J7
J1000
Drive
Function/
Parameter
Parameter
No.
Initial Value
Parameter
No.
Initial Value
Comments
Memobus slave
address
n70 0 H5-01 1F
J7: set as decimal value
J1000: set as hexadecimal value
Memobus
communication Speed
selection
n71 2 H5-02 3
J7 J1000
n71
→
0 H5-02
→
1
n71
→
1 H5-02
→
2
n71
→
2 H5-02
→
3
n71
→
3 H5-02
→
4
Memobus parity
selection
n72 0 H5-03 0
J7 J1000
n72
→
0 H5-03
→
1
n72
→
1 H5-03
→
2
n72
→
2 H5-03
→
0
Transmission wait time
n73 10ms H5-06 10
ms
RTS flow control on/off
n74 0 H5-07 1
J7 J1000
n74
→
0 H5-07
→
1
n74
→
1 H5-07
→
0
Low speed carrier
frequency reduction
n75 0 L8-38
depends on
drive
capacity
J7 J1000
n75
→
0 L8-38
→
0
n75
→
1 L8-38
→
1
COPY function
selection
n76 rdy o3-01 0
Possible with copy unit or remote
operator.
READ prohibit
selection
n77 0 o3-02 0
Fault History
n78 -
U2-01/02
-
In the J1000 the last current fault and the
last fault can be seen in parameter U2-01
and U2-02
Software Version
n79 -
U1-25/26
-
6.2
J7 and J1000 Differences in Parameter Settings
-
Maximum carrier frequency
J7: n46, max. 10 kHz
J1000: C6-02, max. 15 kHz
-
S-Curve setting
J7: fixed settings
J1000: set in seconds
-
Stall Prevention Level
The stall prevention level during acceleration and constant speed run depends on the duty
mode setting.
J7:
The maximum setting of n56/57 is 200%
J1000:
Heavy Duty, The maximum setting of L3-02 and L3-06 is 150%
Normal Duty, The maximum setting of L3-02 and L3-06 is 120%
VAN-V07007E
[J7
→
J1000] Replacement Instructions
14/16