![YASKAWA VIPA System 200V Скачать руководство пользователя страница 79](http://html.mh-extra.com/html/yaskawa/vipa-system-200v/vipa-system-200v_manual_907131079.webp)
Manual VIPA System 200V
Chapter 4 Serial communication
HB97E - CPU - RE_21x-2BS03 - Rev. 15/16
4-13
Interface parameters
The parameter transfer to the communication processor happens during
runtime by using the SFC 230 with order no. 201. The parameters for the
protocols have to be stored in a DB.
To activate the parameters you have to execute a RESET with SFC 234
after transfer.
General parameters for every channel in use:
Data byte
Type
Designator
Values
Default
0 BYTE
Channel
COM
1
COM 2
1
2
1 BYTE
Mode
MODI_NONE (deactivated)
MODI_1 (Parameter following)
0
81h
0
2 BYTE
Baudrate
BAUDRATE_DEF
BAUDRATE_150
BAUDRATE_300
BAUDRATE_600
BAUDRATE_1K2
BAUDRATE_1K8
BAUDRATE_2K4
BAUDRATE_4K8
BAUDRATE_7K2
BAUDRATE_9K6
BAUDRATE_14K4
BAUDRATE_19K2
BAUDRATE_38K4
BAUDRATE_57K6
00h
01h
02h
03h
04h
05h
06h
07h
08h
09h
0Ah
0Bh
0Ch
0Dh
09h
3 BYTE
DataBits
DATABIT_5
DATABIT_6
DATABIT_7
DATABIT_8
0
1
2
3
3
4
BYTE
Parity
PARITY_NONE
PARITY_ODD
PARITY_EVEN
0
1
3
0
5
BYTE
StopBits
STOPBIT_1
STOPBIT_1_5
STOPBIT_2
1
2
3
1
6
BYTE
FlowControl
FLOW_NONE
FLOW_HARDWARE
FLOW_XON_XOFF
0
1
2
1
7 BYTE
Protocol
PROTOCOL_ASCII
PROTOCOL_STXETX_HTB
PROTOCOL_3964
PROTOCOL_3964R
PROTOCOL_3964_RK512
PROTOCOL_3964R_RK512
01h
02h
03h
04h
05h
06h
01h
Parameter-DB
structure
Содержание VIPA System 200V
Страница 1: ...VIPA System 200V CPU Manual HB97E_CPU RE_21x 2BS03 Rev 15 16 April 2015 ...
Страница 4: ...Contents Manual VIPA System 200V ii HB97E CPU RE_21x 2BS03 Rev 15 16 ...
Страница 8: ...Safety information Manual VIPA System 200V 4 HB97E CPU RE_21x 2BS03 Rev 15 16 ...
Страница 66: ...Chapter 3 Deployment CPU 21x 2BS03 Manual VIPA System 200V 3 28 HB97E CPU RE_21x 2BS03 Rev 15 16 ...