Communi-

cation 

Option 

  Is an option card is installed? 

 

∗ 

Check if any communication option is installed

 

 

If a communication option is installed, get the equivalent part 

for the J1000. 

 

Never try to apply J7 options to J1000 unit. 

 

Communication cable connectors from J7 options can be 

used on J1000 options without rewiring. 

 

  Is an AC or DC reactor installed? 

 

∗ 

AC or DC chokes installed with a J7 can be used with a J1000 
and have not to be changed (only for same capacity like the 
installed J7). Before connecting it, make sure that it works 
properly.

 

 

  Is an EMC Filter installed? 

 

∗ 

EMC filters installed with a J7 can partially used with a J1000. 
For details on filter replacement contact your sales agent. 
Before using the old J7 filter in combination with the J1000, 
make sure the filter is free from any damage. 

 

Options, 

Others 

 

 Extension Cables 

 

∗ 

The extension cables for remote operation can continued to be 
used, but the remote operator and the remote operator interface 
have to be replaced! 

 

  Refer to the instruction manual for questions about installation, parameter settings or detailed parameter / 

function descriptions   

VAN-V07007E

 

 [J7

J1000] Replacement Instructions 

3/16

  In case of technical questions regarding the replacement please contact your dealer.

   

Содержание VS MINI J7

Страница 1: ...tric Wire Differences 5 3 5 Control terminal sizes and wire sizes 6 4 Dimensions 7 5 Options Replacement 8 6 Parameter Settings 9 6 1 J7 to J1000 Parameter Correspondence for Drive Replacement 9 6 2 J...

Страница 2: ...to make sure that it is compliant to the standard specification no special firmware Wire Length In the J7 drive main terminals are located at the top of the drive The J1000 drive has all main terminal...

Страница 3: ...it works properly Is an EMC Filter installed EMC filters installed with a J7 can partially used with a J1000 For details on filter replacement contact your sales agent Before using the old J7 filter...

Страница 4: ...lti function input 1 1 Run forward 0 Stop S2 Multi function input 2 1 Run reverse 0 Stop S3 Multi function input 3 J7 Fault Reset J1000 Ext Fault S4 Multi function input 4 J7 Ext Fault J1000 Fault Res...

Страница 5: ...U T1 V T2 W T3 1 2 B1 B2 2 J1000 2A0010 2 terminals M4 1 2 1 5 2 0 5 5 3 5 J7 22P2 R L1 S L2 T L3 U T1 V T2 W T3 1 2 M3 5 0 8 1 0 J1000 2A0012 R L1 S L2 T L3 U T1 V T2 W T3 1 2 B1 B2 2 terminals M4 1...

Страница 6: ...S L2 T L3 U T1 V T2 W T3 1 2 2 J7 43P0 43P7 M4 1 2 1 5 2 0 5 5 3 5 R L1 S L2 T L3 U T1 V T2 W T3 1 2 B1 B2 2 Three Phase 400V J1000 4A0009 4A0011 2 terminals M4 1 2 1 5 2 0 5 5 3 5 3 5 Control termina...

Страница 7: ...29 137 5 Single Phase 200V B1P50 BA0010B 108 128 154 108 128 154 Not required 20P10 2A0001B 20P20 2A0002B 70 76 20P40 2A0004B 102 108 20P70 2A0006B 68 122 68 128 21P50 2A0010B 129 129 22P20 2A0012B 10...

Страница 8: ...Interface for RS 422 485 communication Memobus SI 485 J7 SI 485 J Remote operator without potentiometer JVOP 146 JVOP 182 Remote operator with potentiometer JVOP 144 not available Extension cable 1 m...

Страница 9: ...eference source selection n03 0 b1 01 1 J7 J1000 n03 0 b1 01 3 AI V3 J option required n03 1 b1 01 0 n03 2 b1 01 1 and H3 01 0 n03 3 b1 01 1 and H3 01 2 n03 4 b1 01 1 and H3 01 3 n03 6 b1 01 2 SI 485...

Страница 10: ...tely for each ride profile section Multi speed ref 1 n21 0 0Hz d1 01 0 00 Hz Multi speed ref 2 n22 0 0Hz d1 02 0 00 Hz Multi speed ref 3 n23 0 0Hz d1 03 0 00 Hz Multi speed ref 4 n24 0 0Hz d1 04 0 00...

Страница 11: ...n36 39 10 H1 02 H1 05 6 n36 39 11 H1 02 H1 05 7 n36 39 12 H1 02 H1 05 8 n36 39 13 H1 02 H1 05 9 n36 39 14 H1 02 H1 05 61 n36 39 15 H1 02 H1 05 62 n36 39 16 H1 02 H1 05 A n36 39 17 H1 02 H1 05 1 n36 39...

Страница 12: ...AM function selection n44 0 H4 01 102 J7 J1000 n44 0 H4 01 102 n44 1 H4 01 103 Analog output AM gain n45 1 00 H4 02 100 0 Set H4 02 n45 100 Carrier frequency selection C6 02 o2 04 dep Carrier frequenc...

Страница 13: ...01 3 n59 3 L6 01 2 n59 4 L6 01 4 Over torque detection level n60 160 L6 02 150 Over torque detection time n61 0 1 s L6 03 0 1 s Frequency reference hold selection up down function n62 0 d4 01 0 J7 J10...

Страница 14: ...8 38 0 n75 1 L8 38 1 COPY function selection n76 rdy o3 01 0 Possible with copy unit or remote operator READ prohibit selection n77 0 o3 02 0 Fault History n78 U2 01 02 In the J1000 the last current f...

Страница 15: ...0 type JA x Output power kVA Output current A Carrier frequency kHz Output power kVA Output current A Carrier frequency kHz 0 1 B0P1 BA0001 0 3 0 8 0 3 0 8 0 2 B0P2 BA0002 0 6 1 6 0 6 1 6 0 4 B0P4 BA0...

Страница 16: ...Revision History Rev No Date Modification 21 Dec 07 First Edition VAN V07007E J7 J1000 Replacement Instructions 16 16...

Отзывы: