Inverter SIO Driver
GP-Pro EX Device/PLC Connection Manual
38
External Device Settings
To configure communication settings, use the ENTER, Up, Down, or Shift/RESET key on the digital operator
located on the front of the inverter. Refer to your External Device manual for details.
1
Press the Up key to display [STUP].
2
Press the ENTER key.
3
Press the Up key to display the parameter you want to set.
4
Press the ENTER key.
5
Press the Up, Down, or Shift/RESET key to display the setting value.
6
Press the ENTER key.
7
Reboot the External Device.
This completes the setting of the External Device.
Parameter No.
Settings
Setup Description
b1-01
2
Frequency Reference Selection 1
b1-02
2
Run Command Selection 1
H5-01
01
Node Address Setting (HEX)
H5-02
3
Communication Speed Selection
H5-03
1
Communication Parity Selection
H5-04
3
Stopping Method After Communication Error
H5-05
1
Communication Fault Detection Selection
H5-06
5
Drive Transmit Wait Time
H5-07
1
RTS Control Selection
H5-09
2.0
CE Detection Time