2
-6
Wiring Main Circuit Terminals
Applicable Wire Sizes and Closed-loop Connectors
Select the appropriate wires and crimp terminals from to
Table 2.3
. Refer to instruction manual TOE-C726-2
for wire sizes for Braking Resistor Units and Braking Units.
Table 2.1 200 V Class Wire Sizes
Inverter
Model
CIMR-
Terminal Symbol
Termi-
nal
Screws
Tightening
Torque
(N•m)
Possible
Wire Sizes
mm
2
(AWG)
Recom-
mended
Wire Size
mm
2
(AWG)
Wire Type
G7A20P4
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
M4
1.2 to 1.5
2 to 5.5
(14 to 10)
2
(14)
Power cables,
e.g., 600 V
vinyl power
cables
G7A20P7
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
M4
1.2 to 1.5
2 to 5.5
(14 to 10)
2
(14)
G7A21P5
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
M4
1.2 to 1.5
2 to 5.5
(14 to 10)
2
(14)
G7A22P2
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
M4
1.2 to 1.5
2 to 5.5
(14 to 10)
3.5
(12)
G7A23P7
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
M4
1.2 to 1.5
2 to 5.5
(14 to 10)
5.5
(10)
G7A25P5
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
M5
2.5
8 to 14
(8 to 6)
8
(8)
G7A27P5
R/L1, S/L2, T/L3,
,
1,
2, B1, B2,
U/T1, V/T2, W/T3
M5
2.5
14
(6)
14
(6)
G7A2011
R/L1,
S/L2,
T/L3, , 1, 2,
U/T1,
V/T2, W/T3
M6
4.0 to 5.0
22 to 30
(4 to 3)
22
(4)
B1, B2
M5
2.5
8 to 14
(8 to 6)
-
M6
4.0 to 5.0
22
(4)
22
(4)
G7A2015
R/L1,
S/L2,
T/L3, , 1, 2,
U/T1,
V/T2, W/T3
M8
9.0 to 10.0
22 to 38
(4 to 2)
30
(3)
B1, B2
M5
2.5
8 to 14
(8 to 6)
-
M6
4.0 to 5.0
22
(4)
22
(4)
G7A2018
R/L1, S/L2, T/L3,
,
1, U/T1, V/T2,
W/T3, R1/L11, S1/L21, T1/L31
M8
9.0 to 10.0
30 to 60
(3 to 1)
30
(3)
3
M6
4.0 to 5.0
8 to 22
(8 to 4)
-
M8
9.0 to 10.0
22 to 38
(4 to 2)
22
(4)
G7A2022
R/L1,
S/L2,
T/L3, , 1
U/T1,
V/T2, W/T3, R1/L11, S1/L21, T1/L31
M8
9.0 to 10.0
50 to 60
(1 to 1/0)
50
(1)
3
M6
4.0 to 5.0
8 to 22
(8 to 4)
-
M8
9.0 to 10.0
22 to 38
(4 to 2)
22
(4)