Debugging
:
Error
Code
Content
Error
Code
Content
U0
Preheat time of compressor is insufficient
C6
Alarm because ODU quantity is inconsistent
U2
Wrong setting of ODU’s capacity code/jumper cap
C7
Abnormal communication of converter
U3
Power supply phase sequence protection
C8
Emergency status of compressor
U4
Refrigerant-lacking protection
C9
Emergency status of fan
U5
Wrong address for driving board of compressor
CA
Emergency status of module
U6
Alarm because valve is abnormal
CH
Rated capacity is too high
U8
Malfunction of pipeline for IDU
CC
No main unit
U9
Malfunction of pipeline for ODU
CL
The matching ratio of rated capacity for IDU and ODU is
too low
UC
Setting of main IDU is succeeded
CE
Communication malfunction between mode exchanger
and IDU
UL
Emergency operation DIP switch code of compressor is
wrong
CF
Malfunction of multiple main control units
UE
Charging of refrigerant is invalid
CJ
Address DIP switch code of system is shocking
UF
Identification malfunction of IDU of mode exchanger
CP
Malfunction of multiple wired controller
C0
Communication malfunction between IDU, ODU and IDU’s
wired controller
CU
Communication malfunction between IDU and the
receiving lamp
C1
Communication malfunction between main control and
DC-DC controller
Cb
Overflow distribution of IP address
C2
Communication malfunction between main control and
inverter compressor driver
Cd
Communication malfunction between mode exchanger
and ODU
C3
Communication malfunction between main control and
inverter fan driver
Cn
Malfunction of network for IDU and ODU of mode
exchanger
C4
Malfunction of lack of IDU
Cy
Communication malfunction of mode exchanger
C5
Alarm because project code of IDU is inconsistent
Status:
Error
Code
Content
Error
Code
Content
A0
Unit waiting for debugging
Ay
Shielding status
A2
Refrigerant recovery operation of after-sales
n0
SE operation setting of system
A3
Defrosting
n3
Compulsory defrosting
A4
Oil-return
n4
Limit setting for max. capacity/output capacity
A6
Heat pump function setting
n5
Compulsory excursion of engineering code of IDU
A7
Quiet mode setting
n6
Inquiry of malfunction
A8
Vacuum pump mode
n7
Inquiry of parameters
AH
Heating
n8
Inquiry of project code of IDU
AC
Cooling
n9
Check quantity of IDU on line
AL
Charge refrigerant automatically
nA
Heat pump unit
AE
Charge refrigerant manually
nH
Heating only unit
AF
Fan
nC
Cooling only unit
AJ
Cleaning reminding of filter
nE
Negative code
AP
Debugging confirmation when starting up the unit
nF
Fan model
AU
Long-distance emergency stop
nJ
High temperature prevention when heating
Ab
Emergency stop of operation
nU
Eliminate the long-distance shielding command of IDU
Ad
Limit operation
nb
Bar code inquiry
An
Child lock status
nn
Length modification of connection pipe of ODU