A.8 F: Communication Option Parameters
u
F6, F7: Communication Option Card
Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for EtherNet/IP, Modbus TCP/IP, and LONWORKS
options. F7 parameters are used for the EtherNet/IP and Modbus TCP/IP options.
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F6-01
(3A2)
Communications Error
Operation Selection
Comm Bus Flt Sel
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Ramp to stop. Decel to stop using the decel time in C1-02.
1: Coast to stop.
2: Fast Stop. Decel to stop using the decel time in C1-09.
3: Alarm only.
Default: 1
Range: 0 to 3
F6-02
(3A3)
External Fault from
Comm. Option
Detection Selection
EF0 Detection
0: Always Detected
1: Only During Run
0: Always detected.
1: Detection during run only.
Default: 0
Range: 0, 1
F6-03
(3A4)
External Fault from
Comm. Option
Operation Selection
EF0 Fault Action
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Ramp to stop. Decel to stop using the decel time in C1-02.
1: Coast to stop.
2: Fast Stop. Decel to stop using the decel time in C1-09.
3: Alarm only.
Default: 1
Range: 0 to 3
F6-06
(3A7)
Torque Reference/
Torque Limit Selection
from Comm. Option
Torq Ref/Lmt Sel
0: Disabled
1: Enabled
OLV/PM
OLV/PM
0: Disabled. Torque reference/limit from option board disabled.
1: Enabled. Torque reference/limit from option board enabled.
Default: 0
Range: 0, 1
F6-07
(3A8)
Multi-Step Speed
Enable/Disable
Selection when NefRef/
ComRef is Selected
Fref PrioritySel
0: Net/Com REF
1: MultiStep Speed
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)
Default: 0
Range: 0, 1
F6-08
(36A)
Reset Communication
Parameters
Com Prm Init Sel
0: Init Com Prms
1: No Init Com Prms
0: Communication-related parameters (F6-
oo
) are not reset
when the drive is initialized using A1-03.
1: Reset all communication-related parameters (F6-
oo
) when
the drive is initialized using A1-03.
Default: 0
Range: 0, 1
F7-01
(3E5)
IP Address 1
IP Address 1
Sets the most significant octet of network static IP address.
Default: 192
Min.: 0
Max.: 255
–
F7-02
(3E6)
IP Address 2
IP Address 2
Sets the second most significant octet of network static IP
address.
Default: 168
Min.: 0
Max.: 255
–
F7-03
(3E7)
IP Address 3
IP Address 3
Sets the third most significant octet of network static IP address.
Default: 1
Min.: 0
Max.: 255
–
F7-04
(3E8)
IP Address 4
IP Address 4
Sets the fourth most significant octet of network static IP
address.
Default: 20
Min.: 0
Max.: 255
–
F7-05
(3E9)
Subnet Mask 1
Subnet Mask 1
Sets the most significant octet of network static Subnet Mask.
Default: 255
Min.: 0
Max.: 255
–
F7-06
(3EA)
Subnet Mask 2
Subnet Mask 2
Sets the second most significant octet of network static Subnet
Mask.
Default: 255
Min.: 0
Max.: 255
–
F7-07
(3EB)
Subnet Mask 3
Subnet Mask 3
Sets the third most significant octet of network static Subnet
Mask.
Default: 255
Min.: 0
Max.: 255
–
F7-08
(3EC)
Subnet Mask 4
Subnet Mask 4
Sets the fourth most significant octet of network static Subnet
Mask.
Default: 0
Min.: 0
Max.: 255
–
A.8 F: Communication Option Parameters