![YASKAWA VIPA System 200V Скачать руководство пользователя страница 82](http://html.mh-extra.com/html/yaskawa/vipa-system-200v/vipa-system-200v_manual_907131082.webp)
Chapter 4 Serial communication
Manual VIPA System 200V
4-16
HB97E - CPU - RE_21x-2BS03 - Rev. 15/16
Interface communication
The communication happens via the following handling blocks in the OB1:
No.
Designator
SFC 230
SEND
Initialize a send order
SFC 236
SEND-ALL
Send user data
SFC 231
RECEIVE
Initialize a receive order
SFC 237
RECEIVE-ALL
Receive user data
SFC 232
FETCH
Initialize a fetch order
SFC 233
CONTROL
Block for communication control
Cycle OB1:
•
Create SEND and RECEIVE orders for send and receive initialization
•
Create SEND ALL and RECEIVE ALL orders for user data transfer
The following section contains a summary of this blocks.
The SEND block serves the initialization of a send order to a CP.
Please regard that a send order is only executed when the following
conditions are met:
•
the SEND has received a RLO "1"
•
the bit "order in process" in the indicator word has been reset
Name
Declaration
Type
Description
SSNR IN
INT
Interface
number
ANR
IN
INT
Job number
IND
IN
INT
Mode of addressing
QANF
IN
ANY
Pointer to data source
PAFE OUT BYTE
Parameterization
error
ANZW IN_OUT
DWORD Indicator
word
Overview
SFC 230 - SEND
Parameters
Содержание VIPA System 200V
Страница 1: ...VIPA System 200V CPU Manual HB97E_CPU RE_21x 2BS03 Rev 15 16 April 2015 ...
Страница 4: ...Contents Manual VIPA System 200V ii HB97E CPU RE_21x 2BS03 Rev 15 16 ...
Страница 8: ...Safety information Manual VIPA System 200V 4 HB97E CPU RE_21x 2BS03 Rev 15 16 ...
Страница 66: ...Chapter 3 Deployment CPU 21x 2BS03 Manual VIPA System 200V 3 28 HB97E CPU RE_21x 2BS03 Rev 15 16 ...