![background image](http://html2.mh-extra.com/html/yaskawa/varispeed-f7/varispeed-f7_connection-manual_3213360048.webp)
Inverter SIO Driver
GP-Pro EX Device/PLC Connection Manual
48
Device Setting
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Equipment Settings]. Touch the
External Device you want to set from the diplayed list, and touch [Device].
Flow Control
The communication control method to prevent overflow of transmission and reception
data.
Timeout
Use an integer from 1 to 127 to enter the time (s) for which the Display waits for the
response from the External Device.
Retry
In case of no response from the External Device, use an integer from 0 to 255 to enter how
many times the Display retransmits the command.
Wait To Send
Use an integer from 0 to 255 to enter standby time (ms) for the Display from receiving
packets to transmitting next commands.
Setup Items
Setup Description
Device/PLC Name
Select the External Device to set. Device name is the title of a External Device set with GP-
Pro EX. (Initial value [PLC1])
Series
Display the series of the External Device.
Slave Address
Enter the slave address of the External Device, from 1 to 255 (DEC).
Setup Items
Setup Description