
VAN-V07007E
[J7
→
J1000] Replacement Instructions
10/16
J7
J1000
Drive
Function/
Parameter
Parameter
No.
Initial Value
Parameter
No.
Initial Value
Comments
Min. output frequency
n14 1.5Hz E1-09 1.5
Hz
Min. output voltage
n15
12 V *
E1-10
12.0 V *
* Values for a 400 V class drive are double.
Acceleration time 1
n16
10.0 s
C1-01
10.0 s
Deceleration time 1
n17
10.0 s
C1-02
10.0 s
Acceleration time 2
n18
10.0 s
C1-03
10.0 s
Deceleration time 2
n19
10.0 s
C1-04
10.0 s
S-curve at accel. Start
0 (0 s)
C2-01
0.2 s
S-curve at accel. End
0 (0 s)
C2-02
0.2 s
S-curve at decel. start
0 (0 s)
C2-03
0.2 s
S-curve at decel. end
n20
0 (0 s)
C2-04
0.0 s
J7:
Selection parameter (setting 0,1,2, and 3).
Same setting for all conditions.
J1000:
Numerical parameter (time must be set in
seconds). S-curve set separately for each
ride profile section.
Multi speed ref. 1
n21 0.0Hz d1-01 0.00
Hz
Multi speed ref. 2
n22 0.0Hz d1-02 0.00
Hz
Multi speed ref. 3
n23 0.0Hz d1-03 0.00
Hz
Multi speed ref. 4
n24 0.0Hz d1-04 0.00
Hz
Multi speed ref. 5
n25 0.0Hz d1-05 0.00
Hz
Multi speed ref. 6
n26 0.0Hz d1-06 0.00
Hz
Multi speed ref. 7
n27 0.0Hz d1-07 0.00
Hz
Multi speed ref. 8
n28 0.0Hz d1-08 0.00
Hz
Jog frequency
n29 6.0Hz d1-17 6.00Hz
Frequency reference
upper limit
n30 100% d2-01 100.0%
Frequency reference
lower limit
n31 0% d2-02 0.0%
Motor rated current
n32 - E2-01 -.
Depends on the drive capacity
Motor overheat
protection
n33 0 L1-01 1
J7 J1000
n33
→
0 L1-01
→
1
n33
→
1 L1-01
→
2
n33
→
2 L1-01
→
0
Motor protection time
constant
n34 8min L1-02 1.0
min
Set L1-02 = n34 / 8.
Drive cooling fan
operation selection
n35 0 L8-10 0
J7 J1000
n35
→
0 L8-10
→
0
n35
→
1 L8-10
→
1
Terminal S1 function
selection
- -
H1-01
40
The function of S1 is fixed to Fwd Run in
the J7. The equivalent setting in the
J1000 is H1-01=40 (default).