If the quantity displayed is the same with actual quantity, then press SW7 confirmation button on the master unit to
confirm it. Unit will start next progress:
Debugging Code
Progress Code
Status Code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
03_Confirm the quantity
of modules
db
light
03
light
OC
light
If the quantity displayed is different from actual quantity, then disconnect power and check whether communication wire
among each module is correctly connected. After the check, start debugging again.
Step 8:
in progress 04, the quantity of IDUs needs to be confirmed manually. Main board of each module will
display:
Debugging Code
Progress Code
Status Code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
04_Confirm the quantity
of IDUs
db
Light
04
Light
Quantity of
connected
IDUs
blink
If the quantity displayed is the same with actual quantity, then press SW7 confirmation button on the master unit to
confirm it. Unit will start next progress:
Debugging Code
Progress Code
Status Code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
04_Confirm the quantity
of IDUs
db
Light
04
Light
OC
Light
Step 9:
progress 05 is “Detect internal communication”
If no error is detected, system will display as below and then start next progress.
Debugging Code
Progress Code
Status Code
Progress
LED1
LED2
LED3
Code
Display status
Code
Display status
Code
Display status
05_Detect internal
communication
db
Light
05
Light
OC
Light
If error is detected, system will stay at current progress. Error has to be solved manually. Below are relevant errors:
Debugging Code
Progress Code
Status Code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
05_Detect
internal
communication
db
Light
05
Light
C2
Light
System detects “driven communication error
between master unit and inverter compressor”.
db
Light
05
Light
C3
Light
System detects “driven communication error
between master unit and inverter fan”.
db
Light
05
Light
CH
Light
IDU/ODU “high proportion of rated capacity”.
db
Light
05
Light
CL
Light
IDU/ODU “low proportion of rated capacity”.