Figure 4: Wire loop design recommendation

Series wiring (voltage additive)

Parallel wiring (current additive)

of lightning induced voltage surges.

E L E C T R I C A L   I N S TA L L AT I O N

Electrical Configuration

Under normal conditions, a photovoltaic module is likely to experience 
conditions that produce more current and/or voltage than reported at Standard 
Test Conditions (STC: 1000 W/m

2

, AM 1.5, and 25°C cell temperature). The 

short-circuit current (I

SC

) should be multiplied by a factor of 1.25 and the open-

circuit voltage (V

OC

) should be multiplied by a factor of up to 1.25 based on 

the lowest ambient temperature recorded for the installation location when 
determining component voltage ratings, conductor current ratings, fuse sizes, 
and size of controls connected to the PV output. 

Voltages are additive when PV modules are connected directly in series, 
and module currents are additive when PV modules are connected directly 
in parallel, as illustrated in Figure 5. PV modules with different electrical 
characteristics must not be connected directly in series. The use of suitable 
third-party electronic devices connected to PV modules may enable different 
electrical connections and must be installed according to the manufacturer’s 
specified instructions.

 

Figure 5: Electrical diagrams of series and parallel wiring

The maximum number of PV modules that can be connected in a series string 
must be calculated in accordance with applicable regulations in such a way that 
the specified maximum system voltage of the PV module and all other electrical 
DC components will not be exceeded in open-circuit operation at the lowest 
temperature expected at the PV system location.

An appropriately rated overcurrent protection device must be used when the 
reverse current could exceed the value of the maximum fuse rating of the 
module. An over current protection device and  anti-reflection diode module  
are required for each series string if more than two series strings are connected 
in parallel.and reverse polarity  is forbidden.

Cables and Wiring

Yingli Solar PV modules are provided with two (2) stranded, sunlight 
resistant output cables that are terminated with PV connectors ready for 
most installations. The positive (+) terminal has a female connector while the 
negative (-) terminal has a male connector. The module wiring is intended for 

series connections [i.e. female (+) to male (-) interconnections], but can also be 
used to connect suitable third-party electrical devices that may have alternative 
wiring configurations so long as the manufacturer’s instructions are followed. 

Use field wiring with suitable cross-sectional areas that are approved for use at 
the maximum short-circuit current of the PV module. Yingli Solar recommends 
installers use only sunlight resistant cables qualified for direct current (DC) 
wiring in PV systems. The minimum wire size should be 4mm

2

.

Table 1: Required minimum field wiring specifications

Testing Standard

Wire Size

Temperature Rating

Required Minimum Field Wiring

EN 50618

4 mm

2

- 40ºC to + 90ºC

                

 

 

Cables should be fixed to the installation structure in such a way that 
mechanical damage of the cable and/or the module is avoided. Do not apply 
stress to the cables. Do not bend cables to a bending radius of less than 40mm. 
For fixing, use appropriate means, such as sunlight resistant cable ties and/or 
wire management clips specifically designed to attach to the PV module frame. 
While the cables are sunlight resistant and waterproof, where possible, avoid 
direct sunlight exposure and water immersion of the cables.

Connectors

Keep connectors dry and clean, and ensure that 
connector caps are hand tight before connecting 
the modules. Do not attempt making an electrical 
connection with wet, soiled, or otherwise faulty 
connectors. Avoid sunlight exposure and water 
immersion of the connectors. Avoid connectors resting 

on the ground or roof surface. 

Faulty connections can result in arcs and electrical shock. Check that all electrical 
connections are securely fastened. Make sure that all locking connectors are 
fully engaged and locked. 

Modules must not be interconnected using connectors from different 
manufacturers and / or of different types. If modules having such different 
connectors need to be interconnected, a qualified professional may replace 
connectors according to the manufacturers’ specified instructions such that an 
interconnection can be made with connectors from the same manufacturer and 
the same type.

Figure 6: Series interconnection of a male (-) and female (+) connector

Bypass Diodes

The junction boxes used with Yingli Solar PV modules (not Smart Hot Spot Free 
module) contain bypass diodes wired in parallel with the PV cell strings. In the 
case of partial shading, the diodes bypass the current generated by the non-
shaded cells, thereby limiting module heating and performance losses. Bypass 
diodes are not overcurrent protection devices. 

Bypass diodes divert current from the cell strings in the event of partial shading. 
See Figure 7-1 for a diagram showing how the cell strings are electrically 
connected with the diodes.

