11
WATER QUALITY
It is the End User’s responsibility to have the
cooling water analyzed and chemically treated as
often as necessary so that it conforms to the
limits specified in Table 1. The water quality in
the chilled water, cooling water, and heat medium
circuits shall not exceed the following limits:
ITEM
CHILLED
WATER
COOLING
WATER
MAKE-UP
WATER
S
tand
ar
d
pH (at 77°F)
6.8 - 8.0
6.5 - 8.2
6.8 - 8.0
Conductivity (
S/cm at 77°F)
400
800
300
Chloride ion (Cl
-
ppm)
50
200
50
Sulfate ion (SO
4
2-
ppm)
50
200
50
M-alkalinity (CaCO
3
ppm)
50
100
50
Total hardness (CaCO
3
ppm)
70
200*
70
Calcium hardness (CaCO
3
ppm)
50
150
50
Ionic silica (SiO
2
ppm)
30
50
30
Ref
er
en
ce
Total iron (Fe ppm)
1.0
1.0
0.3
Copper (Cu ppm)
1.0
0.3
0.1
Sulfide ion (S
2-
ppm)
ND
ND
ND
Ammonium ion (NH
4
+
ppm)
1.0
1.0
0.1
Residual chlorine (Cl ppm)
0.3
0.3
0.3
Free carbon dioxide (CO
2
ppm)
4.0
4.0
4.0
Ryzner stability index
-
6.0 - 7.0
-
NOTES:
1.
ND (Not Detectable)
2.
*Total hardness of make-up water shall not exceed 70 ppm when bleed off is the only method used to control water quality.
Table 1
– WATER QUALITY REQUIREMENTS
ERROR CODES
Error Code
Number
Error Description
Notes
Reset
Type
FS
Flow switch alarm
Chilled/hot water flow switch FS1 open, but for less
than 10 minutes. After 10 minutes, this changes
automatically to error code 27.
Auto
01
DCP power error
Optional AroTrend remote monitoring package has
lost power.
Auto
02
DCP communication
line short
Power available to the optional AroTrend remote
monitoring package but communications line is
shorted.
Auto
03
DCP communication
line noise
Optional AroTrend Remote monitoring package
cannot communicate with the chiller-heater.
Auto
04
Accessory error
Optional fire safety shutdown.
Manual
05
Chilled/hot water
pump interlock error
Voltage signal from terminal CM2 in the junction box
is not returning to terminal 3 in the junction box.
Manual
06
Cooling water pump
interlock error
Voltage signal from terminal CM2 in the junction box
is not returning to terminal 4 in the junction box.
Manual
07
Cooling tower fan
interlock error
Voltage signal from terminal CM2 in the junction box
is not returning to terminal 5 in the junction box.
Manual
08
Solution pump error
Solution Pump overload THR1 has tripped.
Manual
09
Generator (HGE) over
heat error
The GP sensor has reported a temperature in excess of
325.4°F
(163°C)
. Unit locks out.
Manual
10
Generator (HGE)
temp error
GPSC has opened. Unit locks out.
Manual