4,
Paragraph 3
(SEP)
D
700
0.1
70
EJX510B
with code /
PE3
D
700
0.1
70
III
EJX530B
A, B, C
100
0.1
10
Article 4,
Paragraph 3
(SEP)
D
700
0.1
70
EJX530B
with code /
PE3
D
700
0.1
70
III
*1: PS is maximum allowable pressure for vessel itself.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 2014/68/EU
(3) Operation
CAUTION
• The temperature and pressure of fluid should
be maintained at levels that are consistent
with normal operating conditions.
• The ambient temperature should be
maintained at a level that is consistent with
normal operating conditions.
• Please take care to prevent water hammer
and the like from inducing excessive
pressures in pipes and valves. If phenomena
are likely, install a safety valve or take
some other appropriate measure to prevent
pressure from exceeding PS.
• Take appropriate measures at the device or
system level to protect transmitters if they
are to be operated near an external heat
source.
2.11 Low Voltage Directive
Applicable standard:
EN61010-1, EN61010-2-030
(1) Pollution Degree 2
"Pollution degree" describes the degree to
which a solid, liquid, or gas which deteriorates
dielectric strength or surface resistivity is
adhering. " 2 " applies to normal indoor
atmosphere. Normally, only non-conductive
pollution occurs. Occasionally, however,
temporary conductivity caused by condensation
must be expected.
(2) Installation Category I
(Anticipated transient overvoltage 330 V)
"Overvoltage category (Installation category)"
describes a number which defines a transient
overvoltage condition. It implies the regulation
for impulse withstand voltage. " I " applies to
electrical equipment which is supplied from the
circuit when appropriate transient overvoltage
control means (interfaces) are provided.