18
6.2
Wiring
Connect the shielded wires to the external terminals on the terminal board in the following
manner.
1. Loosen the terminal screws with a thin-slot screwdriver.
2. Strip the end of the wire (as shown in Fig. 5) and tighten the terminal screws firmly.
3. Confirm that the terminal screws are thoroughly tightened so that the wire will not come
loose.
(Applicable wire core size: 26 to 16 AWG, Tightening torque: 0.22 to 0.25 [N
x
m])
Fig. 5 Sheath Strip Length
Precautions on wire size selection
If a wire is too large, extra pressure will be put on the DI-16H2, resulting in a malfunction. Conversely,
if the wire is too small, a loose connection or disconnection may occur.
長 さ :約 5.5m m
Strip length:
Approx. 5.5 mm