Every piece of cells from Yingli Smart Hot Spot Free module parallels a diode, 
with a cell is covered by shade or occurs an excepion, the paralleled diode can 
bypass this cell, thus avoid hot spot, and can retain the maximum power output.

Bypass diodes divert current from a cell in the event of partial shading, See 
figure 7-2 for a diagram showing how the cells are electricallly connected with 
the diodes.

Fully engage and lock

Cap

+

Содержание YLM-J 3.0 PRO Series

Страница 1: ...tification requirements has been verified by an independent certification laboratory This Installation and User Manual is available in different languages In cases of discrepancy between versions the English language version shall control Failure to comply with the requirements listed in this manual will invalidate the Limited Warranty for PV Modules as provided by Yingli Solar at the time of sale...

Страница 2: ...ules in any way Doing so may degrade performance or cause irreparable damage and will void any applicable warranties If it is necessary to store PV modules prior to installation the PV modules should remain inside the packaging and protected from exposure that could compromise the durability of the packaging Fire Yingli Solar PV Modules have a Class C fire resistance rating in accordance with the ...

Страница 3: ...cross sectional areas that are approved for use at the maximum short circuit current of the PV module Yingli Solar recommends installers use only sunlight resistant cables qualified for direct current DC wiring in PV systems The minimum wire size should be 4mm2 Table 1 Required minimum field wiring specifications Testing Standard Wire Size Temperature Rating Required Minimum Field Wiring EN 50618 ...

Страница 4: ...sult in galvanic corrosion An addendum to UL Standard 1703 Flat Plate Photovoltaic Modules and Panels recommends metal combinations not exceed an electrochemical potential difference of 0 5 Volts The frame rails have pre drilled holes marked with a grounding sign as illustrated in Figure 8 These holes should be used for grounding purposes and must not be used for installation the PV modules Do not...

Страница 5: ...n attachment Figure 12 Installation rails The large size modules are mounted with four outer holes with max mechanical loads of 5400 Pa snow front and 2400 Pa wind back Top down Clamps Third party clamps that have been designed for PV installation structures are an approved installation attachment method for Yingli Solar PV modules Modules must be fastened using clamps applied to the top side of t...

Страница 6: ...rasive materials that could scratch or damage the glass surface Failure to comply with these requirements may adversely affect the PV module performance Yingli Solar PV modules are designed to withstand high snow loads However if removing snow is desired to enhance production use a brush to gently remove snow Do not try to remove frozen snow or ice from PV modules DECOMMISSIONING The dismantling o...

Страница 7: ...racteristics are within 10 percent of the indicated values of Isc Voc and Pmax under Standard Test Conditions irradiance of 1000 W m2 AM 1 5 spectrum and a cell temperature of 25 C Refer to module datasheets for specific power output tolerances Please refer to Table 1 to see which power classes actually exist for which module series Family YLM J 3 0 PRO Type YLxxxD 37e 1 2 xxx 390 415 YLxxxD 37e 1...

Страница 8: ...4 20 N m The tightening steps as follows use torque wrench to tighten nut to target torque nut loosen 90 180 degrees finally tighten the nut to the target torque and reduce the torque attenuation 2 Mounting hole installation 1P tracker Type Mechanical load Pa Safety factor Schematic diagram Purlin parallel to long side frame 1600 1600 1 5 Notes To maximize mounting longevity Yingli Solar strongly ...

Страница 9: ...ashers of minimum 1 4 mm thickness with an minimum outer diameter of 15 57 mm Modules can be attached using the mounting holes the number of mounting holes used for a single long side frame 2 including at least one φ7 10 mm hole on the back of the module frame by fixing the module to the support rails with bolts Secure the module in each mounting location with M6 and M8 bolts and matching flat was...

Страница 10: ... when it is pressed down L represents the length of the long side of the module the described distances are from the module edge to the middle of the clamp The long side frames of the module are fixed to the mounting beam or rail by at least 4 clamps that can be fitted with M8 bolts The length of the clamp 40 mm and the module frame to maintain at least 7 mm but not more than 10 mm overlap part co...

Страница 11: ...es are required to secure the modules to the forklift with a tensile strength greater than 2000 kgf 2 Pass the forearm of the anti tilting bracket through the pallet insert the two bolts into the front round hole of the anti tilting bracket and adjust the support angle of the anti tilting bracket so that the angle with the ground is between 80 and 87 3 When placing it need to wait for the packing ...

Отзывы: