Options
6-
165
Related Constants
Setting Precautions
Always set b1-01 (Reference selection) to 1 (control circuit terminal) when using the AI-14B for three chan-
nels of independent inputs. When this is done, H1-01 to H1-10 (multi-function contact inputs) cannot be set to
2 (Option/Inverter selection).
Using a Digital Reference Board
When using a DI-08 or DI-16H2 Digital Reference Board, set b1-01 (Reference selection) to 3 (Option board).
The DI-16H2 can be used to set a frequency using a 16-bit digital reference. The DI-08 can be used to set a
frequency using a 8-bit digital reference.
Related Constants
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
F2-01
Bi-polar or uni-
polar input
selection
Sets the functions for channel 1 to
3 that are effective when the AI-
14B Analog Reference Board is
used.
0: 3-channel individual (Chan-
nel 1: terminal A1, Channel 2:
terminal A2, Channel 3: termi-
nal A3)
1: 3-channel addition (Addition
values are the frequency refer-
ence)
When set to 0, select 1 for b1-01.
In this case the multi-function
input “Option/Inverter selection”
cannot be used.
0 or 1
0
No
A
A
A
A
A
38FH
AI-14 Input Sel
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO
BUS
Regis-
ter
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vec-
tor
Open
Loop
Vector
2
F3-01
Digital input
option
Sets the Digital Reference Board
input method.
0: BCD 1% unit
1: BCD 0.1% unit
2: BCD 0.01% unit
3: BCD 1 Hz unit
4: BCD 0.1 Hz unit
5: BCD 0.01 Hz unit
6: BCD special setting (5-digit
input)
7: Binary input
6 is only effective when the DI-
16H2 is used.
When o1-03 is set to 2 or higher,
the input will be BCD, and the
units will change to the o1-03 set-
ting.
0 to 7
0
No
A
A
A
A
A
390H
DI Input