background image

 

MAINTENANCE 

 

GENERAL INFORMATION 

ALL 

MAINTENANCE 

SHOULD 

BE 

PERFORMED 

BY 

TRAINED 

AND 

EXPERIENCED PERSONNEL.  Your Yazaki 
Authorized  Service  Provider 

(ASP)

  can  help 

you  establish  a  standard  maintenance 
procedure. 

For  your  safety,  keep  the  area  around 

the equipment clear and free of combustible 
materials,  gasoline  and  other  flammable 
substances.    DO  NOT  obstruct  service 
access  or  combustion  air  supply  to  the 
equipment.  

ROUTINE MAINTENANCE

 

Routine maintenance should be provided 

throughout  the  life  of  the  equipment  to 
ensure 

satisfactory 

performance 

and 

operation.   

During the warranty period, an ASP must 

be  engaged  to  provide  routine  maintenance 
on  chiller-heaters  at  the  beginning  of  each 

cooling  season.    When  the  chiller-heater  is 
used  for  process  cooling  or  heavy  load 
operation  it  may  be  necessary  to  schedule 
additional  service  visits  to  evacuate  non-
condensable  gases  from  the  vacuum 
section.  

MAINTENANCE INTERVALS 

Every 4 months 

(Spring, Summer, Winter)

Evacuation   

(Units  not  used  in  Heat  mode  can 

skip the winter evacuation) 

 

Every 12 months: 

Burner  Combustion  Analysis  and  Gas 

Pressure Check 

(Supply and Manifold) 

Inhibitor  Check 

(If  required.    For  the  K-Series,  an 

inhibitor  charge  is  needed  every  3  years,  on 
average.) 

Palladium Cell Heater Check 
Flow Rate Check 
Solution Pump Rotation Check 

Flame Rod Replacement 

(if required) 

Igniter Rod Replacement 

(if used and required) 

 

Every 3 years: 

HGE  Inspection 

(pulling  the  burner  to  see  the 

condition inside the HGE) 

Average interval for Inhibitor Charge 
Average  interval  for  Flame  and  Igniter  Rod 

Replacement. 

 

 

 

EVACUATION OVERVIEW

 

Arguably  the  most  important  aspect  of 

maintenance 

for 

the 

chiller-heater 

is 

maintaining  a  proper  level  of  vacuum.  
Evacuation  is  performed  at  the  front  of  the 
machine.  The evacuation service valves are 
referred  to  as  Service  Valve  A 

(upper)

  and 

Service Valve B 

(lower)

.   

The  evacuation  service  valves  are  back-

seating  access  valves  similar  to  those  used 
throughout  the  refrigeration  industry.    The 

stem  has  a  10mm  square  head.    The  stem 
secures a copper seal to a steel seat inside 
the  valve.    Do  not  over-torque  this  valve  or 
else  the  seal  can  become  damaged  and 
compromise  vacuum  integrity.    The  proper 
torque is 14.75 ft-lbs 

(20 Nm)

.  Yazaki offers a 

torque  wrench 

(P/N  N7510)

  specifically  for 

use with this service valve. 

A  number  of  precautions  should  be 

observed at all times during evacuation.  

Содержание CH-K30

Страница 1: ...UCTIONS and properly maintained it can provide many years of trouble free operation CONTENTS GENERAL Page ABSORPTION PRINCIPLE 2 COOLING OPERATION 2 HEATING OPERATION 3 CONTROLS GENERAL INFORMATION 4...

Страница 2: ...cooled and heat is normally rejected to a cooling tower though ground loop is also an option COOLING OPERATION High Temperature Generator HGE The gas burner heats a dilute lithium bromide solution in...

Страница 3: ...nd semi concentrated solution flow into the primary separator in exactly the same manner as in the cooling cycle Low Temperature Generator LGE In Heat mode the changeover valve opens a path for the se...

Страница 4: ...y also be supervised and controlled by external control systems to a limited degree when the necessary interconnections are installed Additional controls and interlocks can be explained by your ASP On...

Страница 5: ...2 10 Rated 300vac F4 2 Fuji Model FGAO 2 Rated 250vac F11 F12 2 Fuji Model FGAO 2 Rated 250vac F31 F32 1 Fuji Model FGAO 2 Rated 250vac FB11 FB12 2 Fuji Model FGAO 2 Rated 250vac FB21 FB22 15 Nagasaw...

Страница 6: ...on the I O Board to ON The leaving chilled water temperature can be adjusted using the TC potentiometer on the CPU Board The leaving chilled water set point can be set in a range of 40 1 F 4 5 C to 59...

Страница 7: ...ress the alarm RESET button to restart the cooling or heating operation If Error Code 52 is amongst the codes being displayed it will also be necessary to press the RESET button on the burner controll...

Страница 8: ...Gas Pressure Check Supply and Manifold Inhibitor Check If required For the K Series an inhibitor charge is needed every 3 years on average Palladium Cell Heater Check Flow Rate Check Solution Pump Rot...

Страница 9: ...s vacuum section Just because the vacuum pump has stopped producing bubbles in the water bucket does NOT mean the vacuum level is adequate A digital vacuum gauge MUST be used in order to determine the...

Страница 10: ...iller heater itself as well If doing so pressurize the unit to the same pressure as the circuits using nitrogen See the Service Manual for further details TROUBLESHOOTING SYMPTOM Chiller heater does n...

Страница 11: ...iption Notes Reset Type FS Flow switch alarm Chilled hot water flow switch FS1 open but for less than 10 minutes After 10 minutes this changes automatically to error code 27 Auto 01 DCP power error Op...

Страница 12: ...10 C or above 212 F 100 C Ignored for first 10 minutes of P2 operation Manual 36 CND sensor error CND sensor reads below 14 F 10 C or above 212 F 100 C Auto 40 Loss of cooling capacity LT temperature...

Страница 13: ...13 Please send a copy of any maintenance data sheets to Yazaki Energy Systems Inc at the address FAX number and or email address listed on the last page of this document...

Страница 14: ...Labor Charges for warranty service can be obtained by an authorized service provider upon written request to YESI 7 LIMITATION OF WARRANTY AND LIMITATION OF REMEDY CUSTOMER s remedies shall be limite...

Страница 15: ......

Страница 16: ...MS INC 701 E PLANO PKWY SUITE 305 PLANO TEXAS 75074 6700 Phone 469 229 5443 Fax 469 229 5448 Email yazaki yazakienergy com Web http www yazakienergy com This symbol on the product s name plate means i...

Отзывы: