Inverter SIO Driver
GP-Pro EX Device/PLC Connection Manual
22
External Device Settings
To configure communication settings, use the DSPL, DATA/ENTER, Up, or Down key on the digital operator
located on the front of the inverter. Refer to your External Device manual for details.
1
Press the DSPL key to select [PRGM].
2
Press the Up key to display the parameter you want to set.
3
Press the DATA/ENTER key.
4
Press the Up or Down key to display the setting value.
5
Press the DATA/ENTER key.
6
Reboot the External Device.
This completes the setting of the External Device.
Parameter No.
Settings
Setup Description
n03
2
RUN Command Selection
n04
6
Frequency Reference Selection
n153
1
Slave Address Setting (DEC)
n154
2
Baud Rate Selection
n155
0
Parity Selection
n156
10
Transmission Wait Time
n157
0
RTS Control